Manual 03554
GECO
Stoichiometric
Woodward
63
Updating Application Programming (.S19 file)
An .S19 file can be downloaded to the circuit board with the user interface
software as follows:
Shut
engine
down.
From any screen, type Alt-D (hold the Alt key and press D at the same time).
An input message at the bottom of the screen will request the password
included with the update software. Contact your GECO distributor for more
information.
Another message will request the pathname of the new .S19 file (example:
c:\geco\9925050.s19).
The new program will then be downloaded to the flash memory.
Fuel Metering/Valve Location Considerations
Access for conduit connection
Space for servicing and repair
Protection from direct exposure to water
Stable mounting surface or bracket; the valve should not be suspended on
plumbing or conduit connections
Avoidance of vibration
Selection of a location that will provide an operating temperature within the
specification range listed in the Components section; avoid the vicinity of
exhaust system components.
Plumbing Considerations
Check the Components section for
valve port fitting sizes, pressure
requirements, and plumbing size.
Thin-wall stainless steel tubing is
recommended.
Flareless
stainless
steel fittings are
recommended.
A manual shut-off valve must be
installed between the pressure source and
the valve for servicing and troubleshooting
(1/4-turn ball valve).
The tubing should include vibration
isolation loops (“pigtails”); these loops also
facilitate installation and servicing of the
valve.
The valve should be mounted as close
to the injection point as possible; lengthy
plumbing runs are more acceptable on the
higher pressure, inlet side of the valve.
Содержание GECO
Страница 8: ...GECO Stoichiometric Manual 03554 vi Woodward...
Страница 20: ...GECO Stoichiometric Manual 03554 12 Woodward Figure 2 12 GECO System for Dual Carburetor Engine...
Страница 65: ...Manual 03554 GECO Stoichiometric Woodward 57...
Страница 66: ...GECO Stoichiometric Manual 03554 58 Woodward Figure 8 2 Wiring for Single Bank...
Страница 67: ...Manual 03554 GECO Stoichiometric Woodward 59...
Страница 68: ...GECO Stoichiometric Manual 03554 60 Woodward Figure 8 3 Wiring for Dual Bank...
Страница 69: ...Manual 03554 GECO Stoichiometric Woodward 61 Figure 8 4 Legend Plate...