Manual 03554
GECO
Stoichiometric
Woodward
41
Screen 2: Modbus Configuration
Mode
: ASCII, RTU, or OFF.
Parity
: EVEN, ODD, or NONE.
Baud
: 1200, 2400, 4800, 9600, or
19200. Choice of possible
communication baud rates.
Address
: 0-247. Modbus slave
address.
Access
: USER, or OPERATOR.
Activity
: YES or NO, this indicates
that the control is currently recognizing communication activity on the RS485
port.
Mem Module
: OK, this indicates that the Modbus memory circuitry is functional.
Screen 3: Engine
Speed
: Engine rpm from magnetic pickup
(MPU) or “G-lead.” (This value defaults to
1350 if the Digital In RUN signal is used).
MAP
: Intake manifold absolute pressure in
pounds per square inch absolute.
TC Upstream
: Pre-catalyst thermocouple
input in degrees F.
TC Downstream
: Post-catalyst
thermocouple input in degrees F.
Control1
: OPEN LOOP, CLOSED LOOP,
CL+ADAPTIVE. These are the air/fuel ratio
control modes.
Control2
: (same).
RunMode
: STOPPED, CRANKING, RUNNING. These are the start sequence
modes. Once the engine reaches idle speed, it should be in the RUNNING mode.
Run Time
: The time, in hours, since the last engine start.
Hour Meter
: The total engine run time since the control was installed.
DC Power
: Power supply voltage to the circuit board.
Screen 3: Manual Operation
ClsdLoopSwtch
: OFF, ON. The position of
the closed loop switch on the circuit board.
Manual Mode
: OFF, ON. This mode can
be activated only while in the OPEN LOOP
control mode. It allows for manual
positioning of the control valves.
Engine
Speed 0 rpm
MAP 10.00 psia
TC Upstream 1020
F
TC Dnstream 1080
F
Control1 OPEN LOOP
Control2 OPEN LOOP
RunMode STOPPED
Run Time 0000:00:00
Hour Meter 0.000
DC Power 13.7 volts
Manual Operation
ClsdLoopSwtch OFF
ManualControl OFF
ModBus Configuration
Mode OFF
Parity NONE
Baud 9600
Address 99
Access USER
Activity OFF
Mem Module
OK
Содержание GECO
Страница 8: ...GECO Stoichiometric Manual 03554 vi Woodward...
Страница 20: ...GECO Stoichiometric Manual 03554 12 Woodward Figure 2 12 GECO System for Dual Carburetor Engine...
Страница 65: ...Manual 03554 GECO Stoichiometric Woodward 57...
Страница 66: ...GECO Stoichiometric Manual 03554 58 Woodward Figure 8 2 Wiring for Single Bank...
Страница 67: ...Manual 03554 GECO Stoichiometric Woodward 59...
Страница 68: ...GECO Stoichiometric Manual 03554 60 Woodward Figure 8 3 Wiring for Dual Bank...
Страница 69: ...Manual 03554 GECO Stoichiometric Woodward 61 Figure 8 4 Legend Plate...