37630 easYgen-3000XT Flash Instruction 

  

w w w . w o o d w a r d . c o m 

Update via USB: 

Continue at Step 6 

Update via Ethernet: 

“Select Device” window 

appears. 
 

Notes!

  

Ensure that the device will  

NOT BE SWITCHED OFF

 during update process 

before you 

click “Next”! 

 
Select you device if not already selected and 
click “Next” 

 

 

Notes!

  

If next window says “Failed”: 
 
In this case the actually entered code is below 
Code Level 5. 
Click “Close” then “Disconnect” in ToolKit window. 
Go back to 

Chapter “Preparations” step 4 and 

login with code for Code Level 5 

 

 

If “Production Identifier Mismatch” window 
appears: 
 
The .scp file you have selected does not fit to the 
hardware of that device. 
Click “Cancel” and  
check the selected file in step 

3

 

 

The update process has now started, and ToolKit transfers the file to the memory of the device. 
easYgen-3000XT with display:  
The device switches off the display. Furthermore, “Ready for operation” relay de-energizes. 
The buttons TEST, STOP, AUTO, MAN and the yellow alarm LED are illuminated 

 

easYgen-3000XT with LEDs (metal housing):  
LEDs “Communication” and “Operation” turn red. Furthermore, “Ready for operation” relay de-energizes. 
 

Released

Содержание EGCP-2 to easYgen-3200XT

Страница 1: ...e is explicitly mentioned as completely finished as described below If the device to be updated is installed into a running genset system it is mandatory that a genset control expert guarantees troubl...

Страница 2: ...ommunicating to other devices PC or laptop computer connected to the device via the preferred interface type and cable Current version of update file scp according to the actual device and the preferr...

Страница 3: ...as wset file on your computer to ensure re storing it later 1 Start ToolKit software 2 Open the appropriate configuration file wtool which fits to your device 3 Click the Connect icon Connection sele...

Страница 4: ...2 Continue with Next Application File Selection window opens 3 Click Browse and select the provided scp file If available select _eth scp or _usb scp with respect to the appropriate interface to whic...

Страница 5: ...apter Preparations step 4 and login with code for Code Level 5 If Production Identifier Mismatch window appears The scp file you have selected does not fit to the hardware of that device Click Cancel...

Страница 6: ...lete and the display is showing home screen Check the firmware version how to check the firmware version is described below b Back panel variant Observe the LEDs When you observe the LEDs have become...

Страница 7: ...itch off the device After about 30 seconds the LEDs will start blinking in turn for about 2 30 minutes Afterwards both LEDs again turn red for a moment DO NOT switch off the device 8 After the device...

Страница 8: ...Language must have the same version If there is any discrepancy there will show an exclamation mark besides the respective version HMI Screen ToolKit screen HMI screen In this case please contact your...

Страница 9: ...r your latest specific settings are still again loaded If not Re load your latest saved settings or execute factory settings Undo temporary safety preparations Re connect all interface connections tha...

Страница 10: ...TIES OF ANY KIND EXPRESSED OR IMPLIED THE ADHERENCE TO THE INFORMATION CONTAINED IN THIS APPLICATION NOTE SHALL BE AT THE USER S OWN RISK WOODWARD EXPRESSLY DISCLAIMS ANY REPRESENTATIONS OR WARRANTIES...

Отзывы: