If a warning, an alarm or any predefined operational state is
present, which is assigned to any of the sixteen LED lamps, the
assigned lamp will illuminate in line with its configuration in ToolKit.
If the horn is enabled by an alarm condition, it may be silenced with
the acknowledge button 4, if this is configured in easYgen's
ToolKit .
A function test of all LEDs may be conducted by pressing the con‐
trol button 3.
5.2 Relay Output
The easYlite-200 device is equipped with an output relay to an
external signaling device/horn.
It can be configured in three ways, with the respective output
dependent upon the:
n
status of the incoming horn signal (RPDO)
n
status of the communication interface failure
n
both.
It is reset as follows:
n
Where set to "Communication failure", the relay is reset auto‐
matically if the the communication bus is ok.
n
Where set to "Horn", it is reset by:
– the acknowledge button, if the genset control configurtion
allows this
– horn acknowledgement on the genset control.
If the genset control has the horn activated, this can be silenced by
pressing the acknowledge button , if the genset control configur‐
tion allows this. This disables the horn of the genset control and
the easYlite-200 output relay. A complete acknowledgement of the
alarm, however, can only be performed on the genset control.
Communication interface failures, which may result in energizing
the output relay, cannot be silenced.
Description
Silencing the horn
Operation
Relay Output