Woodward easYlite-200 Скачать руководство пользователя страница 13

Protective equipment:

n

ESD wrist band

NOTICE!
Damage from electrostatic discharge
All electronic equipment sensitive to damage from

electrostatic discharge, which can cause the con‐

trol unit to malfunction or fail.
– To protect electronic components from static

damage, take the precautions listed below.

1.

Avoid build-up of static electricity on your body by not

wearing clothing made of synthetic materials. Wear cotton or

cotton-blend materials as much as possible because these

do not store static electric charges as easily as synthetics.

2.

Before working on terminals on the control unit, ground your‐

self by touching and holding a grounded metal object (pipes,

cabinets, equipment, etc.) to discharge any static electricity.
Alternatively wear an ESD wrist band connected to ground.

3.

Before any maintenance work on the control unit, ground

yourself by touching and holding a grounded metal object

(pipes, cabinets, equipment, etc.) to discharge any static

electricity.
Alternatively wear an ESD wrist band connected to ground.

4.

Keep plastic, vinyl, and Styrofoam materials (such as plastic

or Styrofoam cups, cigarette packages, cellophane wrappers,

vinyl books or folders, plastic bottles, etc.) away from the

control unit, modules and work area.

5.

Opening the control cover may void the unit warranty. Do not

remove the printed circuit board (PCB) from the control cab‐

inet unless instructed by this manual.

If instructed by this manual to remove the

PCB from the control cabinet, follow these

precautions:

Ensure that the device is completely

voltage-free (all connectors have to be

disconnected).

Do not touch any part of the PCB except

the edges.

Do not touch the electrical conductors,

connectors, or components with conduc‐

tive devices or with bare hands.

When replacing a PCB, keep the new

PCB in the plastic antistatic protective

bag it comes in until you are ready to

install it. Immediately after removing the

old PCB from the control cabinet, place it

in the antistatic protective bag.

Electrostatic discharge

General information

Safety > General Safety Notes

37903A

easYgen Expansion Module | LED Lamp Expansion Module

13

Содержание easYlite-200

Страница 1: ...easYlite 200 Manual LED Lamp Expansion Module easYgen Expansion Module Software Version 1 0 37903A...

Страница 2: ...l Technical Manual Woodward GmbH Handwerkstrasse 29 70565 Stuttgart Germany Telephone 49 0 711 789 54 510 Fax 49 0 711 789 54 101 E mail stgt info woodward com Internet http www woodward com 37903A ea...

Страница 3: ...LED display module with 16 programmable alarm warning and status lamps for which three colors red green yellow can be chosen The data collected by easYgen series controllers are transmitted to the ea...

Страница 4: ...n module All screwable terminal connectors are delivered with plug and jack n Clamp fastener installation material 4x n Installation Procedure Supplement paper with links to the latest edition of Tech...

Страница 5: ...Display and Status Indicators 15 3 Installation 16 3 1 Installation 16 3 2 Terminal allocation 18 3 3 Wiring diagram 19 3 4 Power Supply 19 3 5 Relay outputs 20 3 6 Interfaces 21 4 Configuration 22 4...

Страница 6: ...8 Appendix 31 9 Index 32 Table of contents 37903A easYgen Expansion Module LED Lamp Expansion Module 6...

Страница 7: ...ation that could cause death or severe injuries if not avoided WARNING This combination of symbol and signal word indi cates a possibly dangerous situation that could cause death or severe injuries if...

Страница 8: ...consideration of applicable guidelines and regulations the current and known state of the art as well as our many years of in house experience Woodward assumes no liability for dam ages due to n Fail...

Страница 9: ...e product war ranty n thereby exclude warranty coverage for any resulting damage and n invalidate product certifications or listings Our Customer Service is available for technical information Please...

Страница 10: ...ecifies the personnel qualifications required for the different areas of work listed below n Well trained for electrical installations n Skilled and competent to be aware especially of the local safet...

Страница 11: ...hield neighboring live parts Never bypass a fuse or render it inoperable Always use the correct amperage when changing a fuse Keep moisture away from live parts Moisture can cause short circuits WARNI...

Страница 12: ...tings NOTICE Damage to the control system due to improper handling Disconnecting a battery from a control system that uses an alternator or battery charging device whilst the charging device is still...

Страница 13: ...ctricity Alternatively wear an ESD wrist band connected to ground 4 Keep plastic vinyl and Styrofoam materials such as plastic or Styrofoam cups cigarette packages cellophane wrappers vinyl books or f...

Страница 14: ...ulative required personal protective equipment is detailed below ESD wrist band The ESD electrostatic discharge wrist band keeps the user s body set to ground potential This measure protects sensitive...

Страница 15: ...dicates then an alarm at the genset and or failure of communication with its master easYgen device When a warning alarm or status message is issued at the genset control the horn bit of the genset con...

Страница 16: ...ed For definite values please refer to chapter Chapter 7 1 Technical Data on page 29 Field wiring shall be made with use of cables which have temperature rating not less than 90 C AWG mm AWG mm AWG mm...

Страница 17: ...enlarge it accordingly Ensure that the gasket is placed prop erly if used Ensure that the paper strip is not pinched between gasket and panel to maintain isolation 5 Attach clamp inserts Re install th...

Страница 18: ...C input B 2 5mm2 DC power supply negative input 2 DC input B 2 5mm2 DC power supply positive input 3 GND 0 5mm2 Modbus RS 485 Connect the RS 485 port to RS 485 port of easYgen series controllers It is...

Страница 19: ...ltage Input This device can be used with batteries providing the operating voltage range from 8 to 35 VDC The negative pole of the battery must be grounded The wire between the power supply ter minals...

Страница 20: ...Power supply connection to easyLite 200 No Function Cable Size Description 1 DC input B 2 5mm2 DC power supply negative pole 2 DC input B 2 5mm2 DC power supply positive pole Table 3 Power supply term...

Страница 21: ...n below Fig 8 CAN bus terminals and connection No Function Cable Size Description 6 GND 0 5mm2 CAN bus terminals Note It is recommended that the cable shield be grounded at one end 7 CAN L 8 CAN H Fig...

Страница 22: ...can select one of five actions depending on the actual easYgen device to be taken upon communication failure Warning Shutdown Trip and Stop Trip Indication Below are the sixteen rows for the configur...

Страница 23: ...ts own flashing LEDs Once the configuration is complete the user can print the LED labels by means of the Label print button The following screen opens Fig 11 Label print screen in ToolKit Once printe...

Страница 24: ...ud rate Finally in the fifth menu the bit is set for the relay output If Horn is chosen the relay will be energized upon incoming alarm set in the easYgen device If Com Fail is selected the output is...

Страница 25: ...Stop bit 1 to 2 2 1 or 2 stop bits can be set 4 CAN Baud Rate 0 to 1 0 0 250 kbps 1 125 bps 5 Relay Output 0 to 2 0 0 Audible alarm output Horn 1 Communication fail output 2 Horn or comm fail output T...

Страница 26: ...s is further differentiated by color red green yellow and lighting pattern flashing contin uous The control button 3 is the lamp test button All the lamps on the LED panel will be illuminated yellow u...

Страница 27: ...the communication interface failure n both It is reset as follows n Where set to Communication failure the relay is reset auto matically if the the communication bus is ok n Where set to Horn it is r...

Страница 28: ...nnected in parallel to easYgen s RS 485 Fig 15 or CAN Fig 16 terminals respectively Fig 15 RS 485 communication with the easYgen Fig 16 CAN communication with the easYgen An example application with m...

Страница 29: ...ide according to the EU Directive 2006 66 EC WARNING Batteries can be harmful to the environment Dam aged or unusable batteries must be disposed of in a container specially reserved for this purpose I...

Страница 30: ...cation interface 3 One D type USB interface Case Dimension 185 5mm x 125 5mm x 41 1mm Cutout 166 5mm x 106 5mm Working Conditions Temp 25 70 C Relative Humidity 20 93 Storage Conditions Temp 25 70 C P...

Страница 31: ...communication failure Check the RS 485 negative positive connection Check whether the RS 485 converter works correctly or not Check the Module address settings If the problem still cannot be solved pl...