Manual 37390B
easYgen-1000 Series - Genset Control
Page 44/57
© Woodward
Connect in application mode ...
{0} {1o} {1oc}
{2oc}
Terminal Description
A
max
Term. Com.
A
B
Form A, separated contacts
Type
Ø
9
9
9
9
36
37
Relay output [R6]
[BM] -
LogicsManager
SW
2.5 mm²
[0CB] -
SW
[1CB] -
SW
[2CB] -
SW
9
9
9
9
38
39
Relay output [R7]
[BM] -
LogicsManager
SW
2.5 mm²
[0CB] -
Command: open GCB
#1
[1CB] -
Command: open GCB
#1
[2CB] -
Command: open GCB
#1
9
9
9
9
40
41
Relay output [R8]
[BM] -
LogicsManager
SW
2.5 mm²
[0CB] -
LogicsManager
SW
[1CB] -
LogicsManager
SW
[2CB] -
Command: close MCB
#1
9
9
9
9
42
43
Relay output [R9]
[BM] -
LogicsManager
SW
2.5 mm²
[0CB] -
LogicsManager
SW
[1CB] -
LogicsManager
SW
[2CB] -
Command: open MCB
#1
9
9
9
9
44
45
Relay output [R10]
[BM] -
LogicsManager
SW
2.5 mm²
[0CB] -
LogicsManager
SW
[1CB] -
Command: close GCB
#1
[2CB] -
Command: close GCB
#1
9
9
9
9
46
47
Relay output [R11]
[BM] -
Ready for operation
LogicsManager
(closed in normal operation
state)
#1
2.5 mm²
[0CB] -
[1CB] -
[2CB] -
LogicsManager
..using the function
LogicsManager
it is possible to freely program the relays
SW-switchable via the software, [#1]-type 1 (N.O./make contact)
Table 6-22: Relay outputs - terminal assignment, part 1