Approved Venting/Chimney Configurations
Note: Each additional elbow reduces the maximum rise by 3 feet.
Refer to the Simpson-Dura Vent instructions regarding installation
of your Direct-Vent system.
MANUFACTURED HOUSING INSTALLATION
The Franklin Gas Fireplace may be installed in Manufactured
Housing with the following supplemental requirements:
(1)
The appliance must be securely bolted to the floor with steel
straps secured to the leg bolts and to the floor with minimum
1/4” lag bolts. Contact Woodstock Soapstone Company for
steel straps.
(2)
The appliance must be grounded to the manufactured home
trailer frame with a No. 8 (minimum) solid conductor.
ALL VENT CLEARANCES MUST BE MAINTAINED.
CHECK YOUR VENT CLEARANCES AGAINST THE
ILLUSTRATIONS ON PAGE 9.
MINIMUM AND MAXIMUM DISTANCES
• Maximum vertical rise .....................................................24'
• Minimum chimney inside diameter ..................................6”
• Required .............................Existing chimney must be lined
21' Max.
P
!
Illustration 6.7
Illustration 6.6
Vertical installations only