CLEARANCE INSTALLATION DIAGRAMS
B
C
C
A
B
2) Parallel Installation, Single Wall Pipe, Back Vent
WITH REAR HEAT SHIELD & PIPE SHIELD ATTACHED
A. Back of stove shield to wall = 8.5”
D. Side of stove to wall = 26”
B. Back of pipe shield to wall = 8.5”
E. Side of pipe to wall = 35.5”
C. Above pipe to ceiling
= 18”
9
NO HEAT SHIELD
A. Back of stove to wall
= 14” D. Side of stove to wall = 26”
B. Back of pipe to wall
= 15.5” E. Side of pipe to wall = 35.5”
C. Above pipe to ceiling
= 18”
1) Parallel Installation, Single Wall Pipe, Top Vent
A
E
E
D
D
NO HEAT SHIELD
A. Back of stove to wall
= 23.5” D. Side of stove to wall = 26”
B. Back of pipe to wall
= 15.5” E. Side of pipe to wall = 35.5”
C. Above pipe to ceiling
= 18”
WITH REAR SHIELD & PIPE SHIELD ATTACHED
A. Back of stove shield to wall = 18”
D. Side of stove to wall
= 26”
B. Back of pipe shield to wall = 10” E. Side of pipe to wall
= 35.5”
C. Above pipe to ceiling
= 18”
Note: On rear vent applica-
tions, hearth protection must
extend under elbow or hori-
zontal section of pipe, and
extend 2 inches beyond each
side of horizontal pipe.