background image

Stove and Pipe Shields:

Clearances can be reduced by attaching an approved heat shield, Part R-997 and pipe shield,

part #W-413. Woodstock Soapstone Company carries heat shields specifically designed for this

stove. When using one or both of these shields, 

clearance is measured from the back of the

shield to the combustible wall

. The clearance behind the stove can be reduced to 8.5 inches.

The clearance behind the pipe can be reduced to 6 inches.

Clearance Table:

The Absolute Steel Hybrid can be installed at a 14” clearance with no additional protection, if

the stove pipe is top vented, and the provided shield is installed on the inside of the rear flue

cover plate. To further reduce the rear clearance to 8.5”, you must attach an approved rear heat

shield and a 24” pipe shield.

*

These clearance reductions meet or exceed requirements of NFPA  211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel

Burning Appliances. Approved NFPA 211 clearance reduction methods 

DO NOT

allow stove clearances to be reduced below 12”.

NFPA WALL SHIELDS MUST BE SIZED TO NFPA 211 SPECIFICATIONS. CONSULT NFPA 211 AND A QUALIFIED EXPERT

BEFORE IMPLEMENTING THESE REDUCTIONS. 

The only approved method allowing for a rear stove clearance less than 12” is the Approved Rear Heat Shield (#R-997) provided by

Woodstock Soapstone Co. If your installation requires the use of the Approved Rear Heat Shield call 1-800-866-4344.

• These clearances apply to walls, ceilings, furniture and other combustibles.

• The 24” Vertical Stack Shield attaches to the back of the stove pipe and prevents excess heat from being radiated from the pipe.

Heat shield protection is only required for the first 24” of vertical connector pipe. 

•  At least 30” is required from the front of the stove to combustibles (such as curtains, wall hangings, and furniture).

The same clearances from your stove and stove pipe apply to both fireplace and freestanding installations.  Be

particularly careful to check clearances to a wood mantel or a wood fireplace facade.  You must maintain a 30” clearance

to an unprotected wood mantel. See Fireplace Installations on Page 5.

8

Rear heat shield & pipe

shield reduce required

rear clearance to 8.5”

Clearance Table For Model 211 Absolute Steel 

Type of Installation

u

Top Vent Rear Vent Rear Vent with elbow Stove Sides

Stoveck

Pipe goes

Type of protection

q

Stove Back Stovepipe

No Protection

14”

14”

23.5”*

15.5”

26”

With 24” Pipe Shield   

18”

10”

26”

With Approved Rear Heat Shield,

8.5”

18”

10”

*

16”

24” Pipe Shield & Side Shield 

1

/

2

” thick Masonry Against 

12”

12”

20”

12”

13”

Combustible Wall

*

1

/

2

” thick Masonry with 

12”

12”

14”

6”

12”

1” ventilated airspace

*

24 ga. sheet metal with 

12”

12”

14”

6”

12”

1” ventilated airspace

*

1/2” thick non-combustible

12”

12”

14”

6”

12”

insulation board with 1” airspace

*

Clearance from

stove back, top

vent, with

stove pipe

which goes

straight up

Clearance

from stove

back and pipe,

which goes

straight back

Clearance from stove back

and vertical single wall

connector pipe 

with elbow at stove back

See note below regarding NFPA

211 clearance reduction methods

and implementation.
See note below regarding NFPA

211 clearance reduction methods

and implementation.
See note below regarding NFPA

211 clearance reduction methods

and implementation.
See note below regarding NFPA

211 clearance reduction methods

and implementation.

*

Controlling clearance

Содержание 211 Navajo Hybrid

Страница 1: ...tringent but they should be followed They were designed to protect you your home and the environment Improper installations are a major cause of serious fires Failure to follow instructions may result in property damage bodily injury or death Before installing a woodstove check your local building codes and any requirements established by your insurance company You may need a local building permit...

Страница 2: ...ld not be less than the flue collar size Note For flues that exceed the recommended area a stainless steel chimney liner is recommended Height Requirements The chimney must extend 3 ft above the point where it passes through the roof and must also be 2 ft higher than any roof surface or obstruction within 10 feet measured horizontally of the chimney You should check your local building codes for a...

Страница 3: ...nimum 5 8 thick clay liner should be cemented in place and run from the outer surface of the brick to the inner surface of the chimney See Diagram B Above C There are also UL Listed kits available that are specifically designed for passing through a combustible wall For more information on these kits please contact Woodstock Soapstone Company Please note there are several UL listed wall pass throu...

Страница 4: ...n 2 Pitched Cathedral Ceiling through the roof Determine where the stove will be placed Be sure all clearance requirements are satisfied Choose the appropriate support for your installation support box or roof support Use a plumb line to locate the support in the ceiling above Cut the appro priate sized hole in the ceiling and install the necessary framing to secure the sup port Install the suppor...

Страница 5: ... circulate into the room The preferred method for installing a stove in front of a fireplace is by running a stainless steel flex liner down the chimney connecting it to the stove at the fire place Chimneys with large flues should be relined to achieve proper draft If the chimney does not have flue tiles or if the tiles are cracked or compromised an addi tional insulating material must be used It ...

Страница 6: ...in terms of R value K value or C value To convert K or C value to R value use the following formulas K to R R 1 K x T Thickness of the alternate material C to R R 1 C Once alternate materials have been converted to R values the values of multiple layers can be added to determine the combined protection If the overall R value meets or exceeds the specified 39 then the materials are acceptable DO NO...

Страница 7: ... Rear Heat Shield Pipe Shield A 18 x 1 414 12 25 22 5 6 A 66 2 WALL PROTECTION The Model 211 Absolute Steel Hybrid stove has been tested to UL stan dards for clearances to combustible walls The minimum clearances to unprotected walls are as follows Minimum clearances with no heat shields to unprotected combustible walls From the back 14 From the sides 26 DO NOT ASSUME THAT A WALL IS NOT COMBUSTIBL...

Страница 8: ...excess heat from being radiated from the pipe Heat shield protection is only required for the first 24 of vertical connector pipe At least 30 is required from the front of the stove to combustibles such as curtains wall hangings and furniture The same clearances from your stove and stove pipe apply to both fireplace and freestanding installations Be particularly careful to check clearances to a wo...

Страница 9: ... to wall 35 5 C Above pipe to ceiling 18 1 Parallel Installation Single Wall Pipe Top Vent A E E D D NO HEAT SHIELD A Back of stove to wall 23 5 D Side of stove to wall 26 B Back of pipe to wall 15 5 E Side of pipe to wall 35 5 C Above pipe to ceiling 18 WITH REAR SHIELD PIPE SHIELD ATTACHED A Back of stove shield to wall 18 D Side of stove to wall 26 B Back of pipe shield to wall 10 E Side of pip...

Страница 10: ...pproved Double Wall Connector Pipe C Pipe to corner 17 min Approved Double Wall Connector Pipe 4 Corner Installation Double Wall Pipe Back Vent C TOP VENT Your stove comes with a rear heat shield attached Do not remove the rear heat shield it provides extra protection in corner installations and also allows for installa tion closer to combustible walls than would would be possible with no shield W...

Страница 11: ...Having outside air for combus tion is a requirement for all woodburning stoves in the state of Washington and is recommended for woodstoves in super tight new construction Tie Downs The stove must be attached to the floor This is to prevent tipping in the event the home is moved We can provide tie downs for our stoves at no extra charge Spark Arrestor The chimney cap must have a spark arrestor scr...

Страница 12: ... the four mounting bolts are longer to accommodate this shield and are diagonally opposite each other Remove the 2 hex nuts from these longer bolts using a 7 16 wrench or socket Remove the shield and set the shield and nuts aside for reuse 2 Remove the 4 mounting bolts from the cover plate and transfer the cover plate to the top of the stove Install the 2 longer bolts diagonally opposite from each...

Отзывы: