P1-DC3: #35123
Rev 5.2/12-21
12
Performing Inspections and Tests
• Follow the
.
•
Examine air filters regularly
and service when needed.
Service the 2 air filters whenever a bowl contains
liquid or other contaminates, or an element
appears dirty (see “A
IR
F
ILTER
M
AINTENANCE
” in
).
•
Make sure
notification
buzzer can be
heard over noise
at operator
position.
Make sure the notification buzzer is clearly
audible at the maximum distance between the
operator and the lifter, despite any barriers or
obstacles.
1,
2
Checking the 12-Volt Battery
Always check battery
energy before every lift.
While the lifter is powered up, a battery gauge on the LCD
screen displays the current energy level.
3, 4
• If battery energy is in the red range, discontinue lifter
use and charge the battery (see
).
• If battery energy continues to decrease and you try to
attach the lifter to a load, the notification buzzer will
sound continuously and the LCD screen will display “Lockout (low 12V battery)”, along
with a diagnostic code (see
). In this case, you must
charge the battery in order to continue using the lifter.
1..... Maximum buzzer volume is 95 dBA at 2' [60 cm]. If CE or UKCA Standards apply, consult EN 7731 to make sure the notification buzzer is
compliant.
2..... The
provides a convenient opportunity to check this.
3..... If the lifter remains in “Power Save” mode for a long time, the pump will run periodically to test the battery.
4..... If the battery charger is connected to an AC power source, the reading on the battery gauge will not be accurate and “Replace 12V battery?”
may appear on the LCD screen, because the system cannot accurately evaluate the battery.
OPERATION
Содержание 98720
Страница 2: ...P1 DC3 35123 Rev 5 2 12 21 2 ...
Страница 6: ...P1 DC3 35123 Rev 5 2 12 21 4 SPECIFICATIONS Note A standard P11104DC3 is shown ...
Страница 42: ...P1 DC3 35123 Rev 5 2 12 21 40 ...
Страница 43: ...Rev 5 2 12 21 P1 DC3 35123 41 ...