Figure 32 - External Regulator with Vent Pointing Down 

(Propane/LP Only)

FIREPLACE INSTALLATION 

CHECK GAS TYPE

Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install fireplace. See dealer where 
you purchased the fireplace for proper fireplace for your gas type or conversion kit.

INSTALLING GAS PIPING TO FIREPLACE / BURNER SYSTEM LOCATION

INSTALLATION ITEMS NEEDED

Before installing fireplace and burner system, make sure you have the items listed below.
• External regulator (supplied by installer) 

•  Piping (check local codes)

• Sealant (resistant to propane/LP gas)

• Equipment shutoff valve*

• Test gauge connection*

• Sediment trap (recommended)

• Tee joint

• Pipe wrench

• approved flexible gas line with gas connector (if allowed by local codes — not provided)
* A CSA design-certified equipment shutoff valve with 

1

/

8

" NPT tap is an acceptable alternative to test gauge connection.

Purchase the CSA design-certified equipment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce incoming 
gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do not reduce incoming gas 
pressure, burner system regulator damage could occur. Install external regulator with the vent pointing down as shown in

 Figure 

32.

Pointing the vent down protects it from freezing rain or sleet.

External 

Regulator 

100 lb. (min) 

Propane/LP 

Supply Tank 

Vent Pointing 

Down

When using copper or flex connectors use only fittings approved 
for gas connections. The gas control inlet is 

3

/

8

" NPT.

A  qualified  installer  or  service  person  must 
connect appliance to gas supply. Follow all 
local codes. 

WARNING

For  propane/LP  units,  never  connect  fireplace  directly  to  the  propane/LP  supply.  This 
burner system requires an external regulator (not supplied). Install the external regulator 
between the burner system and propane/LP supply. 

CAUTION

Use  only  new  black  iron  or  steel  pipe.  Internally 
tinned copper or copper tubing can be used per 
National  Fuel  Code,  section  2.6.3,  providing  gas 
meets hydrogen sulfide limits, and where permitted 
by local codes. Gas piping system must be sized 
to provide minimum inlet pressure (listed on data 
plate) at the maximum flow rate (BTU/hr). Undue 
pressure loss will occur if the pipe is too small.

CAUTION

24

25

Содержание DV32CV

Страница 1: ...ppliance phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire WARNING Improper installation adjustment alteration services or maintenance can cause injury o...

Страница 2: ...allation 30 Electrical Wiring 28 Installation Precautions 13 Installation Planning 14 Rear Wall Vent Installation 17 Horizontal Termination Configuration 19 Below Grade Installation 21 Vertical Throug...

Страница 3: ...BON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the flu with headaches diz ziness and or nausea If you have these signs the fireplace may not have been installed properl...

Страница 4: ...own cycle Similar noises are found with your furnace heat exchanger or car engine IMPORTANT PLEASE READ THE FOLLOWING CAREFULLY It is not unusual for gas fireplace to give off some odor the first time...

Страница 5: ...draw all combustion air from outside of the dwelling through the vent pipe CODE APPROVAL FIREPLACE HEATERS in the USA and Canada as follows These appliances have been listed by OMNI and found to compl...

Страница 6: ...found Do not install any unit with damaged incomplete or substitute parts Check your packing list to verify that all listed parts have been received You should have the following Fireplace Firebox an...

Страница 7: ...raised on a platform of an appropriate height When the firebox is installed directly on carpeting tile or other combustible material other than wood flooring the firebox shall be installed on a metal...

Страница 8: ...PRE INSTALLATION INFORMATION 8 Figure 3 Fireplace Dimensions Right side view Front view Top view 23 25 14 7 5 8 75 23 25 7 2 25 25 25 25 10 5 26 8 33 36 25 2 25 27 32 36 25 44 25 43...

Страница 9: ...__ __ __ __ __ __ _ _ _ _ _ _ __ to opening COVERING FACE Firebox framing can be built before or after the appliance is set in place Construct firebox framing following Figure 2 and the chart below fo...

Страница 10: ...Woodbridge Foreplace is not respon sible Figure 5 Covering Fireplace face allow for or glass door removal A 1 4 reveal must be provided all the way around the fireplace opening NON COMBUSTION MATERIA...

Страница 11: ...OMBUSTIBLES MANTEL CLEARANCES NOTE The combustible area above the facing must not protrude more than 3 4 from the facing If it does it is considered a mantel and must meet the mantel requirements list...

Страница 12: ...SHING MATERIAL NOTE Any remote wiring i e remote control wall switch and optional fan must be done prior to nal nishing to avoid costly reconstruction INSTALLATION INFORMATION Only noncombustible mate...

Страница 13: ...NG 13 1 Clearance Is Acceptable at the Outside Wall until Flue Pipe Goes Through Nearest Wall Figure 7 Combustible Clearances for Vent Pipe A Minimum of 4 Clearance to the Top Is Required Along Horizo...

Страница 14: ...he attic additional pipe and elbows will be required You may use a chase with a vent termination with exposed pipe on the exterior of the house See Installing Vent System in a Chase below If pipe is e...

Страница 15: ...extend a minimum of 24 610mm above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18 457mm As specified in CAN CGA B149 Installati...

Страница 16: ...ne to the bottom of the graph 3 Select the indicated dimension and position the fireplace in accordance with same Example If the vertical dimension from the floor of the fireplace is 11 3 4m the horiz...

Страница 17: ...ree locking lugs indentations These lugs will slide straight into matching slots on the male end of adjacent pipes and fittings Push the pipe sections together and twist one section clockwise approxim...

Страница 18: ...ll thimble over the vent pipe before connecting the horizontal run to the vent cap See Figure 16 6 Carefully move the fireplace with vent assembly attached toward the wall and insert the vent pipe int...

Страница 19: ...hat minimizes the number of offsets and horizontal vent length The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace or the top of the Transition Elbow...

Страница 20: ...he vent graph page 16 the maximum and if a 90 elbow is required in the horizontal vent it must In Figures 20 and 21 Dimension A plus B must not be greater The maximum number of 45 elbows permitted per...

Страница 21: ...learance Ground Window Well Gravel Drain Foundation Wall Firestop Foundation Recess Watertight Seal Around Pipe Sheet Metal Screws Wall Screws Snorkel Do not back fill around snorkel Aclearanceofatlea...

Страница 22: ...is 270 See Figure 26 The minimum height of the vent above the high est point of penetration through the roof is 2 610mm 1 2 3 4 1 2 3 4 Support Straps Every 3 Example Elbow 1 90 Elbow 2 45 Elbow 3 45...

Страница 23: ...x101 2 267mm x 267mm inside dimensions as shown in Figure 12 page 17 using framing lumber the same size as the ceiling joist If the area above the ceiling is an insulated ceiling or a room nail fires...

Страница 24: ...g Support Box Installation Figure 31 Installed Cathedral Ceiling Support Box CATHEDRAL CEILING INSTALLATION IMPORTANT Review all information on previous page before planning this installation Cathedra...

Страница 25: ...ncoming gas pressure You must reduce incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming gas pressure burner system regulator damage could occur Install external r...

Страница 26: ...aps moisture and contaminants This keeps them from going into the burner system gas controls If sediment trap drip leg is not installed or is installed wrong burner system may not run properly Figure...

Страница 27: ...to reseal Do not overtorque Check test points for gas leaks 6 The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that...

Страница 28: ...roperly Longer length of wire is permitted if the wire is made out of larger gauge diameter wire Always check with local code Figure 35 Wiring Diagram for Wall Switch THE WALL SWITCH OR WALL THERMOSTA...

Страница 29: ...e controls in the lower cavity surface and be careful to not damage and controls in the lower cavity of the fireplace Completely remove the glass frame and set aside GLASS REMOVAL 2 Lean the top of th...

Страница 30: ...the entire Do not use the entire bag of material to cover Ember Materiall Figure 37 Placement of Ember Material IMPORTANT Avoid ports when ember material to ensure that See Figure 40 below IMPORTANT...

Страница 31: ...later Too much ember material can disturb the flame and cause sooting on the glass or logs Figure 43 Log Set complete assembly 4 Place the left cross log 6 as shown Figure 41 Placing Left Cross Log 5...

Страница 32: ...r shall be replaced with the manufacturer s barrier for this appliance Any safety screen guard or barrier removed for servicing the appliance must be replaced prior to operating the appliance WARNING...

Страница 33: ...d slide downward Make sure the Side Panel is secured properly Repeat with opposite side panel into the opening angling in at the top to rest on the face support as shown STEP 4 Support the Air Flow Pa...

Страница 34: ...34 OPERATING INSTRUCTIONS your LIGHTING Turn off wall switch or thermostat Turn off all electric power to the appliance if service to be performed Open access panel...

Страница 35: ...OPERATING INSTRUCTIONS continued 35 Open clockwise clockwise Turn manual shutoff valve counterclockwise to OPEN position Close access panel...

Страница 36: ...rner are not covered with ember the center of the burner Replace logs material If the back holes are clear add more material to Air shutter for Natural Gas is factory set for optimum flame appearance...

Страница 37: ...mount to the glass and wipe off with a damp cloth After all maintenance has been completed re install glass door LOGS Leave logs installed in the fireplace for cleaning Vacuum surface of the logs with...

Страница 38: ...safety to drop out A Inner vent pipe leaking exhaust gases back into system B Horizontal vent improperly pitched C Improper vent cap installation A Check switch and wire for proper connection Place ju...

Страница 39: ...ILLUSTRATED PARTS LIST 11 1 2 3 4 5 6 7 8 LOG SET P N M100514 39...

Страница 40: ...ination 58DVA VCH 3 4 6 Pipe Length 58DVA 06 3 4 9 Pipe Length 58DVA 09 3 4 12 Pipe Length 58DVA 12 3 4 24 Pipe Length 58DVA 24 3 4 36 Pipe Length 58DVA 36 3 4 48 Pipe Length 58DVA 48 4 4 8 1 2 Pipe E...

Страница 41: ...cturer 6 PCB PCB REMOTE CONTROL OPTIONAL 1 7 RCB R RCB R REMOTE RECEIVER OPTIONAL 1 8 C100072 C100072 FLEX CONNECTOR WITH SHUTOFF VALVE 1 DV32CVN DV32CVP 9 D300025 D300027 ORIFICE AIR MIXER 1 10 W5000...

Страница 42: ...127 6...

Страница 43: ...Elbows Quantity 45 Elbows ALTITUDE Feet Above Sea Level Was Stove Derated Yes No If Yes To What Orifice Size Unusual Structure Near Vent Inside Corner Trees Shrubs Other Termination Please Describe Pr...

Страница 44: ...w limitations on how long an implied warranty lasts or do not allow exclusion of indirect damage those limitations of exclusions may not apply to you You may also have additional rights not covered in...

Отзывы: