4.3
ELECTRICAL CONNECTIONS
Electrical installations should only be carried out by suitably
qualified and
certified electricians
.
If in doubt on any issue relating to the electrical
connections on the appliance contact WES Technical Support or your Local
Dealer for guidance before carrying out any connections.
The ECOMPACT boiler must be supplied with a 230V 50 Hz electrical supply via a two pole
isolation switch rated for Overvoltage Category III and protected with a 6A circuit breaker. Also,
the unit shall have a 30mA RCD installed into the mains supply. It is recommended that a power
isolation switch is located adjacent to the boiler to isolate the power during servicing and
maintenance but also out of the reach of children and to prevent accidental turning off of the
mains power.
Only authorized WES personnel may open the control panel on the boiler. Any
interference with the wiring in the control panel will invalidate the warranty. The
boiler and complete plumbing system must be adequately earthed and bonded in
accordance with local Building Regulations and Bye- Laws.
ECOMPACT 15
Page 14
Installation & Assembly
© Wood Energy Solutions
Room thermostats shall be supplied/controlled by safety extra low voltage.
Brown - Time Clock Control Live
Black – Permanent Live
Blue – Neutral
Green / Yellow - Earth