![WoMaster LoRa LC144 Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/womaster/lora-lc144/lora-lc144_user-manual_994005034.webp)
2.Group member of Each
Group Net (for LM100 )
Each bit present Modbus ID
number
HEX, Big Endian
40118
AES Enable
R/W
1:Enable, 0
:
Disable
40119
AES Key
R/W
16 bytes , HEX, Big Endian
40134
Model Name
R/O
16 bytes , HEX, ASCII Code
40142
SN
R/O
16 bytes, HEX, Big Endian
40150
Timeout response time
R/W
2 bytes, Unit:Second
LM only, HEX, Big Endian
40161
RSSI
R/O
2byte, HEX, Big Endian
40162
SNR
R/O
2byte, HEX, Big Endian
40171
Firmware version
R/O
16byte , HEX, Big Endian
40179
Reset
W/O
2byte , HEX, Big Endian
LC144 A/O Log Register (Latest setting for output channel register )
40301
Log: Voltage Output Value
R/O
2 bytes, Unit
:
0.001V
HEX, Big Endian
40302
Log: Current Output Value
R/O
2 bytes, Unit
:
0.001mA
HEX, Big Endian
40303
Log: PWM 5V Output
Frequency
R/O
2 bytes, HEX, Big Endian
40304
Log: PWM 5V Output
Duty Cycle
R/O
2 bytes, HEX, Big Endian
40305
Log: PWM OC Output
Frequency
R/O
2 bytes, HEX, Big Endian
40306
Log: PWM OC Output
Duty Cycle
R/O
2 bytes, HEX, Big Endian
LC144 A/IO Register
41017
CH0 Voltage Input
R/O
2 byte, Unit
:
0.001V
HEX, Big Endian
41002
CH1 Current Input
R/O
2 byte, Unit
:
0.001mA
HEX, Big Endian
41019
CH2 Voltage Input
R/O
2 byte, Unit
:
0.001V
HEX, Big Endian