Electronic motor starter with reversing function

For  additional  information,  please  refer  to  the 
corresponding  documentation  of  the  relevant 
product a

www.woehner.de/en/

 

Short description 

The network-capable 3-phase hybrid motor starter with re-
versing function and current monitoring provides the follow-
ing functions: 
 
– Forward running 
– Reverse running 
– Motor overload protection 
– Engine lock protection 
– Electronic short-circuit protection C14 
– Galvanical interruption 
– Current measurement 
– Voltage measurement 
– Power measurement 
– Connection to IO-Link-systems 
 
The amount of cabling required is reduced to a minimum 
by the internal locking circuit and the load wiring. 

1. 

Content of the EU Declaration of 
Conformity 

Manufacturer: Wöhner GmbH & Co. KG, 
Mönchrödener Str .10, 96472 Rödental, Germany 
 

Product designation 

Part No. 

MOTUS

®

C14 Connect 2,6 A, Panel 

36243 

MOTUS

®

C14 Connect 2,6 A, 30Compact 

36244 

MOTUS

®

C14 Connect 2,6 A, 60Classic 

36245 

MOTUS

®

C14 Connect 2,6 A, CrossBoard 

36246 

MOTUS

®

C14 Connect 6,6 A, Panel 

36247 

MOTUS

®

C14 Connect 6,6 A, 30Compact 

36248 

MOTUS

®

C14 Connect 6,6 A, 60Classic 

36249 

MOTUS

®

C14 Connect 6,6 A, CrossBoard 

36250 

MOTUS

®

C14 Connect Plus 2,6 A, Panel 

36255 

MOTUS

®

C14 Connect Plus 2,6 A, 30Compact  36256 

MOTUS

®

C14 Connect Plus 2,6 A, 60Classic 

36257 

MOTUS

®

C14 Connect Plus 2,6 A, CrossBoard  36258 

MOTUS

®

C14 Connect Plus 6,6 A, Panel 

36259 

MOTUS

®

C14 Connect Plus 6,6 A, 30Compact  36260 

MOTUS

®

C14 Connect Plus 6,6 A, 60Classic 

36261 

MOTUS

®

C14 Connect Plus 6,6 A, CrossBoard  36262 

 
The above mentioned product conforms with the most im-
portant requirements of the following directive(s) and their 
modification directives: 
 
2014/35/EU  

 

Low Voltage Directive 

2014/30/EU 

 Electromagnetic  Compati-
bility Directive (EMC) 

IEC / EN 60947-4-2  

Product standard 

2.  Safety Notes 

2.1 Installation notes 
• 

When working on the device, observe the national safety 

and accident prevention regulations. 

• 

Disregarding these safety regulations may result in death, 

serious personal injury or damage to equipment. 

• 

During  operation,  parts  of  electrical  switching  devices 

carry hazardous voltages. 
 

• 

This device may only be commissioned, installed or retro-

fitted by an electrically skilled person. 

• 

Before working on the device, disconnect the power. 

• 

Protective covers must not be removed when operating 

electrical switching devices. 

• 

Keep the product documentation in a safe place. 

• 

Do not subject the device to mechanical and/or thermal 

loads that exceed the specified limits. 

• 

To  protect  the  device  against  mechanical  or  electrical 

damage, install it in a suitable housing with an appropriate 
degree  of  protection  of  at  least  IP54  in  accordance  with 
IEC/EN 60529. 

• 

Install the device according to the instructions in the in-

stallation instructions. 
Access to circuits within the device is not permitted. 

• 

Do not repair the device yourself; replace it with an equiv-

alent device. Repairs may only be performed by the manu-
facturer. The manufacturer is not liable for damage result-
ing from noncompliance. 

• 

You will find the safety-relevant data in this documenta-

tion and the certificates. 

• 

Only use power supply units with safe isolation with 

SELV / PELV voltage in accordance with 
EN 50178 / VDE 0160 (SELV / PELV). This prevents short 
circuits between primary and secondary sides. 

• 

The device must be operated in a closed control cabinet! 

• 

Observe the minimum permissible load current in safety-

related applications: 
2.6 A devices: ≥ 100 mA 
6.6 A devices: ≥ 100 mA 

Area of application 
• 

This is a product for environment A (industry). The device 

can cause unwanted radio interference if used in Class B 
environments  (household).  In  this  case,  the  user may  be 
obligated to take the necessary precautionary measures 

3.  UL notes 

WARNING: Risk of electrical shock and fire 

The opening of the branch-circuit protective device may be 
an indication that a fault current has been interrupted. 
To reduce the risk of fire or electric shock, current-carrying 
parts and the other components of the controller should be 
examined and replaced if damaged. 
Failure to follow instructions can result in death, serious in-
jury, or equipment damage. 

NOTE 

The device is designed for use with a "low voltage, limited 
energy, isolated power supply". 
For use with a "low voltage, limited energy, isolated power 
supply" use copper cables approved to at least 75 °C. 
 
Suitable for use on a circuit with a maximum of 100 kA rms 
symmetrical amperes and ≤ 480 V. 
FLA 2,6 A (480 V AC), 6,6 A (480 V AC). 

 

 

Содержание 36255

Страница 1: ...Deutsch Stand 11 2020 1 MOTUS C14 ...

Страница 2: ...ngsfrei Entfernen Sie während des Betriebs keine Schutzabde ckungen von elektrischen Schaltgeräten Bewahren Sie die Produktdokumentation auf Setzen Sie das Gerät keiner mechanischen und oder thermischen Beanspruchung aus die die beschriebenen Grenzen überschreitet Bauen Sie das Gerät zum Schutz gegen mechanische oder elektrische Beschädigungen in ein entsprechendes Gehäuse mit einer geeigneten Sch...

Страница 3: ...asten Sie den elektronischen Motorstarter auf das je weilige Sammelschienensystem 30Compact 60Classic o der direkt auf das CrossBoard 1 Sammelschienenadapter 30Compact 2 Sammelschienenadapter 60Classic 3 Tragschienenadapter 4 Elektronikbaustein 5 CrossBoard 7 Anschluss Bild 3 Die Standard Verbindung wird über einen 16 poligen Steckverbinder realisiert Schließen Sie die Leitungen an den Steuersteck...

Страница 4: ... senkrecht Motorabgang unten dynamische Lüfterregelung Umgebungstemperatur C 35 55 70 Max Laststrom A ange reiht mit Abstand 22 5 mm 6 6 6 6 Max Laststrom A ange reiht ohne Abstand 5 3 5 3 6 6 A Geräte Gerät senkrecht Motorabgang unten lüfterloser Betrieb Umgebungstemperatur C 35 55 70 Max Laststrom A ange reiht mit Abstand 22 5 mm 6 0 4 8 Max Laststrom A ange reiht ohne Abstand 2 0 2 0 Weitere In...

Страница 5: ...etrieb 5 C 55 C Derating beachten Relative Luftfeuchtigkeit r F 5 95 nicht kondensierend Umgebungstemperatur Lagerung Transport 40 C 80 C Isolationseigenschaften Bemessungsisolationsspannung 500 V Bemessungsstoßspannung 4 kV Verschmutzungsgrad 2 Anschlussdaten Benennung Anschluss Steuerkreis Anschlussart Push in Anschluss Leiterquerschnitt feindrähtig ohne Aderendhülse 0 2 1 5 mm f AWG 24 16 str L...

Страница 6: ... commissioned installed or retro fitted by an electrically skilled person Before working on the device disconnect the power Protective covers must not be removed when operating electrical switching devices Keep the product documentation in a safe place Do not subject the device to mechanical and or thermal loads that exceed the specified limits To protect the device against mechanical or electrica...

Страница 7: ...e recom mend the use of shielded conductors 6 Mounting Image 2 Snap the electronic motor starter onto the respective bus bar system 30Compact 60Classic or directly onto the CrossBoard 1 busbar adapter 30Compact 2 busbar adapter 60Classic 3 DIN rail adapter 4 Electronical motor starter 5 CrossBoard 7 Connection Image 3 The standard connection is realized using a 16 pin con nector Connect the cables...

Страница 8: ...mic fan control Ambient temperature C 35 55 70 Max load current A lined up at a distance 22 5 mm 6 6 6 6 Max load current A lined up without a gap 5 3 5 3 6 6 A devices device vertical motor output below operation without fan Ambient temperature C 35 55 70 Max load current A lined up at a distance 22 5 mm 6 0 4 8 Max load current A lined up without a gap 2 0 2 0 Further information on derating and...

Страница 9: ...rating Relative air humidity r H 5 95 not condensing Ambient temperature range storage transport 40 C 80 C Insulation properties Rated insulation voltage 500 V Rated surge voltage 4 kV Degree of pollution 2 Connection data Designation of connection Control circuit Connection type Push in connection Conductor cross section flexible without ferrule 0 2 1 5 mm f AWG 24 16 str Conductor cross section ...

Страница 10: ...10 ...

Отзывы: