MIXING INDOOR (MIX INDR)
(See fig. f)
1) Go to the MIX INDR item field in the ADJUST Menu
2) Set to the room design temperature used in the heat-loss
calculation
RANGE: 35 to 100°F (2 to 38°C)
DEFAULT: 70°F (21°C)
MIXING DESIGN (MIX DSGN)
(See fig. g)
1) Go to the MIX DSGN item field in the ADJUST Menu
2) Set to the design supply water temperature used in the
heat-loss and design calculations
RANGE: 70 to 220°F (21 to 104°C)
DEFAULT: 110°F (43°C)
MIXING MAXIMUM (MIX MAX)
(See fig. h)
1) Go to the MIX MAX item field in the ADJUST Menu
2) Set to the maximum supply water temperature used in the
mixing system
RANGE: 80 to 225°F (27 to 107°C)
DEFAULT: 180°F (82°C)
NOTE:
Do not exceed the water temperatures
shown for the following construction methods.
MOTOR SPEED (MOTR SPD)
(See fig. i)
1) Go to Motor Speed item field in Adjust Menu
2) Set the time the actuating motor requires to operate from
fully closed to fully open
RANGE: 30 to 230 sec
DEFAULT: 150 sec
27
PROGRAMMING
PROGRAMMING - Step 1 - Programming the Control
f
g
h
• Concrete
150°F
• Poured Underlayment 140°F
• Radiant Wall/Ceiling
120°F
(using drywall)
• Joist No Plates
180°F
• Joist w/Plates
165°F
• Quik Trak
®
180°F
i
Содержание proMIX 101
Страница 1: ...proMIX 101 Installation Manual...
Страница 4: ...2 INTRODUCTION INTRODUCTION Control Overview...
Страница 46: ...44 APPENDIX I proMIX 101 Menu Tree APPENDIX I...
Страница 47: ...45 APPENDIX I proMIX 101 Menu Tree APPENDIX I...
Страница 48: ...46 APPENDIX II Application Drawings APPENDIX II...
Страница 49: ...47 APPENDIX II Application Drawings APPENDIX II...
Страница 50: ...48 APPENDIX II APPENDIX II Application Drawings...
Страница 51: ...49 APPENDIX II APPENDIX II Application Drawings...
Страница 55: ......