When placing the device into operation or after maintenance work, the probe has to be submerged slowly into 
the medium! A rough immersion into the medium can damage or destroy the diaphragm.

!

If there is any danger of damage by lightning or overpressure when the device is installed outdoor, we suggest 
putting a sufficiently dimensioned overpressure protection between the supply or switch cabinet and the device

Installation steps for flange version

-

Carefully remove the pressure measuring device from the package and dispose of the package properly.

-

Please ensure that the mounting thread is clean and free of damage.

-

Check to ensure that the O-ring fits properly in the groove.

-

Screw in the mounting thread of the transmitter in the transmitter flange.

-

Next, tighten it by an open-end wrench. (approx. 25 Nm)

-

Install the flange according to your demands. If a new transmitter flange is needed, it can be ordered from 
Winters Instruments

Removing the protection cap (if existing)

For the protection of the diaphragm, some of the probes have a plugged-on protection cap. If the device shall be
used in high-viscosity media such as sludge, a removal of the cap before start-up is necessary. Thus, the sensor
becomes flush and the medium will attain quickly to the diaphragm.

If it is necessary for your application to remove the protection cap, this has to be done with utmost care. To 
prevent a damage of the diaphragm, please follow these instructions.

Removal by hand

-

Hold the probe in a way that the protection cap points upwards.

-

Hold the probe with one hand on the sensor section (1).

-

Remove the protection cap (2) with the other hand.

Removal with a tool (recommended)

-

Hold the probe in a way that the protection cap points upwards.

-

Slide a small tool such as a screwdriver (8) straight through two opposite drill holes in the protective cap (2).

-

Lever it off by moving up the handle of the screwdriver.

Make sure that the sensor (7) under the protection cap will not be damaged!

3.5 Cable protection (optional)

On order, the probe has been delivered with cable protection; if the device has optionally been prepared for
mounting with stainless steel or PVC pipe, a suitable cable protection has to be mounted by the customer.

The probe must be installed in such a way that rubbing or impact of the device, e. g. against a tank wall, is

prevented. It is also important to consider the operating conditions such as flow conditions.

Electrical

 

Installation

Y WARNING!

Install the device only when currentless!

Establish the electrical connection of the device according to the technical data shown on the manufacturing label,
the following table and the wiring diagram.

 

 

 

figure 2

removal of protection cap

Y       DANGER!

   The transmitter must not be installed in potentially explosive atmosphere requiring category 1 status.

Y       WARNING!

 Input supply to pressure transmitter must be SELV (or class 2). Source in accordance with CSA 61010-1-04.

Содержание LM3

Страница 1: ...www winters com WINTERS INSTRUMENTS MANUFACTURER OF INDUSTRIAL INSTRUMENTATION LM3 SUBMERSIBLE TRANSMITTER INSTALLATION AND OPERATING MANUAL ...

Страница 2: ...immunity according to EN 61326 Electrical Connection Cable with sheath material PVC grey PUR black FEP black Housing 316Ti SS Seals FKM Viton Kalrez EPDM Nordel Diaphragm 316L SS Weight 100 g without cable Current Consumption Current 25 mA max Connecting Cables Cable capacitance Signal line shield and signal line signal line 160 pF m Cable inductance Signal line shield and signal line signal line ...

Страница 3: ...angerous situation which may result in death or serious injuries Y CAUTION potentially dangerous situation which may result in minor injuries CAUTION potentially dangerous situation which may result in physical damage NOTE tips and information to ensure a failure free operation Target group Y WARNING To avoid operator hazards and damages of the device the following instructions have to be worked o...

Страница 4: ...l Safety Data Sheet SIL Declaration of Conformity Product identification The device can be identified by its manufacturing label It provides the most important data By the ordering code the product can be clearly identified The manufacturing label must not be removed from the device Mechanical installation Mounting and safety instructions Y WARNING Install the device only when depressurized and cu...

Страница 5: ...for your application to remove the protection cap this has to be done with utmost care To prevent a damage of the diaphragm please follow these instructions Removal by hand Hold the probe in a way that the protection cap points upwards Hold the probe with one hand on the sensor section 1 Remove the protection cap 2 with the other hand Removal with a tool recommended Hold the probe in a way that th...

Страница 6: ...l resistance of the connecting cable could cause problems this cable has to be checked with the following calculation with RL resistance of connecting cable in ohm p specific resistance in ohm mm m l cable length in m A cross section of conductor in mm with Vtot total voltage drop Rload load resistance to be taken out of the current data sheet the following condition must be fulfilled with VS plan...

Страница 7: ...e operating manual Y WARNING The device has to be used within the technical specifications only compare the data in the data sheet Placing out of service Y WARNING When dismantling the device it must always be done in the depressurized and currentless condition Check also if the medium has to be drained off before dismantling Y WARNING Depending on the medium it may cause danger for the user Compl...

Страница 8: ...o the European Directives 2002 96 EG and 2003 108 EG on waste electrical and electronic equipment Waste of electrical and electronic equipment may not be disposed by domestic refuse Y WARNING Depending on the measuring medium deposit on the device may cause danger for the user and the environment Comply with adequate precautions for purification and dispose of it properly Warranty conditions The w...

Страница 9: ...WINTERS INSTRUMENTS Tel 1 800 WINTERS www winters com 9 ...

Страница 10: ...INTERS Fax 403 723 6647 calgary winters com USA Houston Winters Instruments 5400 W Sam Houston Pkwy N Houston Texas 77041 Tel 281 880 8607 1 800 WINTERS Fax 281 880 8614 usasales winters com Asia Shanghai Winters Instruments Room 203 Building 8 No 471 Guiping Road Shanghai 200233 China Tel 86 21 6104 2610 Fax 86 21 6104 2615 asiasales winters com www wintersasia com Latin America Buenos Aires Wint...

Отзывы: