background image

29 

 

 

The condensing unit needs to be hardwired. To bring the rated high voltage to the 
factory-installed contactor in the chassis cabinet to line side (L1 & L3) of the contactor. 
Use table 1 to identify the minimum recommended AWG, 

USE COPPER WIRE 

ONLY

. Run a ground lead to be connected to the condensing unit Ground lead/LUG. 

There is a separate ground lug for the condensing unit internal components (See Fig 
3). The load side of the factory-installed contactor will be factory-wired.

 

 

Turn on power to the condensing unit 24 hours prior to system start-up to allow 
crankcase heater to warm up compressor crankcase.

 

Unit 

Recommended 

Minimum AWG 

SP25 

16 

Start-Up 

Prior to charging the system and start-up ensure the system has been powered for at 
least 

24 hours

. This is required so the co

mpressor’s crankcase heater has ample time 

to warm the system to avoid premature failure. Then proceed to charging the system. 

Refrigerant Charging 
Note

: Models DS, and WGS utilize a Headmaster control valve to control head pressure 

at low ambient applications, therefore require a specific initial charging procedure as 
outlined below. 

Determining the amount of charge (Low Ambient and Extreme Climate Protection) - 
When “refrigerant side” head pressure control is utilized on a system, one of the most 
important factors is determining the total system refrigerant charge. While on most 
packaged units the amount of charge is listed on the unit, the required charge for a field 
built-up system cannot be listed by the manufacturer. Charge is usually added when the 
system is started up until “proper” system performance is reached. However, this is not 
satisfactory and if the system is to function properly year-round, the correct amount of 
extra charge must be calculated ahead of time.

 

Charging System with Head Pressure Control 
Note

: When charging any system with head pressure control the outdoor ambient 

temperature must be known.  

Charging of Systems with Head Pressure Control in temperatures 

above

 70°F (21°C) 

(After normal evacuation procedures): 

1.  Connect refrigerant cylinder to liquid line service valve port.

 

2.  Charge liquid refrigerant into the high side of the system. Weighing the charge is 

recommended.

 

3.  Remove the refrigerant drum and connect it to the suction service valve.

 

4.  Charge refrigerant vapor into the low side. Do not allow liquid refrigerant into the 

low side.

 

5.  Start the system.

 

Содержание 99H0204-20

Страница 1: ...s com Wine Guardian reserves the right without notice to make changes to this document at its sole discretion Please visit our web site for the most current version of the Wine Guardian manual and oth...

Страница 2: ...for SP25 16 Specifications 19 Installation 20 Pre Installation 20 Pre Installation Planning 20 Installing The Fan Coil 20 Reducing Noise Generation 21 Ductwork 22 Duct Collar and Panel Adjustment 23...

Страница 3: ...ning the Humidifier Optional 37 Electric Heat 37 Extreme Climate Protection 37 Maintenance Schedule 37 Monthly 37 Yearly 38 Troubleshooting 39 Resetting the High Pressure Switch 39 Contact and Warrant...

Страница 4: ...with local codes and regulations and are experienced with this type of equipment Exposure to safety hazards is limited to maintenance personnel working in and around the unit When performing maintena...

Страница 5: ...d when the unit has been damaged in any way Do not use extension cords Do not modify the equipment it may cause damage to the equipment and will void the warranty Receiving Inspecting and Unpacking Wh...

Страница 6: ...to remove heat from the refrigerant to the ambient air outside the wine cellar The word condenser refers to the condensation of the refrigerant from gas to liquid phase CE Certificate of European conf...

Страница 7: ...red split two piece climate control system designed specifically for the storage of wine at cellar temperatures It is designed for easy installation and operation Wine Guardian uses digital electronic...

Страница 8: ...ing of the Wine Guardian s Evaporator is powder coated aluminum to prevent rust and corrosion All evaporator coils are aluminum tubes and aluminum fins with a protective anti corrosion coating The uni...

Страница 9: ...on based on head pressure and heats the oil reservoir including a 3R Condenser Fan We recommend this bundle if the system will experience condenser inlet temperatures below 20 F 7 C or above 115 F 37...

Страница 10: ...ardian system is sold in kits by size for each unit Each kit contains two adapter collars one 25 foot 7 3 meters length of round flexible duct and two straps The number of duct kits needed depends on...

Страница 11: ...nce with the NEC Wires are numbered and color coded to match the wiring diagrams Internal Drain Trap Water condensate from the evaporator coil fills the trap and forms a seal to prevent air from being...

Страница 12: ...12 Overview of the Evaporator Fig 1...

Страница 13: ...13 Terminal Strip Connections White Heat Cyan 24 Volt AC Common Yellow Cool Red 24 Volt AC Power Green Fan Humidity Connection Yc Cc Evaporator to Condenser 24 Volt Connection...

Страница 14: ...14 Overview of the Condenser Fig 2...

Страница 15: ...15 Refrigeration Illustration Fig 3...

Страница 16: ...16 Wiring Diagram for SP25 Fig 4 DS025 Condenser...

Страница 17: ...17 Wiring Diagram for SP25 cont Fig 5 SP25 Molex connections Wiring Diagram for SP25 cont Fig 6 SP25 Electrical Schematic See Next Page...

Страница 18: ...18...

Страница 19: ...19 Specifications Wine Guardian Specification Sheet 60Hz models...

Страница 20: ...nates This indicates the system has power RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT SHARP EDGES ARE PRESENT INSIDE THE WINE GUARDIAN SYSTEM Pre Installation Planning Prior to installation determi...

Страница 21: ...hin 0 25 6 35mm end to end and 1 8 3 18mm side to side for proper operation Locate the unit as close to the wine cellar as possible to reduce the length of the duct runs If possible use straight ducti...

Страница 22: ...ser section to redirect or absorb sound to bring in outside air to the unit inlet and or to exhaust the hot air out of the ambient space Ductwork Diameters inches Wine Guardian 60 Hz units Model Evapo...

Страница 23: ...panel by sliding the panel collar up to disengage the bottom hook from the housing before completely removing the panel collar from the unit Fig 4 5 To replace the panel collar simply reverse the pre...

Страница 24: ...or the drain line to function properly If draining into a nearby sink the unit must be elevated higher than the rim of the sink in order for the water to drain by gravity Install with a 6 35mm per lin...

Страница 25: ...as it is supplied with many standard features to assist full operation in this wide range Mount the condensing unit above normal snowfall levels to allow uninhibited winter operation A buildup of snow...

Страница 26: ...longer horizontal runs to prevent potential oil return problems See sample piping chart on page 27 When sweat connections are made in the connecting lines be sure that the inside of the tubing is clea...

Страница 27: ...ks found Connect a good vacuum pump to both the low and high side service valves while still in their factory supplied position isolating the refrigerant charge in the condensing unit Draw a deep vacu...

Страница 28: ...ASE ONLY TO AVOID COMPRESSOR DAMAGE LIQUID MUST ALWAYS BE CHARGED INTO THE HIGH SIDE OR INTO AN ACCUMULATOR Be sure there is not an overcharge of refrigerant An overcharge might permit liquid refriger...

Страница 29: ...procedure as outlined below Determining the amount of charge Low Ambient and Extreme Climate Protection When refrigerant side head pressure control is utilized on a system one of the most important f...

Страница 30: ...ize and clear the Sight glass Use supplied information on the following pages for proper final charge 5 At this point the system is correctly charged for this type of head pressure control at the ambi...

Страница 31: ...wine cellar is already at specified conditions e g 57 F 13 C 55 RH and if your superheat is very low or zero you may have overcharged your system Sub Cooling With your compound pressure gauge set ins...

Страница 32: ...f 16oz 453kg from this new total and that is the amount you ADD to the system upon start up In this example 47oz 1 327kg ADDED Additional Charge for Extreme Climate Protection XLA Option Systems For s...

Страница 33: ...nd the ductwork has been connected power on the unit Once the impeller is running check the ducts and ductwork connections for any air leaks Balance Air Distribution Confirm condenser airflow is unres...

Страница 34: ...on Company Name License Date of Startup Address Technician City Certification ID Number State Zip Certification Source e g NATE Company Phone Technician Phone Company Email Technician Email Email comp...

Страница 35: ...4 hours Indoor Unit Has water been placed in drain pan to confirm proper drainage Piping Have leaks checks been made at compressor outdoor and indoor coils TXVs Thermostatic Expansion Valves Filter Dr...

Страница 36: ...Some maintenance to the unit may be required due to dust or dirt in the air stream The condenser coil is provided with a reusable washable air filter The filter protects the coil from becoming coated...

Страница 37: ...e by an amount shown in the specifications Extreme Climate Protection The purpose of the Extreme Climate Protection is to protect the compressor and refrigerant system It has two distinct components a...

Страница 38: ...ushing Be careful to keep the drains pans clear of all debris Inspect cabinet for corrosion or rusting clean and paint Inspect for dirt buildup on or inside the unit Clean unit by vacuuming or wiping...

Страница 39: ...ssure Switch Has Shut Down the Unit Every Wine Guardian unit has a manual reset high pressure switch in the refrigeration system This switch shuts the compressor and condenser down if the head pressur...

Страница 40: ...40 Fig 1 Please see the link below for a video on how to reset the High Pressure Switch https www youtube com watch v TFGFTWZVeAs...

Страница 41: ...hat Wine Guardian or its distributors are found liable for damage based on any defect or nonconformity in the products their total liability for each defective product shall not exceed the purchase pr...

Страница 42: ...wineguardian com Help wineguardian com Email info wineguardian com Warranty The Wine Guardian unit serial number is noted on all packing lists and bills of lading and along with shipping date is kept...

Отзывы: