background image

 

D

i

rectory of Terms 

Ambient Air

 – The surrounding area outside the wine cellar such as a room, basement, garage or 

outdoors. 

BTU/H – 

British thermal units/hour. A unit of measurement to describe the power of heating and 

cooling system. 

CFM 

– Cubic feet per minute. A unit of measurement for the amount of air handled by the fan.

 

Condensate / Condensation

 – The water formed out of the air when it is cooled below a certain 

temperature (called dew point). Often referred to as “sweating” on pipes and cold surfaces. This water 
collects at the bottom of the evaporator or cooling coil and drains out of the unit through the drain line.

 

Condensing Unit (Heat Rejection) 

– The condensing unit uses the compressor, condenser coil and 

fan to remove heat from the refrigerant to the ambient air 

outside

 the wine cellar. The word condenser 

refers to the condensation of the refrigerant from gas to liquid phase.

 

CSA/ETL – 

Canadian Standards Association/Edison Testing Laboratory (product compliance to 

safety standards) 

F –

 (Degrees) Fahrenheit 

Fan Coil Unit (Evaporator Cooling)

 – The fan coil unit uses the cooling coil and the fan to remove 

heat from the air 

inside

 the wine cellar to the refrigerant, cooling the air and condensing moisture out 

of the air. The word evaporator refers to the evaporation of the refrigerant from liquid to gas phase in 
the coil. The fan coil unit is ducted to or can be placed inside the wine cellar.

 

Flexible Duct 

– Round ducts with steel reinforced plastic liners, a layer of insulation and an outer 

plastic layer used to convey the air from the unit to the wine cellar or ambient space.

 

Grille or Diffuser

 – Inlet or outlet plates to direct the airflow or protect the inside of the unit.

 

Heat Gain / Loss

 – The amount of cooling or heating expressed in watts transferred between the wine 

cellar and the ambient space. The Wine Guardian must offset this heat/gain loss.

 

Inlet Air

 – The air returning from the wine room to the Wine Guardian fan coil.  

I

.

D

. – Inside diameter 

NEC

 – National Electrical Code 

O.D. – 

Outside diameter 

Psig Pounds – 

Force per square inch gauge  

Recovery

 – The amount of cooling the unit does to return the cellar to its set point temperature after 

some new heat load is introduced, such as people or new cases of warm wine entering the cellar.

 

Return Air 

- The air leaving the cellar and returning to the inlet of the fan coil. (See Inlet Air above) 

TXV 

– Thermal expansion valve 

VAC 

– Volts alternating current

 

SP

 – Static pressure. Unit of measurement (inches of water column) of the pressure of the air handled 

by the fan.

 

Set Point

 – The desired temperature or humidity set on the remote interface controller or humidistat. 

Supply Air 

- The air entering the wine cellar from the discharge of the fan coil.  

Содержание 15H0128-00

Страница 1: ...yracuse NY Wine Guardian reserves the right without notice to make changes to this document at its sole discretion Please visit our web site for the most current version of the Wine Guardian manual an...

Страница 2: ...e Wine Guardian fan coil 11 Ducted split systems specifications sheet 13 Wiring Diagram for 1 4 Ton and 1 2 Ton Units 14 Wiring Diagram for 1 Ton Unit 15 Wiring Diagram for 2 Ton Unit 16 24 Volt Conta...

Страница 3: ...lit System Interconnecting Line Sizing Chart 33 Sample Piping Configurations 34 Leak Checking and Evacuation Process 35 Wiring 35 Refrigerant Charging 36 Determining the amount of charge 36 Procedures...

Страница 4: ...grees when unit is not running 57 Humidity too low or supply air is too cold without optional humidifier 57 Humidity too low without optional humidifier 58 Humidity too low with optional humidifier 58...

Страница 5: ...rs to the evaporation of the refrigerant from liquid to gas phase in the coil The fan coil unit is ducted to or can be placed inside the wine cellar Flexible Duct Round ducts with steel reinforced pla...

Страница 6: ...Wine Guardian fan coil 11 Ducted split system specifications sheet 13 Wiring diagrams for and ton units 14 Wiring diagram for the 1 ton unit 15 Wiring diagram for the 2 ton unit 16 24 volt contactor...

Страница 7: ...quipment for any sign of damage caused during transit Report all visual or concealed damage to the carrier and file a claim immediately Thoroughly inspect the contents for any visible damage or loose...

Страница 8: ...tion is furnished with a sealed UL approved power cord and plug The Wine Guardian Ducted Split System Contains 1 A Wine Guardian Fan Coil Unit with A thermal expansion valve to control the flow of ref...

Страница 9: ...ller for remote mounting within the wine cellar The remote interface controller has multiple control functions for cooling heating and operation It has a fully automatic mode to switch between heating...

Страница 10: ...Split Systems A factory installed low ambient option is available that makes the Wine Guardian capable of exposure to low ambient temperatures This feature controls the condenser fan operation based o...

Страница 11: ...11 Fig 2 Overview of the Wine Guardian fan coil Fig 1...

Страница 12: ...1 13 11 13 11 13 15 00 G Drain outlet location Inches 0 656 0 919 0 919 0 848 AA Discharge opening height Inches 7 50 7 50 7 50 9 188 BB Discharge opening width Inches 7 00 11 00 11 00 11 188 CC Inlet...

Страница 13: ...13 Ducted split system specifications sheet...

Страница 14: ...14 Wiring Diagram for SS025 and SS050 Units Fig 4...

Страница 15: ...15 Wiring Diagram for SS088 Units Fig 5...

Страница 16: ...16 Wiring Diagram for SS200 Units Fig 6...

Страница 17: ...17 24 Volt Contactor Detail Sheet Fig 7...

Страница 18: ...zardous situation which if not avoided could result in death or serious injury Following is a typical example of a Warning message as it could appear in the manual WARNING RISK OF PERSONAL INJURY OR D...

Страница 19: ...ve exposure to dangerously high voltage Make sure you are aware of the level of electrical hazard when working on the system Observe all electrical warning labels on the unit Electrical Shock Hazards...

Страница 20: ...e 60 hertz cycles Control Method Disconnect power cord and On Off switch DANGER Never reach into a unit while the fan is running Never open an access door to a fan while the fan is running Disconnect...

Страница 21: ...ong The wide blade or the third prong is provided for your safety If the provided plug does not fit into your outlet consult an electrician for replacement of the obsolete outlet Protect the power cor...

Страница 22: ...fan coil section Set the system on the floor or a sturdy level surface Plug in the system Press the on off switch to see if the control illuminates This indicates the system has power A built in timer...

Страница 23: ...e openings or outlets to the unit Never allow anything to rest on or roll over the power cord Never place the unit where the power cord is subject to wear or abuse Do not use extension cords Never ove...

Страница 24: ...Where to run the drain line Are all the parts available to complete the installation Performing a Pre installation Check Check for the proper installation of the electrical plug configuration Check fo...

Страница 25: ...communication cable The second communication port can be used for other factory options such as remote temperature humidity sensors CAUTION RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT Check suppor...

Страница 26: ...or proper operation Locate the unit as close to the wine cellar as possible to reduce the length of the duct runs If possible use short and straight ducting on all ductwork runs Typical Mounting Arran...

Страница 27: ...27 Rod Mount Fig 2 Shelf Mount Fig 3 Optional ductwork connection on same wall Fig 4...

Страница 28: ...Model Outlet supply air Single Outlet supply air Single Inlet Return Air Single SS025 8 6 8 SS050 10 10 10 SS088 10 10 10 SS200 12 12 12 CAUTION RISK OF DAMAGE TO EQUIPMENT Avoid crimping the flexible...

Страница 29: ...ory kit Pull the outer plastic wrapping and insulation away from the end of the duct to expose the reinforced inside duct liner Use tie straps of clamp around the inside liner to fasten the duct colla...

Страница 30: ...a sort piece of one half inch copper tubing and secure with clamps If no drain is available use a bucket Do not extend the drain below the rim of the bucket Empty the bucket periodically The Wine Gua...

Страница 31: ...IN ANY WAY Do not use extension cords Plug the unit into the wall outlet Gently pull on the plug to make sure it is tight IMPORTANT The electrical power supply must be either 115 volt or 230 volt AC...

Страница 32: ...unit to assist in monitoring the refrigerant charge and the state of the refrigerant in the system Keep horizontal and vertical distances between the indoor and outdoor section as close as possible to...

Страница 33: ...l Liquid Line OD Liquid connection at evaporator OD Suction line OD Min Suction line insulation thickness in Suction connection at evaporator OD Maximum total line length Maximum lift height SS025 1 4...

Страница 34: ...orator Condenser Condenser Condenser Evaporator Evaporator Evaporator Evaporator Evaporator Condenser Condenser Condenser Evaporator Condenser Soft copper sages and creates an oil trap Incorrect Insta...

Страница 35: ...acuum pump The system is now ready for charging Charge the system with the correct amount of refrigerant and mark the amount with a ballpoint pen in the space provided on the unit nameplate NOTE When...

Страница 36: ...ic initial charging procedure as outlined below The SS200 system does not use this method of low ambient control utilizes fan cycling but can accept initial charge into the liquid receiver port the sa...

Страница 37: ...ormation on the following pages for proper final charge Charging of Systems with Sporlan Head Pressure Control in ambients below 70 degrees F After normal evacuation procedures NOTE When charging in a...

Страница 38: ...valve port back seated valve stem to allow un restricted refrigerant flow from evaporator back to the compressor Convert suction pressure to a saturated temperature as derived from a pressure temperat...

Страница 39: ...5 16 60 28 109 5 17 70 27 114 11 22 80 27 134 13 25 100 27 179 22 30 115 28 215 27 33 SS088 OD Ambient F Suction psig Discharge psig Superheat F Sub cooling F 15 22 98 5 15 40 23 95 5 17 60 25 108 8...

Страница 40: ...sensor installation details Mounting the Remote Interface Controller IMPORTANT Wine Guardian units are supplied with 50 feet of Cat 3 6 wire twisted pair communication cable with RJ 11 connectors Fail...

Страница 41: ...wo 1 8 holes and insert anchors provided within the mounting surface Anchors may not be required if securing to a wall stud or racking system 4 Plug in the communication cable to the back of the remot...

Страница 42: ...ount the remote sensor directly on an outside wall or wall adjacent to a boiler room Use a piece of foam insulation behind the sensor to insulate it from a hot or cold surface The recommended height i...

Страница 43: ...e kit Fig 4 6 Plug the remote sensor cables into the splitter device at the Wine Guardian unit along with the communication cable for the remote interface controller Fig 5 NOTE If using multiple remot...

Страница 44: ...Failure to perform this procedure will result in the system reading only one sensor and not the average of multiple sensors NOTE If multiple sensors control the Wine Guardian unit change factory defau...

Страница 45: ...display the Humidity setpoint Press the Up or Down arrows to adjust the humidity to the desired set point NOTE Wine Guardian humidifier must be installed and setting six set to 1 or 2 before the contr...

Страница 46: ...on to advance to Setting 4 Press the Up or Down arrow buttons to adjust to the desired set point Factory default is 5 High humidity alarm set point Setting 5 Press Mode button to advance to Setting 5...

Страница 47: ...n compressor stop and restart Rapid start stop of compressors can cause premature failure Factory default is 5 minutes Set up remote sensor or remote interface controller Setting 10 Press Mode button...

Страница 48: ...e button to advance to Setting 17 Press the Up or Down buttons to adjust to the desired setpoint This setting is the minimal allowable temperature difference between heating and cooling setpoints Maxi...

Страница 49: ...w once to change screen from alarm to normal Temperature and Humidity indication Hi Hum will remain on screen until humidity falls below the High Humidity Alarm set point Setting 5 Low humidity alarm...

Страница 50: ...d to humidifier Drain lines and trap installed properly Ductwork fittings and grilles installed properly All cold duct surfaces insulated No obstructions to air flow around condensing unit Starting up...

Страница 51: ...cuit is energized and operating AUTO means the fan runs only when the remote interface controller is calling for cooling heating or the humidistat is calling for humidification Running the Unit Check...

Страница 52: ...ature gradient of approximately 5 to 10 degrees between floor and ceiling To increase or decrease the temperature in various zones change the air flow patterns To keep the entire wine cellar at the sa...

Страница 53: ...asks require knowledge of mechanical and electrical methods Make sure you are familiar with all hazards general safety related procedures and safety labels on the unit CAUTION EXPOSURE TO MICROBIAL GR...

Страница 54: ...ng coil is located between the evaporator coil and blower inside the transition duct It contains the heating element and high temperature limit switches The heating coil is wired to work in conjunctio...

Страница 55: ...use a vacuum with a brush attachment to clean the coils Clean condensate pan under the evaporator coil by flushing Be careful to keep the drain pans clear of any and all debris Inspect cabinet for cor...

Страница 56: ...rn on switch No power to outlet Check circuit breaker and wiring Unit not plugged in Plug in the unit Power switch light is on and the remote interface controller light is off Possible Cause Solution...

Страница 57: ...controlling temperature Reset remote interface controller to higher cooling temperature Check for remote interface controller rise across coil Reset remote interface controller to higher heating tempe...

Страница 58: ...er around cellar Humidity too high when unit is running but not cooling Possible Cause Solution Compressor not operating Ambient temperature is too high Check and reset high limit switch Clear blockag...

Страница 59: ...ain is trapped Trap plugged Condensate pan plugged Unit not level Re pipe to remove external traps Clean trap Remove blockage and clean Level with shims Unit is running properly but the sound of the u...

Страница 60: ...by dust covering the filter or an obstruction blocking the airflow in the duct or grille Possible Cause Solution Head pressure in unit is too high because Remove the obstruction at the condensing uni...

Страница 61: ...face controller guide for remoteinterface controllerinformation Lowsuction pressure Check low pressure switch Check pressure and adjust superheat High pitched or loud rubbing noise clanking or vibrati...

Страница 62: ...le at Wine Guardian for warranty purposes All correspondence regarding warranty must include the model number and serial number of the unit involved Note that the warranty is null and void if the seri...

Отзывы: