33
quarter inch, a vibration eliminator should be installed close to the motor compressor in a
horizontal parallel to the compressor, crankshaft or in a vertical position 90 degrees to
compressor crankshaft.
NOTE: The suction line should be clamped near the inlet end of the vibration
eliminator. The vibration eliminator is located between the clamp and the
compressor
.
Split System Interconnecting Line Sizing Chart
Table 3
Model
Liquid
Line(OD)
Liquid
connection
at
evaporator
(OD)
Suction
line (OD)
Min.
Suction line
insulation
thickness
(in)
Suction
connection
at
evaporator
(OD)
Maximum
“total” line
length
Maximum
lift
(height)
SS025
1/4”
1/4”
3/8”
3/8”
3/8”
50’
15’
SS050
1/4”
1/4”
1/2”
3/8”
*3/8”
50’
15’
SS088
3/8”
*1/4”
1/2”
5/8”
1/2”
50’
15’
SS200
3/8”
3/8”
7/8”
5/8”
*1/2”
50’
15’
*Interconnecting tube must be reduced down at evaporator connection
Notes:
Line lengths are expressed in equivalent feet = actual run fitting allowances (i.e. ~5’ for
each bend/elbow allowance).
Use only refrigeration grade dehydrated tubing.
Install refrigeration piping per local codes and ASHRAE guidelines.
Содержание 15H0128-00
Страница 11: ...11 Fig 2 Overview of the Wine Guardian fan coil Fig 1...
Страница 13: ...13 Ducted split system specifications sheet...
Страница 14: ...14 Wiring Diagram for SS025 and SS050 Units Fig 4...
Страница 15: ...15 Wiring Diagram for SS088 Units Fig 5...
Страница 16: ...16 Wiring Diagram for SS200 Units Fig 6...
Страница 17: ...17 24 Volt Contactor Detail Sheet Fig 7...
Страница 27: ...27 Rod Mount Fig 2 Shelf Mount Fig 3 Optional ductwork connection on same wall Fig 4...