![WindowMaster NV Solo Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/windowmaster/nv-solo/nv-solo_manual_985483027.webp)
27
9.1 Retrieving service data
The software version of the control panel and weather station may appear in the display. Access to the
service area via the basic settings takes place by one long press on the
key (3 seconds). First, the
software edition of the control unit (
, Panel) is displayed and afterwards a short press of the
key
displays the software edition of the control unit/weather station (SEN=sensor). The number 10 in the display
indicates version 1.0, 12 indicates 1.2, etc. Exit the service data display by pressing the
key shortly.
10. Technical data
The product is in conformity with the provision of EU directives.
10.1 Control panel
Voltage
2 x 1.5 V (2 batteries, AA/Mignon/LR6) or 2 x 1.2 V
(2 batteries, AA/Mignon/LR6)
Surrounding temperature
-10°C to +50°C
Dimensions of control unit
103 x 98 x 28mm (WxHxD)
Frequency
868.2 MHz
Note:
We reserve the right to make technical changes
10.2 Weather station
Voltage
13-30V DC / 12-24 V AC
Surrounding temperature
-30°C to +60°C
Weather station dimensions
96 x 77 x 118mm (WxHxD)
Output
Potential free contacts to input on control unit
(WUC / WCC / WSC)
Heating rain alarm
approx. 1.2 W
Measuring range of temperature sensor
-40°C to +80°C
Accuracy of temperature sensor
0.6°C
Measuring range of wind sensor
0 - 35m/s
Accuracy of wind sensor
1 m/s
Backup time
10 years
Note:
We reserve the right to make technical changes
10.3 Factory settings
The control panel is pre-programmed with:
Opening at indoor temperature > 25°C
Lock-out at outdoor temperature >5°C
Wind alarm from 4 m/s
Rain alarm is activated (ON)
Run time 5 seconds (LEASP)
Interval time 7 minutes (LEASP)
dAS is activated (ON)