4.2 Wind and rain alarm, temporary or permanent
The second basic setting to be set is for a temporary or permanent wind and rain alarm.
The signal from the wind or rain alarm can be temporary (the signal to the control unit stops after 4 minutes -
OFF) or permanent (continues as long as the rain sensor is wet or the wind sensor senses wind - ON).
The alarm is factory set to ON.
Select the desired setting ON or OFF using
;
The alarm signal shall be permanent (The window remains closed in the event of a rain or wind
alarm).
The control panel is factory set to ON. RECOMMENDED SETTING
The alarm signal shall stop after 4 minutes
Confirm selection by pressing
-key. The display will automatically change to setup for the next parameter
–
dAS (4.3).
4.3 dAS
The third basic setting to be set is dAS.
dAS is a function that makes it possible to use WindowMaster Smoke Ventilation Units WSC xxx.
dAS is pre-set to be ON.
RECOMMENDED SETTING: ON.
Confirm the selection by pressing the
key. The display will automatically change to setup for the next
parameter
– operating setting (point 4.4).