19
7) Automatic detectors
a) Spray test aerosol on the detectors.
b) The actuators move open through to the end position. The red LED in the detector, the red alarm
LED (also in the control panel) and the permanent acoustic signal in the operating panel are ON.
c) While running, press the Closed button at the ventilation button, then press both buttons, the
actuators must neither close nor stop!
d) Press the reset/Closed button in the operating panel. The actuators close through to the end position.
The ventilation function is released again. The red alarm LED (also in the control panel) and the
signal generator are OFF.
8) Emergency power supply test
a) Remove the mains fuse from the control panel. Adhere to the VDE regulations! (only Germany
- see National guidelines)
b) The green mains and operating LED's are OFF, the yellow accumulator Led is flashing (control pabel
in the accumulator mode).
The malfunction message at the SHE main operating panels panels is ON.
c) The ventilation buttons are deactivated.
d) If the actuators were open, they will automatically close after 2 minutes.
e) Test the SHE trip and reset/closed as described under 5).
f) Refit the mains fuse.
g) The green mains and operating LED's are ON, the yellow accumulator LED is OFF. The malfunction
message at the operating panels is OFF.
9) Activation of inspection check reminder
a) Connect power and back-up batteries to the smoke panel.
b) Connect all components to prevent fault signal.
c) Set SW1/1 to ON..
d) The operation LED flashes app. 10 seconds to control the activation.
e) The maintenance reminder is now activated.
10) Wind/rain detector
a) Open the actuators with the ventilation button.
b) Wet the rain sensor, the actuators will fully close, the green wind/rain LED in the control panel is ON.
c) While running, press the Open button at the ventilation button, then press both buttons, the actuators
must neither open nor stop!
d) The SHE trip has priority.
When the start-up was successful, then close the doors of the operating panels and of the control panel.
If the start-up was unsuccessful (error with one of the test run processes), please refer to the chapter Function
description (see connection possibilities). If necessary, check the wiring in accordance with the wiring diagram.
11) Back-up batteries