background image

6

OPM-114

REV B

ENGINE

Refer to the engine operators manual for more detailed operation and 

maintenance information.

CAUTION: EQUIPMENT DAMAGE:

Be sure to check the engine oil level frequently as specified in the 

engine manual.

The engine manufacturer has established an excellent worldwide 

engine service organization; engine service is available from a nearby 

authorized dealer or distributor. Go to the WINCO website for a list of 

engine dealers (http://wincogen.com/Engine_Support) or contact the 

WINCO Service Department.

The rated power of each engine-generator is limited by the 

temperature, altitude, and all other ambient conditions specified by 

the engine manufacturer. Engine power may decrease 3% for each 

1000 feet above sea level, and will decrease an additional 3% for each 

10 degrees Fahrenheit above 60° Fahrenheit. Units should not be 

operated in ambient temperature greater than 122° Fahrenheit.

GENERATOR

WINCO generator sets use brushless, AVR (Auto-Voltage Regulator) 

controlled broad-range generator ends. The generator converts 

rotational mechanical energy into electrical energy. These WINCO units 

are equipped with generators manufactured by Cummins Generator 

Technology. Each generator ‘end’ has its own data tag. A unique serial 

number is on the data plate.

TRAILER/HOUSING

These switchable voltage generators are normally shipped fully  

enclosed & mounted on a trailer.  The trailer is DOT approved and you 

should receive a certificate of origin. This will allow you to register the 

equipment and obtain tags from your state. If you should encounter any 

problems registering the trailer, contact the WINCO Service Dept at 

507-357-6831.

INTRODUCTION

PRODUCT DESCRIPTION

This engine-generator set is designed for unattended remote start 

operation. It can be operated as part of a fully automatic standby power 

system or independently as a local start unit in a prime power system. 

The engine-generator set is fully tested at the factory prior to shipment 

to insure proper operation of each individual component as well as the 

total system’s performance and reliability.

The engine generator set consists of a multi-cylinder, liquid cooled 

engine nominally operating at 1800 rpm. The generator frequency 

regulation is maintained by the engine governor to /- 1.5 Hz 

(cps), from no load to rated load for standard mechanical governors 

and to /- .5 Hz or better for units equipped with an electronic 

governor. The generator is a single bearing, direct drive, rotating field 

design.  The generator is connected to the engine flywheel via flexible 

drive disks. Generator set is skid mounted with isolation mounts 

between the engine and base on all units.

A customer supplied 12 Volt battery is required to complete the 

installation. Battery requirements are listed later under the battery 

installation section. 

Unit Orientation Note:

 All references used in this manual for unit 

familiarization, access and component locations on the Generator Set 

are oriented from a TOP (plan) VIEW with engine at the FRONT and 

generator to the REAR.

WINCO uses a common junction box for all customer control and 

power connections (both AC output and DC control). The common 

electrical junction box is always on the left side at the generator end of 

the machine.

The engine is controlled and Generator Set operation is monitored for 

safe operation by a programmable microprocessor based electronic 

Engine Control Module (ECM) with an LCD digital display. The 

generator set ECM control is mounted on a vertical pedestal on the 

right side of the generator. The ECM is programmed with a cycle 

cranking sequence - 3 cycles of 15 seconds on/15 seconds off, and 

5 minute cool-down delay. The cool-down delay can be changed in 

the field from 0 to 30 minutes by your installer. Other features, timing 

cycles, set points, and signal output capabilities are possible. Consult 

factory for procedure and passwords.

NOTICE:

These units will automatically transfer if a power outage occurs while 

running in exercise mode.

GENERATOR SET

Every WINCO generator set has its own unique identity data plate. 

This data plate identifies the complete unit model number, the system 

serial number, and has links to the individual components that form the 

generator set in our factory records. Several of the major components 

also have their own individual data plates providing additional 

information to document build data for warranty and replacement parts. 

Содержание RP25/D

Страница 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 SERVICE DEPT 507 357 6831 SALES DEPT 507 357 6821 www wincogen com INSTALLATION AND OPERATORS RP25 D GENERATORS MANUAL DSE 7310 MKII ELECTRIC START...

Страница 2: ...SWITCH ELECTRICAL CONNECTIONS 10 RECEPTACLE PANEL A C ELECTRICAL CONNECTIONS GROUNDING CAM LOCK CONNECTIONS D C ELECTRICAL CONNECTIONS STARTING PROCEDURE 12 SELECTING THE CORRECT VOLTAGE DC INTERCONN...

Страница 3: ...erial number as yours If you should ever need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER ________...

Страница 4: ...rmance Poor maintenance improper or careless use can result in potentially deadly hazards from electrical shock exhaust gas asphyxiation or fire Please read all safety instructions carefully before in...

Страница 5: ...1 8 Gal Hr Engine Fluid Specifications Fuel ASTM D 975 1D or 2D EN590 or equivalent Oil Type SEE LUBRICATION SECTION Oil Capacity 8 6 Quarts Cooling System 50 50 mix GENERATOR END NOTE Review the Sta...

Страница 6: ...onsists of a multi cylinder liquid cooled engine nominally operating at 1800 rpm The generator frequency regulation is maintained by the engine governor to within 1 5 Hz cps from no load to rated load...

Страница 7: ...er emphasized Failure to use the proper oil and keep the crankcase properly filled will cause excessive engine wear and shorten its useful life PREPARING THE UNIT UNPACKING 1 As you receive your unit...

Страница 8: ...onnect the battery negative cable When removing the battery cables from the battery reverse the procedure disconnect the negative first and then the positive cable 5 Be sure all connections are tight...

Страница 9: ...second start delay and a 15 second transfer delay to allow the engine to warm up before transferring the load to the generator When the line power is restored the ATS has a 5 minute transfer delay to...

Страница 10: ...it THIS RECEPTACLE UTILIZES A HUBBLL PLUG PART CS6365 K 250V 50 AMP CIRCUIT BREAKERS These circuit breakers protect the 2 50 amp twistlock receptacles H L 120V 20 AMP CIRCUIT BREAKERS These two push b...

Страница 11: ...engine generator set and the generator set must be properly grounded to good earth ground Generally an 8 foot copper rod driven into the earth will provide a proper earth ground GROUND NEUTRAL L1 L2...

Страница 12: ...n the display SELECTING THE CORRECT VOLTAGE A variety of phase voltages are available from the four position selector switch The four basic connection patterns are Delta 120 240 Low or Parallel Wye 12...

Страница 13: ...connected can cause serious personal injury or equipment damage DO NOT jump start these engine generator sets Starting these units on a low battery or jump starting them will cause damage to the engi...

Страница 14: ...ext to the AUTO button NOTE For setting the exerciser circuit for all ATS see the operator s manual shipped with the ATS WARNING EQUIPMENT DAMAGE Never apply a load to the generator until you have fir...

Страница 15: ...e Cam Locks If you need to run an isolated neutral system the jumper between the neutral and ground musts be removed at the terminal block 4 Grounding The Unit To comply with current safety standards...

Страница 16: ...the DSE 7310 MKII Normally it will tell why the unit has failed This will shorten your trouble shooting time and in many cases prevent the replacement of parts that may not be defective Problem Possib...

Страница 17: ...HHN THHW THW 2 XHH XHHW XHHW 2 ZW 2 SIZE AWG OR KCMIL Wire Type RHW THHW THW THWN XHHW USE Wire Type TBS SA SIS THHN THW 2 THWN 2 RHH RHW 2 USE 2 XHH XHHW XHHW 2 ZW 2 44 57 75 88 101 114 132 154 176 2...

Страница 18: ...18 OPM 114 REV B SELECTOR SWITCH WIRING DIAGRAM SEE FOLLOWING PAGE FOR REFENCES...

Страница 19: ...5 6 7 5 9 6 216 5 9 51 6 5 37 21 7 33 1 8 21 5 56 5 6 7 87 67 6 6 7 6 1 6 6 7 6 1 0 5 029 5 1 8 6 1 83 7 1 8 5 6 00 5 2 6 6 7 00 5 9 5 286 1 335 7 7 92 7 6 725 6 7 66 0 7 7 7 5 1 02 3 57 5 7 6 5 1 217...

Страница 20: ...20 OPM 114 REV B DSE 7310 MKII WIRING DIAGRAM...

Страница 21: ...PHASE AC WIRING HIGH AND LOW WYE THREE PHASE L 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS 24 5060 00 60708 165 REE PHASE AC WIRING H AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS SE HIGH WYE TS...

Страница 22: ...GLE PHASE 240 VOLTS G 4 LEAD THREE PHASE WIRING DELTA THREE PHASE DELTA 120 240V SINGLE PHASE AC WIRING 4 LEAD 5060 00 60708 165 THREE PHASE DELTA 120 240 VOLTS THREE PHAS WIRING DE SINGLE PHASE 120...

Страница 23: ...1 725 1 1 51 66 211 725 8 7 7 21 2 22 17 2 3 8 6 1 725 2 3 8 5 67 57 62 12 3 27 5 5 5 9 6 216 5 9 51 6 5 37 21 7 33 6HH 6KHHW 56 5 61 6 6 7 6 1 6 6 76 6 1 6 6 7 6 6 7 1 335 7 7 1 1 51 66 7 7 7 5 1 02...

Страница 24: ...d fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some st...

Отзывы: