60706-195

Page 9

0210-00

B - Generator Circuit Breaker, This circuit breaker provides
overload protection for the generator.  Your power feeds from the
transfer switch will connect to the bottom lugs on the circuit
breaker.  The generator power feeds have already been wired
into the upper lugs.

The table below gives you the circuit breaker size,  lug wire sizes
and torque specification.  (see the actual breaker for additional
information  and restrictions)

kW

Voltage PH

Amp

Wire Capability

Lug Torque

40

120/240

1

175

#4 AWG - 300 MCM 250 in lbs

40

120/208

3

150

#4 AWG - 300 MCM 250 in lbs

40

120/240

3

125

#4 AWG - 300 MCM 250 in lbs

40

277/480

3

60

#14 - #1/0 AWG

80 in lbs

30

120/240

1

125

#12 AWG -2/0 AWG 50 in lbs

30

120/208

3

100

#12 AWG -2/0 AWG 50 in lbs

30

120/240

3

90

#12 AWG -2/0 AWG 50 in lbs

30

277/480

3

45

#14 - #1/0 AWG

80 in lbs

Minimum Conductor Sizes between the Generator and the ATS.
Based on wire type and temperature rating. Wire has been
derated for 40

C ambient temperatures.

Cu Conductor

Al Conductor

C/B

        Wire Temperature Rating

kW Voltage PH Amp 75

0

C

90

0

C

75

0

C

90

0

C

40 120/240 1

175

3/0 AWG 2/0 AWG 250 MCM 4/0 AWG

40 120/208 3

150

2/0 AWG 1/0 AWG 3/0 AWG 2/0 AWG

40 120/240 3

125

1/0 AWG #1 AWG

3/0 AWG 2/0 AWG

40 277/480 3

60

#4 AWG #6 AWG

#3 AWG #4 AWG

30 120/240 1

125

1/0 AWG #1 AWG

3/0 AWG 2/0 AWG

30 120/208 3

100

#2 AWG #3 AWG

1/0 AWG #1 AWG

30 120/240 3

90

#2 AWG #3 AWG

1/0 AWG #2 AWG

30 277/480 3

45

#6 AWG #8 AWG

#4 AWG #6 AWG

For additional information on wire sizing refer to table 310-16 of
the National Electrical Code ANSI/NFPA 70.

C - Ground Lug, These ground lugs are bonded to ground and
are provided for you to connect your ground wire from the transfer
switch to.  The lugs on the 40 kW will handle wire sizes #6 AWG
to 250 MCM and should be torqued to 250 in. lbs. The lugs on the
30 kW will accommodate #6 AWG to 250 MCM  and should be
torqued to 250 in. lbs.

D. 120 Volt Terminal Block, This terminal block is provide for the
120 volt/ 15 amp feed from customers distrubution panel for the
block heater and the trickle charger.

****************

*****  WARNING  *****

****************

  A main line circuit breaker has been provided inside the genera-
tor housing. During all wiring installations make sure the breaker
is in the off position and the generator operation switch is in the
off position.

****************

*****  WARNING  *****

****************

EQUIPMENT DAMAGE - When installing a Three Phase 240 volt
system be sure you know which lead is the high voltage "wild" leg
(208 Volt line to neutral). The generator normally carries the high
voltage on the G2 lead.

The load current carrying wires (L) and (T) must be sized to
handle the maximum load current without excessive voltage drop.
By code, the wire must be heavy enough to handle the full current
rating of the main line circuit-breaker (or fuse) in the entrance (or
sub-panel) protecting the contactor switch.

 All wires should be installed in rigid or flexible conduit.  (Knock-
outs are provided in the control box).

See the manual shipped with the Automatic Transfer Switch for
connection locations in the switch.  Connections in each switch
will vary depending on the type of  switch and the manufacturer.

GROUNDING

A grounding lug has been provided on the engine generator set
to grounded to earth ground if required.  Check with your local
codes.  Generally a 6 foot copper rod driven into the earth will
provide a proper earth ground.

D.C. ELECTRICAL
CONNECTIONS

NOTE:

There are varies DC connectors on the engine that have
nothing connected to them.  This was done intentional, these
connectors are for END OF LINE TESTING and other various
diagnostic tests.  There are not used during normal opera-
tions and can just be ignored.

All DC connections are completed in the small box just below the
engine control cabinet.  In addition there are two small fuses
mounted on the top of the engine control cabinet that protect both
the engine control and all the other DC connections.  See the
display on pervious page for call outs.

CONTROL PANEL LAYOUT

A - DGC-2020 Digital Gen-Set Control.  See Explanation on
page 3.

Содержание PSS30

Страница 1: ...PACKAGE STANDBY SYSTEMS INSTALLATION AND OPERATIONS MANUAL PSS30 B PSS40 E...

Страница 2: ...ned SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries Read and understand all instructions...

Страница 3: ...electrician or contractor The installation must comply with all national state and local codes g Always make sure unit is disabled before placing your hands anywhere near the fan belts alternator or...

Страница 4: ...er liquid cooled engine equipped to run on L P N G fuel The engine operates at 1800 rpm and frequency regulation is maintained by the electronic governor within 5 cycles variation from no load to rate...

Страница 5: ...emperature monitoring over crank protection ECU specific protection elements and diagnostic reporting Metered engine parameters include oil pressure coolant A Liquid Crystal Display The backlit 64 by...

Страница 6: ...setting or resetting the system clock 1 Press K right key for initial set or K left to back up up down to choose menu item and time date element to be changed 2 Press L Edit to access change mode to e...

Страница 7: ...engine s requirements and assist in making you aware of the decisions you must make In no case should the instructions or information provided be interpreted to conflict with any local state or natio...

Страница 8: ...nstalled from the secondary regula tor to the generator set WARNING PERSONAL DANGER Do not use galvanized pipe in fuel line runs The galvanized coating can become eroded and flake off causing possible...

Страница 9: ...performed or supervised only by personnel knowledgeable of batteries and the required precautions Keep unauthorized personnel away from batteries When installing or replacing batteries use the proper...

Страница 10: ...e to do so can cause damage to the engine control module in the generator set All connections must be clean and tight Check the electrolyte fluid in the battery periodically to be sure it is above the...

Страница 11: ...t Terminal Block This terminal block is provide for the 120 volt 15 amp feed from customers distrubution panel for the block heater and the trickle charger WARNING A main line circuit breaker has been...

Страница 12: ...will not start and run without either the jumper installed or a remote N C switch installed G Fuel Select Toggle Switch This SWITCH allows you to change the engine from one fuel to the other See Chang...

Страница 13: ...generator terminals in the Automatic Transfer Switch The voltage between the G1 and the G3 terminals should be the same as it was on the generator front panel The voltage should also be checked betwe...

Страница 14: ...3 Governor is defective 4 AC short in generator components ATS PANEL WILL NOT TRANSFER TO EMERGENCY SUPPLY GENERATOR 1 No AC generator output from generator 2 Defective transfer switch controller 3 In...

Страница 15: ...60706 195 Page 13 0210 00 VOLTAGE REGULATOR WIRING THREE PHASE AND SINGLE PHASE...

Страница 16: ...Page 14 0210 00 60706 195 THREE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS...

Страница 17: ...60706 195 Page 15 0210 00 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING SINGLE PHASE 120 240 VOLTS THREE PHASE DELTA 120 240 VOLTS...

Страница 18: ...Page 16 0210 00 60706 195 DC SCHEMATIC...

Страница 19: ...0706 195 Page 17 0210 00 PSS30 OUTLINE DRAWING AND WIRING ENTRANCE PSS40 OUTLINE DRAWING AND WIRING ENTRANCE DIMENSIONS ARE SUBJECT TO CHANGE ALWAYS OBTAIN A CERTIFIED DRAWING FOR CONSTRUCTION PURPOSE...

Страница 20: ...e are limited to 12 months or 1000 hours which ever accurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation on t...

Отзывы: