background image

7

60706-238/H

Never use gasoline that has been stored for an extended 

period of time as the fuel will lose its volatile properties and 

you will be left with varnish residue.

The use of additives, such as STA-BIL, or an equivalent, will 

minimize the formation of fuel gum deposits. If a unit has 

been out of operation for an extended period of time, it 

is best to drain old fuel from the engine and replace with 

fresh fuel before attempting to start. 

See the engine manual for special instructions for operating 

this unit over 5000 feet.

INSTALLING THE FUEL LINE

The information in this manual is offered to assist you in 

providing the proper vapor fuel supply for your engine. This 

information is only provided to advise you of the engine’s 

requirements and the decisions you must make. In no case 

should this information be interpreted to conflict with any 

local, state, or national codes. If in doubt, always follow local 

codes.

DANGER: FIRE/PERSONAL INJURY

All fuel lines must be installed by a qualified fuel 

supplier.

DANGER: FIRE/PERSONAL INJURY

The NG fuel supply line must always be shut off when 

the engine is not running. Failure to do so may allow 

fuel to leak at the unit.

DANGER: PERSONAL INJURY

Units that are intended to be run unattended MUST 

have an electric fuel solenoid installed. This solenoid 

MUST be wired to AUTOMATICALLY turn off the fuel 

whenever the engine stops.

The fuel source should be as close as possible to the 

outdoor operating location. This will reduce the installation 

cost of fuel runs. Connect the fuel supply line to the inlet 

of the fuel demand regulator on the unit using a locally 

approved flexible fuel line (see table for recommended line 

size). The pressure supplied to the demand regulator must 

be 4 to 6 ounces or 7 to 11 inches w.c. (water column). 

The primary regulator at the fuel supply must be capable of 

delivering the proper volume of fuel at this pressure.

Have your local fuel supplier install a protected fuel 

connection at the outside operating location. They should 

also install a lockable fuel shut off valve at the connection 

point. An approved flexible fuel line must be installed 

between the engine generator set and the supply line. The 

fuel line used to connect the supply line to the demand 

regulator must be a locally approved flexible fuel line. 

Products used will vary in different regions depending on 

availability and local codes. Consult with your local fuel 

supplier to ensure complete compliance with ALL codes.

 

 

1. Remove the plastic cover plug from the demand 

   regulator.

 

 

2. Connect the flex fuel line to the demand regulator or 

 

  the optional solenoid.

A positive fuel shut-off device must be installed in the fuel 

line close to the engine-generator set. This manual shut-off 

valve is required by code even if the 12 Volt fuel solenoid 

kit is installed. This optional 12 Volt DC valve is available 

through your local WINCO dealer and can be used to shut 

off during normal periods of operation without having to 

shut off the manual valve.

DANGER: PERSONAL INJURY

Do NOT use galvanized pipe in the fuel line runs. The 

galvanized coating will become eroded and flake 

off, causing possible obstruction or damage to the 

regulator or fuel valve. The obstruction could cause an 

inoperative engine or an explosive fuel leak.

Size of pipe required for generators operating on NG gas.

  Length of fuel line*     Fuel line size

 

 

Less than 25 feet 

 

 

3/4/ in black pipe

  25-100 

Feet 

    1 

in 

black 

pipe

  Over 

100 

feet    Not 

recommended**

*Allow an additional 3 feet for each standard elbow. Do not 

use ‘street ells’ (restrictive).

**Consult factory for fuel run over 100 feet.

DANGER: FIRE/PERSONAL INJURY

Be careful when sealing gas joints. Excessive sealing 

compound can be drawn into the solenoid, regulator, 

or carburetor causing an engine malfunction or 

dangerous fuel leak.

DANGER: PERSONAL INJURY

Do NOT use galvanized pipe in the fuel line runs. The 

galvanized coating will become eroded and flake 

off, causing possible obstruction or damage to the 

regulator or fuel valve. The obstruction could cause an 

inoperative engine or an explosive fuel leak.

Correct fuel pressure cannot be stressed enough. The most 

common cause for inoperative systems is an inadequate 

or incorrect fuel pressure. Power and performance of the 

engine is in direct relation to the correctness of the fuel 

system. The following diagram is of a typical NG installation. 

Reference numbers 2 and 3 in the previous diagram are 

system parts supplied by the customer. Reference number 4 

is the engine-generator set. 

The following table is of the fuel pressure reading at each 

reference in the system.

13240-11

8

60706-236

Natural Gas

          

2

3

4

UNIT OFF

LINE PSI 7-11 in

7-11 in

 

4-6 oz   

4-6 oz

STARTING 

LINE PSI 7-11 in

7-11 in

4-6 oz 

4-6 oz 

NO LOAD

LINE PSI 7-11 in

7-11 in

4-6 oz

4-6 oz

FULL LOAD

LINE PSI  7-11 in

7-11 in

4-6 oz

4-6 oz

Remember that whichever fuel delivery system or 

type of vapor fuel used, the fuel pressure at the 

demand regulator installed on the engine generator 

must be between 4 and 6 oz. (7-11 inches of water 

column).  Any lower pressure and the unit will starve 

IRUIXHOXQGHUORDG$Q\KLJKHUDQGWKHXQLWZLOOµÀRRG¶

when attempting to start. 

LP TANK SIZING

The tank sizes shown below are the smallest recom-

mended tank sizes based on the outside temperature. 

Once above this minimum acceptable size, the size of 

L.P. tank used will generally depend on how long you 

ZDQWWKHXQLWWRUXQZLWKRXWUH¿OOLQJ.HHSLQPLQG

the colder it gets the slower L.P. will vaporize.  This 

is the reason for the larger tanks at low temperature.  

Minimum sizing is not based on running time. 

Temp f. 60 deg 

30 deg 

0 deg 

-20 deg 

150 gal

250 gal

500 gal 1000 gal

CHANGING FUEL TYPES

These engine generator sets are designed to run 

on three different fuels; gasoline, natural gas or LP 

vapor.  They may be easily changed from one fuel to 

another.

FROM GASOLINE TO LP/NG

1.  With the engine running turn off the gasoline  

 fuel valve.

2.  Run the engine until it runs out of fuel.

3.  Remove the plastic insert from the demand  

regulator.

 ,QVWDOODORFDOO\DSSURYHGÀH[LEOHIXHOOLQH

 &RQQHFWWKH/31*YDSRUIXHOOLQHWRWKHÀH[

-

ible fuel line. You can’t connect the black iron 

pipe dir

 $OOWKUHHXQLWVKDYHWZRGLIIHUHQWKRVH¿WWLQJV

on the top of the demand regulator. One is for  

LP and one is for Natural Gas. Make sure the  

KRVHLVDWWDFKHGWRWKHSURSHU¿WWLQJ6HHWKH

picture below.

7.  Turn on the vapor fuel.

8.  Start the engine.

9 .  Apply the load to the generator.

FROM LP/NG TO GASOLINE

1.  With the engine running turn off the LP/NG 

fuel supply.

2.  Run the engine until it runs out of fuel.

 5HPRYHWKHÀH[LEOHIXHOOLQHIURPWKHGHPDQG

regulator.

4.  Reinstall the plastic insert in the regulator. 

5.  Check to be sure the gasoline fuel valve is off.

6.  Fill the gasoline fuel tank.

7.  Turn on the gasoline fuel valve.

8.  Start the engine.

If the optional FUEL SOLENOID kit has been in 

stalled on the unit all vapor fuel connection will be 

made at the 12 volt gas valve.

Содержание HPS6000HE/I

Страница 1: ...ber as yours If you should ever need to contact us concerning this unit it will help us to respond to your needs faster MODEL _________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE DATE _________________________________________ DEALER NAME ___________________________________________ DEALER PHONE ________________________________________ ...

Страница 2: ...SPARK PLUG CARBON CANISTER GENERATOR CARE 18 EXERCISING THE GENERATOR GENERATOR MAINTENANCE CLEANING TROUBLESHOOTING 18 RECEPTACLE WIRING DIAGRAM 19 CA EVAP EMISSION CONTROL 20 LIMITED WARRANTY 20 SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the generator Read and understand all instructions in the manual before ...

Страница 3: ...turer Mecc Alte Spa Generator Model Number S16W 130 A Part Number 16346 006 Rotor Resistance 3 95 Ohms Stator Resistance 0 36 Ohms Cap Winding Resistance 2 45 Ohms Capacitors 25 mF Capacitor Part Number 16346 612 ENGINE Engine Manufacturer Honda Engine Model Number GX340 Type RT2VWE2 Code GCBET Spark Plug Gap 0 030 in Intake Valve Clearance 0 006 0 010 in Exhaust Valve Clearance 0 010 0 012 in Oil...

Страница 4: ...the earth 2 FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not smoke or use open flame near the generator set or fuel tank D Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate E Store fuel only in a...

Страница 5: ...ds The diagram below represents this 5 500 watt rated output generator A B represent the 120 volt output legs of this generator Up to 2 250 watts at 120 volts 22 9 Amps can be drawn from the receptacles attached to either A or B output legs This generator is capable of producing 22 9 Amps of 240 volt current at C Check the appliance or tool nameplates for the current and voltage to insure compatib...

Страница 6: ...el This engine is certified to operate on unleaded gasoline with a minimum octane rating of 87 or higher Gasoline containing no more than 10 ethanol is accepted CAUTION EQUIPMENT DAMAGE Do not use unapproved gasolines such as E15 or E85 Do NOT mix oil in the gasoline Use of unapproved fuels will damage the engine components and void the engine warranty Use of fuels with content of ethanol greater ...

Страница 7: ... with your local fuel supplier to ensure complete compliance with ALL codes 1 Remove the plastic cover plug from the demand regulator 2 Connect the flex fuel line to the demand regulator or the optional solenoid A positive fuel shut off device must be installed in the fuel line close to the engine generator set This manual shut off valve is required by code even if the 12 Volt fuel solenoid kit is...

Страница 8: ...onnect the ridged mounted pipe directly 6 Turn on the vapor fuel 7 Start the engine 8 Apply the load to the generator NG TO GASOLINE 1 With the engine running turn off the NG fuel supply 2 Run the engine until it runs out of fuel 3 Remove the flexible fuel line from the demand regulator 4 Reinstall the plastic insert in the regulator 5 Check to be sure the gasoline fuel valve is off 6 Fill the gas...

Страница 9: ...nect the positive battery cable to the bat terminal first Then connect the negative battery cable to the bat terminal Make sure all connections are clean and tight Reverse the sequence when disconnecting disconnect the negative cable first The engines produce enough direct current to keep the battery charged under normal operating conditions but were not intended to be used as a battery charger WA...

Страница 10: ...low a certain point the low oil module on the engine will shut it down This oil warning system will automatically stop the engine before the oil level reaches a critical danger point This feature is designed to prevent costly repairs and downtime CAUTION EQUIPMENT DAMAGE Allowing the engine to shutdown repeatedly on low oil level may cause excessive wear which can be cumulative ...

Страница 11: ...rip lightly until resistance is felt then pull briskly 6 When the engine starts open the choke gradually 7 The engine should promptly come up to operating speed NOTICE Do not allow the starter grip to snap against the en gine Return it gently to prevent damage to the starter CAUTION EQUIPMENT DAMAGE Never permit the choke to remain on after the engine has run for a short time It is not necessary t...

Страница 12: ... Because the engine vacuum needs to activate the fuel system it is almost impossible to manual start the unit using NG 1 Check oil level refill as needed 2 Turn on the NG fuel supply 3 NEVER use the choke when operating on NG 4 Turn the engine switch to the on position 5 Operating the starter Rotate the key switch briefly to START position The starter life is improved by using shorter starting cyc...

Страница 13: ...do so could result in damage to equipment plugged into the unit and possi ble injury to the individual All engines have a tendency to slow down when a load is applied When the electrical load is connected to the generator the engine is more heavily loaded and as a result the speed drops slightly This slight decrease in speed together with the voltage drop within the generator itself results in a s...

Страница 14: ...erator at these sites a secondary emergency distribution panel may have to be installed The emergency distribution panel must be installed by a licensed electrician according to all CONNECTING THE LOADS APPLYING THE LOADS Allow the engine to warm up for two or three minutes before applying any load This will allow the engine to reach normal operating temperature and oil to circulate throughout the...

Страница 15: ...load on the generator during the initial start up See the nameplate on your generator for the amperage capabilities of your unit CAUTION EQUIPMENT DAMAGE Failure to properly limit and balance the load applied to the generator will cause the generator to produce low voltage and may damage the engine generator set It may also cause severe damage to the loads con nected to the generator at that time ...

Страница 16: ...ecommendation section in this manual NOTE This engine requires 38 4 ounces 1 2 qt of oil if completely drained Use caution when refilling the engine as some residual oil may have remained in the engine Always use the dipstick when filling the engine with oil to prevent overfilling E Replace filler plug F Start engine up and warm it up G After warming up the engine recheck the oil level and refill ...

Страница 17: ... every 300 hours of operation Always replace with the same spark plug that came in the engine and check gap before installing Spark plug gap is 0 030 Poor spark will also occur if spark plug wire does not fit firmly on spark plug If this happens reform the terminal to fit firmly on spark plug tip CARBON CANISTER Designed to collect store and dispose of fuel vapors created in the fuel tank fuel sys...

Страница 18: ...roperly should it be needed in an emergency GENERATOR MAINTENANCE Any major generator service including the installation or replacement of parts should be performed only by a qualified electrical service technician USE ONLY FACTORY APPROVED REPAIR PARTS A Bearing The bearing used in these generators is a heavy duty double sealed ball bearing They require no maintenance or lubrication B Receptacles...

Страница 19: ...19 60706 238 H GND GND G ND GND GND GND G3 G3 N N N N N N N G3 G1 G1 G1 G1 G1 G1 G1 G1 G1 G3 RECEPTACLE WIRING DIAGRAM ...

Страница 20: ...sole remedy for a failure under this warranty shall be limited to the repair of the product At WINCO s option material found to be defective in material or workmanship under normal use and service will be repaired or replaced For warranty service return the product within the warranty period to your nearest WINCO Authorized Service Center or to WINCO in Le Center Minnesota Duration Consumer Commer...

Отзывы: