INSTALLING LP/NG FUEL LINE

The information in this manual is offered to assist you in 

providing the proper vapor fuel supply for your engine. This 

information is only provided to advise you of the engine’s 

requirements and the decisions you must make. In no case 

should this information be interpreted to conflict with any 

local, state, or national codes. If in doubt, always follow local 

codes.

DANGER: FIRE/PERSONAL INJURY

All fuel lines must be installed by a qualified fuel 

supplier.

DANGER: FIRE/PERSONAL INJURY

The LP/NG fuel supply line must always be shut off 

when the engine is not running. Failure to do so may 

allow fuel to leak at the unit.

DANGER: PERSONAL INJURY

Units that are intended to be run unattended MUST 

have an electric fuel solenoid installed. This solenoid 

MUST be wired to AUTOMATICALLY turn off the fuel 

whenever the engine stops.

The fuel source should be as close as possible to the 

outdoor operating location. This will reduce the installation 

cost of fuel runs. Connect the fuel supply line to the inlet 

of the fuel demand regulator on the unit using a locally 

approved flexible fuel line (see table for recommended line 

size). The pressure supplied to the demand regulator must 

be 4 to 6 ounces or 7 to 11 inches w.c. (water column). 

Any lower pressure and the unit will starve for fuel under 

load. Any higher and the unit will ‘flood’ when attempting 

to start. The primary regulator at the fuel supply must be 

capable of delivering the proper volume of fuel at this 

pressure.

Have your local fuel supplier install a protected fuel 

connection at the outside operating location. They should 

also install a lockable fuel shut off valve at the connection 

point. An approved flexible fuel line must be installed 

between the engine generator set and the supply line. The 

fuel line used to connect the supply line to the demand 

regulator must be a locally approved flexible fuel line. 

Products used will vary in different regions depending on 

availability and local codes. Consult with your local fuel 

supplier to ensure complete compliance with ALL codes.

 

1. Remove the plastic cover plug from the demand 

   regulator.

 

2. Connect the flex fuel line to the demand regulator or 

 

  the optional solenoid.

Size of pipe required for generators operating on NG/LP 

gas.

  Length of fuel line*     Fuel line size

 

 

Less than 25 feet 

 

 

3/4 in black pipe

  25-100 

Feet 

    1 

in 

black 

pipe

  Over 

100 

feet    Not 

recommended**

*Allow an additional 3 feet for each standard elbow. Do not 

use ‘street ells’ (restrictive).

**Consult factory for fuel run over 100 feet.

DANGER: FIRE/PERSONAL INJURY

Be careful when sealing gas joints. Excessive sealing 

compound can be drawn into the solenoid, regulator, 

or carburetor causing an engine malfunction or dan-

gerous fuel leak.

DANGER: PERSONAL INJURY

Do NOT use galvanized pipe in the fuel line runs. The 

galvanized coating will become eroded and flake off, 

causing possible obstruction or damage to the reg-

ulator or fuel valve. The obstruction could cause an 

inoperative engine or an explosive fuel leak.

NATURAL GAS

Correct fuel pressure cannot be stressed enough. The most 

common cause for inoperative systems is an inadequate 

or incorrect fuel pressure. Power and performance of the 

engine is in direct relation to the correctness of the fuel 

system. The following diagram is of a typical NG installation. 

Reference numbers 2 and 3 in the previous diagram are 

system parts supplied by the customer. Reference number 4 

is the engine-generator set. The following table is of the fuel 

pressure reading at each reference in the system.

Natural Gas Fuel Pressure Table

1

2

3

4

Unit Off

Tank PSI

10-15 lbs

7-11 in

4-6 oz

7-11 in

4-6 oz

Starting

Tank PSI

10-15 lbs

7-11 in

4-6 oz

7-11 in

4-6 oz

No Load

Tank PSI

10-15 lbs

7-11 in

4-6 oz

7-11 in

4-6 oz

Full Load

Tank PSI

10-15 lbs

7-11 in

4-6 oz

7-11 in

4-6 oz

LP VAPOR

LP TANK SIZING

The tank sizes shown below are the smallest recommended 

tank sizes based on the outside temperature. Once above 

this minimum acceptable size, the size of LP tank used will 

generally depend on how long you want the unit to run 

without refilling. Keep in mind the colder it gets, the slower

LP will vaporize. This is the reason for the larger tanks at low 

temperatures. Minimizing sizing is NOT based on running 

time.

Temp (F)

60°

30°

-20°

150 gal

250 gal

500 gal

1000 gal

13240-11

8

60706-236

Natural Gas

          

2

3

4

UNIT OFF

LINE PSI 7-11 in

7-11 in

 

4-6 oz   

4-6 oz

STARTING 

LINE PSI 7-11 in

7-11 in

4-6 oz 

4-6 oz 

NO LOAD

LINE PSI 7-11 in

7-11 in

4-6 oz

4-6 oz

FULL LOAD

LINE PSI  7-11 in

7-11 in

4-6 oz

4-6 oz

Remember that whichever fuel delivery system or 

type of vapor fuel used, the fuel pressure at the 

demand regulator installed on the engine generator 

must be between 4 and 6 oz. (7-11 inches of water 

column).  Any lower pressure and the unit will starve 

IRUIXHOXQGHUORDG$Q\KLJKHUDQGWKHXQLWZLOOµÀRRG¶

when attempting to start. 

LP TANK SIZING

The tank sizes shown below are the smallest recom-

mended tank sizes based on the outside temperature. 

Once above this minimum acceptable size, the size of 

L.P. tank used will generally depend on how long you 

ZDQWWKHXQLWWRUXQZLWKRXWUH¿OOLQJ.HHSLQPLQG

the colder it gets the slower L.P. will vaporize.  This 

is the reason for the larger tanks at low temperature.  

Minimum sizing is not based on running time. 

Temp f. 60 deg 

30 deg 

0 deg 

-20 deg 

150 gal

250 gal

500 gal 1000 gal

CHANGING FUEL TYPES

These engine generator sets are designed to run 

on three different fuels; gasoline, natural gas or LP 

vapor.  They may be easily changed from one fuel to 

another.

FROM GASOLINE TO LP/NG

1.  With the engine running turn off the gasoline  

 fuel valve.

2.  Run the engine until it runs out of fuel.

3.  Remove the plastic insert from the demand  

regulator.

 ,QVWDOODORFDOO\DSSURYHGÀH[LEOHIXHOOLQH

 &RQQHFWWKH/31*YDSRUIXHOOLQHWRWKHÀH[

-

ible fuel line. You can’t connect the black iron 

pipe dir

 $OOWKUHHXQLWVKDYHWZRGLIIHUHQWKRVH¿WWLQJV

on the top of the demand regulator. One is for  

LP and one is for Natural Gas. Make sure the  

KRVHLVDWWDFKHGWRWKHSURSHU¿WWLQJ6HHWKH

picture below.

7.  Turn on the vapor fuel.

8.  Start the engine.

9 .  Apply the load to the generator.

FROM LP/NG TO GASOLINE

1.  With the engine running turn off the LP/NG 

fuel supply.

2.  Run the engine until it runs out of fuel.

 5HPRYHWKHÀH[LEOHIXHOOLQHIURPWKHGHPDQG

regulator.

4.  Reinstall the plastic insert in the regulator. 

5.  Check to be sure the gasoline fuel valve is off.

6.  Fill the gasoline fuel tank.

7.  Turn on the gasoline fuel valve.

8.  Start the engine.

If the optional FUEL SOLENOID kit has been in 

stalled on the unit all vapor fuel connection will be 

made at the 12 volt gas valve.

Содержание Home power HPS12000HE

Страница 1: ...ould ever need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _______________________________________...

Страница 2: ...N CANISTER GENERATOR CARE 18 EXERCISING THE GENERATOR GENERATOR MAINTENANCE CLEANING TROUBLESHOOTING 18 RECEPTACLE WIRING DIAGRAM 19 CA EVAP EMISSION CONTROL 20 LIMITED WARRANTY 20 SAVE THESE INSTRUCT...

Страница 3: ...Amps 72 36 GENERATOR Generator Manufacturer Mecc Alte Spa Generator Model Number S20FS 160 A Part Number 351836 1 Rotor Resistance 6 57 Ohms Stator Resistance 0 124 Ohms Cap Winding Resistance 0 60 O...

Страница 4: ...the earth 2 FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C...

Страница 5: ...te performance these units should never be run in small compartments without positive fresh air flow RESTRICTED USES DO NOT remove from the cradle assembly Removal of the generator from the cradle ass...

Страница 6: ...al horsepower motors take about the same amount of current to run them whether they are Repulsion Induction RI Capacitor Cap or Split Phase SP type If the electric motor is connected to a hard startin...

Страница 7: ...with the recommended oil to the upper limit mark on the oil level dipstick Running the engine with a low oil level can cause engine damage This type of damage is not covered by the Distributor s Limit...

Страница 8: ...d flake off causing possible obstruction or damage to the reg ulator or fuel valve The obstruction could cause an inoperative engine or an explosive fuel leak NATURAL GAS Correct fuel pressure cannot...

Страница 9: ...rams above are system parts supplied by customer Reference number 4 is the engine generator set Below is a table of the fuel pressure reading at each reference in the system Fuel Pressure Table Single...

Страница 10: ...came with instructions and parts list After installing the dolly kit keep instructions and parts list for future reference OPTIONAL FUEL SOLENOID KIT An optional 12 Volt DC fuel solenoid kit is availa...

Страница 11: ...e to the bat terminal first Then connect the negative battery cable to the bat terminal Make sure all connections are clean and tight Reverse the sequence when disconnecting disconnect the negative ca...

Страница 12: ...proved by using shorter starting cycles with time to cool off between cranking cycles Do not operate the starter more than 5 seconds and wait at least 10 seconds before operating the starter again 7 6...

Страница 13: ...ment plugged into the unit and possi ble injury to the individual All engines have a tendency to slow down when a load is applied When the electrical load is connected to the generator the engine is m...

Страница 14: ...GENERATORS This WINCO portable generator ships with a bonded neutral and overcurrent protection NFPA 70 refers to this as a separately derived system When connecting it to a building a transfer switch...

Страница 15: ...nameplate on your generator for the amperage capabilities of your unit CAUTION EQUIPMENT DAMAGE Failure to properly limit and balance the load applied to the generator will cause the generator to prod...

Страница 16: ...l can damage paint and some types of plastic Be careful not to spill fuel when filling your fuel tank Damage caused by spilled fuel is not covered under the Distributor s Limited Warranty Gasoline is...

Страница 17: ...ET AIR CLEANER COVER LATCH AIR CLEANER CASE PACKING FOAM FILTER ELEMENT PAPER FILTER ELEMENT AIR CLEANER COVER WING NUT AIR CHAMBER 9 Operating the engine without an air filter or with a damaged air f...

Страница 18: ...perly should it be needed in an emergency GENERATOR MAINTENANCE Any major generator service including the installation or replacement of parts should be performed only by a qualified electrical servic...

Страница 19: ...19 60706 236 J 17 13240 11 60706 236 CONTROL PANEL WIRING DIAGRAM RECEPTACLE WIRING DIAGRAM...

Страница 20: ...quest THERE ARE NO EXPRESS WARRANTIES OTHER THAN THOSE DESCRIBED HEREIN THERE ARE NO OTHER WARRANTIES EXPRESSED OR IMPLIED OR OTHERWISE CREATED INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILI...

Отзывы: