UNIT CAPABILITIES

GENERATOR CONNECTIONS

120 Volt and 240 Volt receptacles are provided for 

connection to various loads. The diagram below represents 

this 10,800 watt (rated output) generator. A & B represent 

the 120 volt output legs of this generator. Up to 5400 watts 

at 120 volts (45 Amps) can be drawn from the receptacles 

attached to either A or B output legs. This generator is 

capable of producing 45 Amps of 240 volt current at C. 

Check the appliance or tool nameplates for the current and 

voltage to insure compatibility. Remember that power taken 

from C reduces the power available at equally both A and B 

and vice versa. Output is based on gasoline fuel, derate 10% 

for LP and 20% for NG.

STARTING ELECTRIC MOTORS

Electric motors require much more current (amps) to start 

them than to run them. Some motors, particularly low cost 

split-phase motors, are very hard  to start and require 5 to 7 

times as much starting current as running current. Capacitor 

motors are easier to start and usually require 2 to 4 times 

as much starting current as running current. Repulsion 

Induction motors are the easiest to start and require only 1 

1/2 to 2 1/2 times as much starting as running current.

Most fractional horsepower motors take about the same 

amount of current to run them whether they are Repulsion 

Induction (RI), Capacitor (Cap), or Split-Phase (SP) type.

If the electric motor is connected to a hard starting load 

such as an air compressor, it will require more starting 

current. If it is connected to a light load, or no load such as 

a power saw, it will require less starting current. The exact 

requirement will also vary with the brand or design of the 

motor.

Self-exciting generators respond to severe overloading 

differently than utility power. When overloaded, the engine 

is not able to supply enough power to bring the electric 

motor up to operating speed. The generator responds with 

high initial starting current, but the engine speed drops 

sharply. The overload may stall the engine. If allowed to 

operate at very low speeds, the electric motor starting 

winding will burn out in a short time. The generator 

winding might also be damaged.

CAUTION: EQUIPMENT DAMAGE

Running the generator set under these conditions may 

result in damage to the generator stator as well as the 

motor winding.

The heavy surge of current required for starting motors 

is required for only an instant. The generator will not be 

damaged if it can bring the motor up to speed in a few 

seconds of time. If difficulty is experienced in starting 

motors, turn all other electrical loads off and if possible 

reduce the load on the electric motor.

Содержание Home power HPS12000HE

Страница 1: ...ould ever need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _______________________________________...

Страница 2: ...N CANISTER GENERATOR CARE 18 EXERCISING THE GENERATOR GENERATOR MAINTENANCE CLEANING TROUBLESHOOTING 18 RECEPTACLE WIRING DIAGRAM 19 CA EVAP EMISSION CONTROL 20 LIMITED WARRANTY 20 SAVE THESE INSTRUCT...

Страница 3: ...Amps 72 36 GENERATOR Generator Manufacturer Mecc Alte Spa Generator Model Number S20FS 160 A Part Number 351836 1 Rotor Resistance 6 57 Ohms Stator Resistance 0 124 Ohms Cap Winding Resistance 0 60 O...

Страница 4: ...the earth 2 FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C...

Страница 5: ...te performance these units should never be run in small compartments without positive fresh air flow RESTRICTED USES DO NOT remove from the cradle assembly Removal of the generator from the cradle ass...

Страница 6: ...al horsepower motors take about the same amount of current to run them whether they are Repulsion Induction RI Capacitor Cap or Split Phase SP type If the electric motor is connected to a hard startin...

Страница 7: ...with the recommended oil to the upper limit mark on the oil level dipstick Running the engine with a low oil level can cause engine damage This type of damage is not covered by the Distributor s Limit...

Страница 8: ...d flake off causing possible obstruction or damage to the reg ulator or fuel valve The obstruction could cause an inoperative engine or an explosive fuel leak NATURAL GAS Correct fuel pressure cannot...

Страница 9: ...rams above are system parts supplied by customer Reference number 4 is the engine generator set Below is a table of the fuel pressure reading at each reference in the system Fuel Pressure Table Single...

Страница 10: ...came with instructions and parts list After installing the dolly kit keep instructions and parts list for future reference OPTIONAL FUEL SOLENOID KIT An optional 12 Volt DC fuel solenoid kit is availa...

Страница 11: ...e to the bat terminal first Then connect the negative battery cable to the bat terminal Make sure all connections are clean and tight Reverse the sequence when disconnecting disconnect the negative ca...

Страница 12: ...proved by using shorter starting cycles with time to cool off between cranking cycles Do not operate the starter more than 5 seconds and wait at least 10 seconds before operating the starter again 7 6...

Страница 13: ...ment plugged into the unit and possi ble injury to the individual All engines have a tendency to slow down when a load is applied When the electrical load is connected to the generator the engine is m...

Страница 14: ...GENERATORS This WINCO portable generator ships with a bonded neutral and overcurrent protection NFPA 70 refers to this as a separately derived system When connecting it to a building a transfer switch...

Страница 15: ...nameplate on your generator for the amperage capabilities of your unit CAUTION EQUIPMENT DAMAGE Failure to properly limit and balance the load applied to the generator will cause the generator to prod...

Страница 16: ...l can damage paint and some types of plastic Be careful not to spill fuel when filling your fuel tank Damage caused by spilled fuel is not covered under the Distributor s Limited Warranty Gasoline is...

Страница 17: ...ET AIR CLEANER COVER LATCH AIR CLEANER CASE PACKING FOAM FILTER ELEMENT PAPER FILTER ELEMENT AIR CLEANER COVER WING NUT AIR CHAMBER 9 Operating the engine without an air filter or with a damaged air f...

Страница 18: ...perly should it be needed in an emergency GENERATOR MAINTENANCE Any major generator service including the installation or replacement of parts should be performed only by a qualified electrical servic...

Страница 19: ...19 60706 236 J 17 13240 11 60706 236 CONTROL PANEL WIRING DIAGRAM RECEPTACLE WIRING DIAGRAM...

Страница 20: ...quest THERE ARE NO EXPRESS WARRANTIES OTHER THAN THOSE DESCRIBED HEREIN THERE ARE NO OTHER WARRANTIES EXPRESSED OR IMPLIED OR OTHERWISE CREATED INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILI...

Отзывы: