15
OPM-103
REV B
TROUBLE SHOOTING TABLES
ENGINE WILL NOT CRANK:
1. Low/dead battery
2. Blown DC fuses 2 Amp or 25 Amp
3. Defective DSE4510
4. Defective key switch
5. Loose or dirty battery terminals
6. Defective starter
7. Defective Start solenoid
8. Locked up engine genset
9. Defective engine harness
10. Improper battery voltage to start solenoid, fuel pump, or fuel
solenoid
ENGINE CRANKS BUT WILL NOT START
1. Improper fuel delivery to the unit
2. Fuel supply shut off
3. Fuel tank empty
4. Air in the fuel system
5. Engine fuel solenoid has not opened
6. Defective fuel pump
7. Defective fuel solenoid
8. Defective engine harness
9. Improper battery voltage to fuel pump or fuel solenoid
ENGINE STARTS, THEN STOPS AND ALARM LIGHT COMES ON
1. Engine oil pressure is low
2. Engine has water temperature
3. Refer to fault code on DSE4510
ENGINE WILL NOT COME UP TO SPEED AFTER IT STARTS
1. Insufficient fuel volume getting to the unit
a. Too small of fuel line
b. Fuel racks not opened properly
2. Governor is defective
3. AC short in generator components
NO AC OUTPUT FROM GENERATOR
1. Defective Diode
2. Defective voltage regulator
3. Defective rotor
4. Defective stator
5. Defective exciter rotor
6. Defective exciter stator
7. AC short in the output leads
8. Defective/open generator output breaker
9. Wiring error
DSE4510 INITIAL START UP
WARNING: EQUIPMENT DAMAGE:
DO NOT jump start these engine-generator sets. Starting these units
on a low battery or jump starting them will cause damage to the engine
control module.
Use the following check list to verify correct installation before starting
the engine.
□
Engine oil. Fill as required with proper grade/qty.
□
Engine coolant. Fill as required with proper mixture.
□
Unit mounting base properly bolted down.
□
Clearance for service and maintenance on all sides.
□
Proper fuel line material and size.
□
All fuel line connections tight.
□
Battery connections clean and tight
□
Battery fully charged.
□
All AC and DC wiring installed and properly protected.
After completing the previous checklist, the engine-generator set is
ready for initial start-up.
STARTING PROCEDURE
MANUAL MODE
WARNING: EQUIPMENT DAMAGE:
Before attempting to start this unit, complete your pre-start checklist
and ensure the generator mainline circuit breaker is in the proper
position prior to starting. Starting this unit without it properly connected
can cause serious personal injury or equipment damage.
1. Press and release the red Stop/Reset button
2. Press and release the green Start Engine button. The engine-
generator set will crank and start automatically. If the engine fails
to start, it will display a fault code and the common alarm
indicator will start blinking. See the fault code appendix portion of
this
manual.
3. With the unit running smoothly, check the no load voltage and
frequency of the generator output.
4. Once the unit is running and the safety on time has elapsed, the
engine monitoring switches are active for low oil pressure and
high water temperature.
5. After the engine is up and running, the circuit breaker can be
closed to power your loads. During periods of very cold operation,
it is best to let the engine warm up for a few minutes before
applying the load.
6. When stopping the unit, it is best to turn off all the loads before
pressing the stop button. This prevents your loads from getting
low voltage while still running during shutdown.