14

OPM-137/D

MAINTENANCE

GENERAL INFORMATION

The main components of the generator are: rotor and stator 
assembly, cooling fan, brushes, brush holder assembly, 
end brackets. Before performing any maintenance on the 
generator, isolate and/or disable the drive system so the 
unit can not be accidentally started while being repaired.

The trouble shooting chart lists various symptoms of 
poor generator operation with possible causes and the 
appropriate corrective action. You will need a volt-ohm 
meter or test light to check some of the causes. For some of 
the other causes you will need to check generator speed. 
To check generator speed, you can use a frequency meter, 
a tachometer, or a 120V-60Hz electric clock and a correctly 
operating wrist watch (run the electric clock and a correctly 
power and compare the clock’s second hand movement 
with that of the wrist watch. They should run at the same 
speed. If the clock runs faster, generator speed is too high, 
and vice versa).

CAUTION: EQUIPMENT DAMAGE

Most electrical equipment in North America operates 
satisfactory at frequencies between 58.5 and 62 Hz (cycles 
per second). Operating the generator at frequencies 
outside that range may cause damage to the generator 
and/or to electrical equipment driven by the generator.

PERIODICAL MAINTENANCE

Service/maintenance items include periodic external 
physical inspection for missing hardware or damage to 
mounting or drive system and checking the oil level in 
the gearcase. It is recommended that the generator be 
operated at least monthly under normal loads to familiarize 
operators with the procedures and controls as well as to dry 
out any accumulated condensation or other moisture in the 
generator electrical windings. The maintenance and service 
attention invested will ensure getting the peak performance 
that was designed to the unit.

Routine preventative maintenance minimizes costly repairs 
and generator down-time. Before each use, inspect the 
generator: gearcase oil level should be correct, cooling 
vents and screens should be clear, and generator mounting 
hardware should be tight. Clean and inspect the generator 
after storing it for long periods, and after using it in 
extremely dusty conditions or in severe weather, such as 
rain or blowing snow.

LUBRICATION

The generator bearings are factory lubricated and sealed, 
and require no further lubrication.

The generator input shaft should be cleaned and lubricated 
with a thin film of grease before installing the drive shaft 
and each time it is removed.

The drive shaft (tumbling bar) requires greasing. Keep the 
universal joints in the coupling shaft free from grease and 
dirt build-up.

NOTE: 
Do not over lubricate the universal joints.

Check the generator gearcase oil level before each use of 
the generator. Maintain the oil level at the oil level plug 
height. The generator is shipped with lubricant in the 
gearcase. Specifications for the gearcase lubricant are:

API Serice: GL-5
Grade: SAE 85W-90-140
Amount: 0.85 Pints

The following kind of oil are recommended for use in the 
generator gearcase: Mobile SAE 85W-90-140 API Service 
GL-5, Sunonco/DX XL80W90-140, Kendal Three Star 85W-
140, Amoco 85W140 or equivalent.

CAUTION: EQUIPMENT DAMAGE
Do not overfill generator gearcase. Overfilling causes 
overheating and oil seal failure.

Change oil at least once every twelve months or 150 hours 
of operation. Change it more often if you use the generator 
in bad weather. Use the following procedure to change 
generator gearcase oil:

1. Remove gearcase breather. Soak breather in cleaning 
  solvent, then allow to dry.

Page 7

60706-199

1005-00

MAINTENANCE

General  Information

The main components of the generator are: armature, field

coils,  cooling  fan,  brushes,  brush  holder  assembly,  end

brackets, and rectifier.  Before performing any maintenance

on the generator, isolate and/or disable the drive system so

the unit can not be accidentally started while being repaired.

The  troubleshooting  chart  lists  various  symptoms  of  poor

generator  operation  with  possible  causes  and  the  appro-

priate corrective action. You will need a volt-ohm meter or

test light to check some of the causes. For some of the

other causes you will need to check generator speed. To

check generator speed you can use a frequency meter, a

tachometer, or a 120V-60Hz electric clock and a correctly

operating wrist watch. (Run the electric clock on generator

power  and  compare  the  clock’s  second  hand  movement

with that of the wrist watch. They should run at the same

speed. If clock runs faster, generator speed is too high,

and vice versa.)

CAUTION: Equipment Damage

Most electrical equipment in North America operates

satisfactorily at frequencies between 58.5 and 62 Hz

(cycles per second.) Operating the generator at frequen-

cies outside that range may cause damage to the genera-

tor and/or to electrical equipment driven by the generator.

Periodical  Maintenance

Service/maintenance items include periodic external physi-

cal inspection for missing hardware or damage to mounting

or drive system and checking the oil level in the gear case.

It is recommended that the generator be operated at least

monthly under normal loads to familiarize operators with the

procedures and controls as well as to dry out any accumu-

lated condensation or other moisture in the generator elec-

trical  windings.    The  maintenance  and  service  attention

invested will insure getting the peak performance that was

designed into the unit.

Routine  preventive  maintenance  minimizes  costly  repairs

and generator down-time. Before each use, inspect the

generator: gear case oil level should be correct, cooling

vents and screens should be clear, and generator mount-

ing hardware should be tight. Clean and inspect the

generator after storing it for long periods, and after using

it in extremely dusty conditions or in severe weather, such

as  rain  or  blowing  snow.

Lubrication

The generator bearings are factory lubricated and sealed,

and require no further lubrication.

The generator input shaft should be cleaned and lubricated

with a thin film of grease before installing the drive shaft and

each time it is removed.

The drive shaft (tumbling bar) requires greasing. Keep the

universal joints in the coupling shaft free from grease and

dirt  buildup.

NOTE:

Do not over lubricate the universal joints.

Check the generator gear case oil level before each use of

the generator. Maintain the oil level at oil level plug height.

(See page 6 for oil level plug location.) The generator is

shipped with lubricant in the gear case. Specifications for

gear case lubricant are:

API Service: GL-5

Grade: SAE 85W-9O-140

Amount: 2 pints

The following kinds of oil are recommended for use in the

generator gear case: Mobil SAE 85W90-140 API Service GL-

5, Sunoco/DX XL80W90-140 Kendal Three Star 85W-140,

Amoco 85W140 or equivalent.

CAUTION: Equipment Damage

Do not overfill generator gear case. Overfilling causes

overheating and oil seal failure.

Change the oil at least once every six months. Change it

more often if you use the generator in bad weather. Use the

following procedure to change generator gear case oil:

1. Remove gear case breather. Soak breather in cleaning

solvent, then allow it to dry.

2. Remove oil level check plug.

3. Remove the oil drain plug, drain the oil into a clean oil

resistant container, 1 quart or larger. Check the oil for

metal. Fine metal dust in the oil does not indicate

trouble, but metal chips do. Dismantle the gear case and

look for damaged gears if you find metal chips in the oil.

4. Replace the oil drain plug. Refill the gear case through

the breather port with new oil of the recommended type.

Fill the case up to oil level check plug height. (It will take

about 2 pint.)

5. Replace the oil level check plug.

6. Replace the breather.

Cleaning and Inspection

Use a vacuum cleaner or dry low pressure compressed air

(regulated at 25-35 PSI) to clean the generator periodically.

WARNING

DO NOT CLEAN THE GENERATOR WHILE IT IS RUNNING.

Proceed  as  follows:

Breather Vent

Содержание 50PTOC4-03/1

Страница 1: ...uld ever need to contact us concerning this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER ________________________________...

Страница 2: ...THREE PHASE 277 480V THREE PHASE 36 MONTH LIMITED WARRANTY 20 LIMITED WARRANTY 20 SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and ma...

Страница 3: ...unit is properly grounded for your application WARNING FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep...

Страница 4: ...RPM AVR AS440 Input Shaft 1 3 8 6 spline Required Tractor PTO HP100 Gear Lube Volume 0 875 Pint Type SAE 80 90W 140 50PTOC4 17 1 Watts 50 000 Volts 120 240 Phase Three Amps 120 Input Speed 540 RPM Gen...

Страница 5: ...han required for full power operation The generator will work but produce only as much kW output as the tractor can supply HP for For example a 20 HP output tractor will deliver a maximum of approxima...

Страница 6: ...is noted it is always easiest to refuse the shipment and let WINCO take care of the freight claim If you sign for the unit the transfer of the ownership requires that you file the freight claim 2 Bef...

Страница 7: ...g on flat level ground All four deck pads must be in constant contact with the ground at all times This will reduce the vibration in both the generator and the tumbling bar C For safety the generator...

Страница 8: ...the following diagrams A properly rated and installed double throw manual power isolation transfer switch must be used with a standby generator The transfer switch isolates the load from the power li...

Страница 9: ...k 7 8 of an inch and inserted into one of the contacts in the plug kit You will then either need to solder them together using a good grade of resin core solder or they can be crimped with an appropri...

Страница 10: ...TS WITH EMERGENCY POWER IMPORTANT When making standby service hook up make sure load to be transferred to standby generator will not exceed generator rating Watthour Meter Watthour Meter To Power Line...

Страница 11: ...e load disconnect receptacle is the largest gray receptacle on the generator output panel To aid in determining how much load can be applied to the generator and how it should be distributed among the...

Страница 12: ...he gearcase marked OIL LEVEL To refill oil see LUBRICATION in the MAINTENANCE section in this manual NOTE Either too little or too much oil can harm the equipment 3 Make sure the drive shaft tumbling...

Страница 13: ...t should be checked each time you use the generator As a quick check you can plug in a trouble light and check for normal brightness 4 With engine and generator running smoothly switch on the electric...

Страница 14: ...east once every twelve months or 150 hours of operation Change it more often if you use the generator in bad weather Use the following procedure to change generator gearcase oil 1 Remove gearcase brea...

Страница 15: ...breather CLEANING INSPECTION Use a vacuum cleaner or dry low pressure compressed air regulated at 25 35 PSI to clean the generator periodically WARNING Do NOT clean the generator while it is running P...

Страница 16: ...R 7 Shorted or open rotor 8 Shorted or open stator 1 Reset circuit breakers replace if defective 2 Disconnect the load Check voltage at receptacle cord set Check motors appliances and load leads for s...

Страница 17: ...17 OPM 137 D WIRING DIAGRAM G1 G1 G2 G2 GND GND GND GND GND G2 G2 G2 G2 G1 G1 G1 N N N 120 240V SINGLE PHASE BACK VIEW...

Страница 18: ...18 OPM 137 D N GND GND GND GND GND N N G3 G3 G2 G3 G2 G2 G2 G2 G1 G1 G1 G1 G1 120 208V 120 240V THREE PHASE BACK VIEW...

Страница 19: ...19 OPM 137 D GND GND GND N N N N G3 G3 G2 G2 G1 G1 G1 G1 G1 277 480V THREE PHASE BACK VIEW...

Страница 20: ...you may have other rights which vary from state to state Note Some states do not allow limitation on the duration of implied warranty and some states do not allow the exclusion or limitation of incid...

Отзывы: