Winco 27PTOC4-03 Скачать руководство пользователя страница 8

8

OPM-136/D

ELECTRICAL CONNECTIONS

GROUNDING

Proper grounding of your generator is application 

dependent. Carefully evaluate your planned use of your 

generator to understand which grounding you require. 

If you are not sure what to do, contact a competent 

professional to assist you. The NFPA 70 250:34-35 are good 

technical references.  

STANDARD PORTABLE GENERATOR

Your WINCO portable generator ships with a bonded 

neutral. You can safely use this generator without external 

grounding as long as all loads are powered through the 

receptacle panel. 

VEHICLE-MOUNTED GENERATOR

Your WINCO portable generator ships with a bonded 

neutral. When mounted to a vehicle to safely distribute 

power it is necessary that the generator frame is bonded 

to the vehicle frame. The generator should only supply 

equipment that is cord and plug connected through 

receptacles mounted on the generator or the vehicle. 

PERMANENTLY INSTALLED GENERATORS

This WINCO portable generator ships with a bonded 

neutral and overcurrent protection. NFPA 70 refers to this 

as a “separately derived system.” When connecting it to a 

building a transfer switch specifically designed for GFCI and 

bonded neutral generators is required. 

CAUTION:

Only qualified electricians should install electrical wiring. 

Wiring must conform to all applicable national, state, 

and local codes. (Reference: National Fire Protection 

Association Manual No. 70, National Electrical Code.)

DANGER: PERSONAL INJURY:

A manual transfer switch must be installed to separate the 

generator and the commercial power lines. The switch 

must isolate the generator from the commercial power 

lines and the load when the generator is on standby, and 

must isolate the commercial power lines from the load and 

the generator when the generator is supplying power. See 

the following diagrams.

A properly rated and installed double throw manual power 

isolation transfer switch must be used with a standby 

generator. The transfer switch isolates the load from the 

power line and allows you to safely operate your loads 

without endangering the power line repair crew. See 

diagram on page 8. 

The load, connected to the normal terminals of the transfer 

switch, is energized by the normal power line when the 

switch is in the normal position. The generator, connected 

to the emergency terminals of the switch, furnishes power 

when the switch is in the emergency mode position.

There are two ways to install a manual transfer switch. The 

first shown on the left side of the diagram on page 8, is to 

install the switch between the watt-hour meter and the 

normal distribution panel. As with any system you must 

install an entrance rated breaker before the manual transfer 

switch. The manual transfer switch must in all cases be 

equal to or greater than the rating of the entrance rated 

breaker.

The second way to install the system is to purchase and 

install an emergency distribution panel and move the 

circuits you wish to back up to the new distribution panel. 

In this case the manual transfer switch only has to be 

sized to the amperage of the circuit breaker in the main 

distribution panel that is feeding it. See the right hand 

drawing of the diagram on page 8.

Before deciding which system to install, first determine 

which loads you can safely run on your PTO generator and 

the cost of buying a large manual transfer switch versus 

the cost of a smaller switch and the additional distribution 

panel.

PLUG KIT

The bag contains an instruction sheet, 2 plug bodies, four 

contacts, two handle and the hardware to assembly the 

disconnect plug. You will need to purchase the appropriate 

length of fine stranded copper wire for your application 

in order to complete the assembly of the disconnect plug. 

Your application and local code will determine the type 

of wire used. WINCO’s recommended wire size is given in 

each plug kit.

If you require different inserts or contacts for local code,

WINCO has a variety of different inserts and contacts 

available.

Contact the factory at 507-357-6831 for pricing. 

Single Phase 
120/240V

Three Phase
120/208V & 120/240V

Three Phase
277/480V

Содержание 27PTOC4-03

Страница 1: ...r need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCH...

Страница 2: ...THREE PHASE 36 MONTH LIMITED WARRANTY 20 LIMITED WARRANTY 20 SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the gen...

Страница 3: ...by NFPA are appropriate CAUTION NOISE HAZARD Excessive noise is not only tiring but continual exposure can lead to loss of hearing A Use hearing protection when working around this equipment for long...

Страница 4: ...s 120 240 Phase Three Amps 87 Input Speed 540 RPM Generator Speed 1800 RPM AVR AS540 Input Shaft 1 3 8 6 spline Required Tractor PTO HP 63 30PTOT4 17 Watts 31 600 Volts 120 240 Phase Three Amps 87 Inp...

Страница 5: ...equired for full power operation The generator will work but produce only as much kW output as the tractor can supply HP for For example a 20 HP output tractor will deliver a maximum of approximately...

Страница 6: ...is noted it is always easiest to refuse the shipment and let WINCO take care of the freight claim If you sign for the unit the transfer of the ownership requires that you file the freight claim 2 Bef...

Страница 7: ...generator B The design of the trailer must enable the trailer to remain stable during operation and to resist tipping caused by generator starting and reflected load torque C The trailer height and m...

Страница 8: ...r switch isolates the load from the power line and allows you to safely operate your loads without endangering the power line repair crew See diagram on page 8 The load connected to the normal termina...

Страница 9: ...imped with an appropriate compression crimper or both Approved Crimping tools are 1 Anderson Power Products 2 ETC Model HHS hydraulic crimper 3 ITT Blackburn NO 1640 4 T B Thomas Betts TBM5 To complet...

Страница 10: ...TS WITH EMERGENCY POWER IMPORTANT When making standby service hook up make sure load to be transferred to standby generator will not exceed generator rating Watthour Meter Watthour Meter To Power Line...

Страница 11: ...e load disconnect receptacle is the largest gray receptacle on the generator output panel To aid in determining how much load can be applied to the generator and how it should be distributed among the...

Страница 12: ...he drive shaft tumbling bar is assembled with its universal joint knuckles synchronized If the knuckles are not synchronized the bar will chatter when rotating which will cause the generator output vo...

Страница 13: ...t should be checked each time you use the generator As a quick check you can plug in a trouble light and check for normal brightness 4 With engine and generator running smoothly switch on the electric...

Страница 14: ...se Mobil SAE 85W90 140 API Service GL 5 Sunoco DX XL80W90 140 Kendal Three Star 85W 140 Amoco 85W140 or equivalent CAUTION Equipment Damage Do not overfill generator gear case Overfilling causes overh...

Страница 15: ...sure compressed air regulated at 25 35 PSI to clean the generator periodically WARNING Do NOT clean the generator while it is running Proceed as follows 1 Remove control box cover Vacuum or blow dust...

Страница 16: ...R 7 Shorted or open rotor 8 Shorted or open stator 1 Reset circuit breakers replace if defective 2 Disconnect the load Check voltage at receptacle cord set Check motors appliances and load leads for s...

Страница 17: ...17 OPM 136 D WIRING DIAGRAM 120 240V SINGLE PHASE BACK VIEW G1 G2 N N N G2 G2 GND GND GND GND GND G2 G2 G2 G2 G1 G1 G1 G1 G1...

Страница 18: ...18 OPM 136 D G1 G1 G1 G1 GND GND GND GND GND G1 G1 G2 G2 G3 G3 G2 N N N N G2 G2 G2 120 208V 120 240V THREE PHASE BACK VIEW...

Страница 19: ...19 OPM 136 D 277 480V THREE PHASE BACK VIEW GND GND GND N N N N N G3 G3 G2 G2 G1 G1 G1 G1 G1 G1...

Страница 20: ...you may have other rights which vary from state to state Note Some states do not allow limitation on the duration of implied warranty and some states do not allow the exclusion or limitation of incid...

Отзывы: