OPERATION

OUTPUT POWER AVAILABLE AND LOAD 

DETERMINATION

Before using the generator, read and understand the 

following information. 

Generator output current (amperage) is internally limited 

by three circuit breakers. If too much demand is placed on a 

generator output (if you try to drive too many motors with 

it, for example), one of the circuit breakers will trip, cutting 

off the output in order to protect the generator.

A 20 Amp push-to-reset circuit breaker protects the 120V 

duplex receptacle output circuit. 20 Amps is the total limit 

for both outputs of the duplex receptacle. The 480V is 

equipped with the Anderson receptacle only.

A 50 Amp toggle circuit breaker protects the 240V 

receptacle output circuit. The 480V is equipped with the 

Anderson receptacle only.

A large two pole (three pole for three phase) switch type 

main circuit breaker protects the generator windings and 

output circuits, including the load disconnect receptacle 

outputs. The load disconnect receptacle is the largest gray 

receptacle on the generator output panel.

To aid in determining how much load can be applied to 

the generator, and how it should be distributed among the 

generator output receptacles, the following formulas may 

be useful. Get load voltages, current, and wattage from the 

nameplates on the equipment in the load.

Load current (in Amps) x Load voltage = Load wattage

Amps x Volts = Watts

Watt/1000 = kW

Load wattage / Load voltage = Load current (in Amps)

Example: 250W, 120V floodlight load: 250W / 120V = 2 

Amps

 

NOTE: 

Electric motors require more current to start than to run. 

Commonly, the current rating given on a motor nameplate 

is the full load (running) current required by the motor, 

not its starting current, which is a lot higher. Motor starting 

current requirements vary greatly, by motor size and type. 

Repulsion-induction type motors are the easiest to start, 

typically using 1 1/2 to 2 1/2 times as much current to start 

as to run. Capacitor type motors usually require 2 to 4 times 

as much current to start as to run. Split-phase type motors 

are the hardest to start, normally using 5 to 7 times as much 

current to start as to run.

Содержание 27PTOC4-03

Страница 1: ...r need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCH...

Страница 2: ...THREE PHASE 36 MONTH LIMITED WARRANTY 20 LIMITED WARRANTY 20 SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the gen...

Страница 3: ...by NFPA are appropriate CAUTION NOISE HAZARD Excessive noise is not only tiring but continual exposure can lead to loss of hearing A Use hearing protection when working around this equipment for long...

Страница 4: ...s 120 240 Phase Three Amps 87 Input Speed 540 RPM Generator Speed 1800 RPM AVR AS540 Input Shaft 1 3 8 6 spline Required Tractor PTO HP 63 30PTOT4 17 Watts 31 600 Volts 120 240 Phase Three Amps 87 Inp...

Страница 5: ...equired for full power operation The generator will work but produce only as much kW output as the tractor can supply HP for For example a 20 HP output tractor will deliver a maximum of approximately...

Страница 6: ...is noted it is always easiest to refuse the shipment and let WINCO take care of the freight claim If you sign for the unit the transfer of the ownership requires that you file the freight claim 2 Bef...

Страница 7: ...generator B The design of the trailer must enable the trailer to remain stable during operation and to resist tipping caused by generator starting and reflected load torque C The trailer height and m...

Страница 8: ...r switch isolates the load from the power line and allows you to safely operate your loads without endangering the power line repair crew See diagram on page 8 The load connected to the normal termina...

Страница 9: ...imped with an appropriate compression crimper or both Approved Crimping tools are 1 Anderson Power Products 2 ETC Model HHS hydraulic crimper 3 ITT Blackburn NO 1640 4 T B Thomas Betts TBM5 To complet...

Страница 10: ...TS WITH EMERGENCY POWER IMPORTANT When making standby service hook up make sure load to be transferred to standby generator will not exceed generator rating Watthour Meter Watthour Meter To Power Line...

Страница 11: ...e load disconnect receptacle is the largest gray receptacle on the generator output panel To aid in determining how much load can be applied to the generator and how it should be distributed among the...

Страница 12: ...he drive shaft tumbling bar is assembled with its universal joint knuckles synchronized If the knuckles are not synchronized the bar will chatter when rotating which will cause the generator output vo...

Страница 13: ...t should be checked each time you use the generator As a quick check you can plug in a trouble light and check for normal brightness 4 With engine and generator running smoothly switch on the electric...

Страница 14: ...se Mobil SAE 85W90 140 API Service GL 5 Sunoco DX XL80W90 140 Kendal Three Star 85W 140 Amoco 85W140 or equivalent CAUTION Equipment Damage Do not overfill generator gear case Overfilling causes overh...

Страница 15: ...sure compressed air regulated at 25 35 PSI to clean the generator periodically WARNING Do NOT clean the generator while it is running Proceed as follows 1 Remove control box cover Vacuum or blow dust...

Страница 16: ...R 7 Shorted or open rotor 8 Shorted or open stator 1 Reset circuit breakers replace if defective 2 Disconnect the load Check voltage at receptacle cord set Check motors appliances and load leads for s...

Страница 17: ...17 OPM 136 D WIRING DIAGRAM 120 240V SINGLE PHASE BACK VIEW G1 G2 N N N G2 G2 GND GND GND GND GND G2 G2 G2 G2 G1 G1 G1 G1 G1...

Страница 18: ...18 OPM 136 D G1 G1 G1 G1 GND GND GND GND GND G1 G1 G2 G2 G3 G3 G2 N N N N G2 G2 G2 120 208V 120 240V THREE PHASE BACK VIEW...

Страница 19: ...19 OPM 136 D 277 480V THREE PHASE BACK VIEW GND GND GND N N N N N G3 G3 G2 G2 G1 G1 G1 G1 G1 G1...

Страница 20: ...you may have other rights which vary from state to state Note Some states do not allow limitation on the duration of implied warranty and some states do not allow the exclusion or limitation of incid...

Отзывы: