Page

 

11

 

Power wires can enter through the side of the unit or through 
the auxiliary entrance, located in the bottom of the unit. 
When bringing wiring through the bottom of the furnace, 
cable connectors must be installed to hold wiring in place and 
to relieve any strain on the wiring.  
 
These connectors will also serve as a seal between the furnace 
and the floor. Thus, additional sealing is not required. 
The use of a five-conductor cable from the thermostat to the 
furnace is recommended for typical heating or heating / 
cooling installations with a three-conductor cable from the 
furnace to the condenser. 
 
A seven-conductor cable from the thermostat to the furnace is 
recommended for a typical heat pump installation with a five-
conductor cable from the furnace to the condenser. 
 
The thermostat wire colors and the typical heating / cooling 
connections are listed in Table 10.  
 
The thermostat wire colors and the typical heat pump heating / 
cooling connections are listed in Table 11. 

 

NOTE: 

There is a 3 Amp slow blow bar fuse located on the 

right side of the control box that protects the 24 VAC circuit. 
Replace this fuse only with the equivalent 3 Amp fuse.  

 

NOTE:

 If the thermostat cable is on the left side of the 

furnace place the grommet in the 3/8” hole on the left side of 
the furnace casing. Run the thermostat wire cable through the 
control box exiting the right side of the control box next to the 
low voltage pigtails. Follow the steps for “

Typical Heating / 

Cooling Thermostat Wiring Connections”

 or “

Typical 

Heat Pump - Heating / Cooling Thermostat Wiring 
Connections”

 

 
Thermostat Installation 

The adjustable heat anticipator in the thermostat is pre-set at 
0.4 Amps. This setting should be checked at the time of 
installation. 
 
In some cases the thermostat may be a “self-setting" type in 
which case no Amp setting will be found on the thermostat, 
eliminating the need for any field adjustment. 
 
Thermostat should be located on an inside wall in an open area 
to more closely regulate average room air, preferably, where 
there is air movement back to furnace. Locating height of 
thermostat is important. Thermostat should be located 
preferably in a hall way upstream from the furnace return 
airflow, not within 3 feet of from any windows and 52 to 66 
inches above the floor. 

 

DO NOT

 place the thermostat within three feet of any the 

furnace supply air registers 

DO NOT

 place the thermostat within three feet of any the air 

conditioner supply air registers 

 

Maintenance, operating and/or programming instructions are 
in the envelope accompanying the thermostat. Give the 
envelope to the homeowner. 

 

  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Separate Heating and Cooling System; Same Thermostat 

If the furnace and the cooling unit have separate transformers 
be sure to use a thermostat with isolated heating and cooling 
contacts to prevent interconnection of Class II 24 Volt 
Systems. Cycle furnace and the air conditioner separately to 
make sure it will operate correctly. 

 

Most new thermostats have a separate heating and cooling 
contact for use with homes that have a furnace and air 
conditioner that are completely separate and each have a 24 
VAC transformer for system control. These thermostats have a 
“RC” terminal for cooling and a “RH” terminal for heating. 
Use these terminals to connect cooling unit (RC and Yellow) 
and the furnace (RH and White) for separate operation. Refer 
to Figure 21 and 22. 
 
If your thermostat does not have the “RC” and “RH” terminals 
it is recommended that you purchase a new thermostat. 
 

Separate Heating and Cooling Thermostats 

If the heating/cooling system in your house is a central heating 
and cooling system but the furnace and the cooling unit are 
controlled by separate thermostats then the use of a thermostat 
interlock switch is required in order to prevent the furnace and 
the air conditioner from operating at the same time. 

Do not locate thermostat within three feet of any of the 
following items: 

1.

 

Furnace supply air registers 

2.

 

Cooling unit supply air registers 

3.

 

Lights or heat lamps 

4.

 

Aquariums 

5.

 

Televisions, stereo, amplifiers, surround sound 
systems 

6.

 

Stoves or any cooking appliance 

7.

 

Refrigerator 

8.

 

Washer and/or dryer 

9.

 

Hot water tank 

10.

 

Sink or near any hot water 

11.

 

Within 15 feet of any electric space heater 

12. Within 2 feet of any sunlight 

Содержание WEFC**48

Страница 1: ...l Cabinet Door Bracket Location 7 28 Wiring Diagram 20 kW w X 13 Blower Motor 20 13 Control Box Component Locations 9 29 Wiring Diagram 5 kW w PSC Blower Motor 21 14 Control Box Cover and Circuit Brea...

Страница 2: ...Blower Motor Heat Strip kW Blower Motor HP W Winchester E Electric Heat F Furnace 42 1 3 HP 48 1 2 HP 60 3 4 HP 10 10 kW 12 12 kW 15 15 kW 20 20 kW C PSC Blower Motor X X 13 Blower Motor Table 2 Furn...

Страница 3: ...replacing the air filters Observe all precautions in the manuals and on the attached labels when working on this appliance 11 These instructions cover minimum requirements and conform to existing nati...

Страница 4: ...opening FOR A C and HP Furnaces 3 4 HP Blower Minimum 390 in free area opening Use Return Grille or A C Coil Cabinet or any return grille with a minimum 390 in free area opening Top Return Only Recom...

Страница 5: ...90 DCU0 03 11 90 DCU0 03 12 90 DCU0 03 Table 5 Duct Connectors Figure 6 Duct Connector Depths Installing the Duct Connector 1 Attach the four seal strip foam tape gaskets provided with the duct conne...

Страница 6: ...TALLATION Installing the Furnace with a Return Air Grille Frame Assembly Alcove Installation This kit is approved for use in an alcove heating only installation without an air conditioning coil The re...

Страница 7: ...emove the coil cabinet from the box and assemble per the instructions 6 Lay the coil cabinet on its back and place the coil cabinet flanges against the furnace top cover 7 Place coil cabinet door brac...

Страница 8: ...n on the wire 11 If you are using a dual circuit for a 15kW 17kW or 20kW model you will need to insert both green wires into the ground lug and tighten the set screw 12 Tighten the screws on the cable...

Страница 9: ...99 10 12 0 10 4 99 12 0 4 99 10 10 BTU 15 876 26 512 33 686 38 612 33 686 15 876 38 612 15 876 33 686 33 686 kW 4 65 7 77 9 78 11 32 9 78 4 65 11 32 4 65 9 78 9 78 BTU 14 736 23 339 30 222 36 483 30...

Страница 10: ...ow Voltage Wire Gauge and Max Lengths Figure 17 Control Box In coming Power Low Voltage Wiring Blower Wiring and Low Voltage Fuse Locations For personal safety be sure to turn the electrical power OFF...

Страница 11: ...air preferably where there is air movement back to furnace Locating height of thermostat is important Thermostat should be located preferably in a hall way upstream from the furnace return airflow not...

Страница 12: ...ections RED 24 VAC R Red R N A WHITE Heat 1st Stage Heat W White W or W1 N A GREEN Indoor Fan G Green G N A YELLOW Cooling Stage 1 Y Yellow Y or Y1 Y or Y1 BROWN 24 VAC Common BRN Brown C C Table 10 R...

Страница 13: ...met in the right side of the casing and place the thermostat wire cable on the right side of the control box next to the low voltage pigtails 5 Connect the Red 24 VAC supply wire from the thermostat t...

Страница 14: ...the main service House Circuit Breaker panel Figure 23 X 13 Motor Terminals Replacing the Blower Motor 1 Turn off all electrical supply circuits to the furnace at the main service panel 2 Remove furn...

Страница 15: ...aks found 7 Set the blower selector switch to the AUTO position 8 Set the thermostat above the room temperature to check for proper operation of the electric heaters 9 Set the thermostat to the desire...

Страница 16: ...WINCHESTER BY MORTEX PRODUCTS INC FORT WORTH TX 76106 Page 16 Table 13 X 13 Motor Factory Speed Tap Settings...

Страница 17: ...25 5 kW Electric Heater Wiring Diagram with a Standard Digital Heating Cooling Heat Pump Single or Two Stage Programmable Thermostat X 13 blower motor NOTE IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH T...

Страница 18: ...W Electric Heater Wiring Diagram with a Standard Digital Heating Cooling Heat Pump Single or Two Stage Programmable Thermostat X 13 blower motor NOTE IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNI...

Страница 19: ...Electric Heater Wiring Diagram with a Standard Digital Heating Cooling Heat Pump Single or Two stage Programmable Thermostat X 13 blower motor NOTE IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT...

Страница 20: ...ctric Heater Wiring Diagram with a Standard Digital Heating Cooling Heat Pump Single or Two Stage Programmable Thermostat X 13 blower motor NOTE IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUS...

Страница 21: ...Electric Heater Wiring Diagram with a Standard Digital Heating Cooling Heat Pump Single Stage Programmable Thermostat PSC blower motor NOTE IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE...

Страница 22: ...12kW Electric Heater Wiring Diagram with a Standard Digital Heating Cooling Heat Pump Single Stage Programmable Thermostat PSC blower motor NOTE IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUS...

Страница 23: ...17kW Electric Heater Wiring Diagram with a Standard Digital Heating Cooling Heat Pump Single Stage Programmable Thermostat PSC blower motor NOTE IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUS...

Страница 24: ...d Digital Heating Cooling Heat Pump Single Stage Programmable Thermostat PSC blower motor NOTE IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH TYPE 105 C...

Отзывы: