8. Fault Findings –

Causes and Remedies

8.1 Pump is switched on, but

fails to run:

– Check power supply fuses.
– Check voltage at pump terminals

(refer to name plate data).

– Check capacitor size (refer to name

plate data!).

– Rotor shaft has jammed, e.g. by

incrustations.
Remedy: Remove central access

plug, check free movement of shaft

or free respectively at the slotted

shaft end by means of a screw-

driver.

Observe safety procedures

as for 6.1!
At high water temperatures

and system pressures, close

isolating valves at both pump

ports. First, allow pump to

cool down.

8.2 Noise

– Cavitation due to insufficient inlet

pressure.
Remedy: Increase system pressure

within permissible limits.

If the fault cannot be located or rec-
tified, please contact your nearest
Wilo representative.

9. Spare Parts

State all name plate data when order-

ing spare parts.

Technical modifications reserved.

Содержание Star Z 20/1

Страница 1: ...au und Betriebsanleitung GB Installation and Maintenance Instructions F Notice de mise en service et de montage I Istruzioni di montaggio uso e manutenzione E Instrucciones de instalaci n y funcionami...

Страница 2: ...Fig 1 Fig 2 3 400 V Fig 4 Fig 3...

Страница 3: ...N L N L N L N L 1 230 V 50 Hz N L Fig 5 Fig 5 Fig 5 b Fig 5 a Fig 5 c...

Страница 4: ......

Страница 5: ...2 ZD 25 6 R 1 DN 28 G R 1 The minimum inlet pressure at the pump suction port must be maintained to avoid cavitation noise 2 Safety These instructions contain basic refe rence to safety aspects which...

Страница 6: ...on Work It is the Operator s responsibility to ensure that inspections and installa tion work are carried out by authorized and qualified personnel only having themselves made fully conversant with th...

Страница 7: ...heads can be selected of different capacities Double pumps are suita ble of adapting a pipe system to suit individual load characteristics 4 2 Scope of Supply Pump complete Installation and Operating...

Страница 8: ...2 Pos 2 ATTENTION ATTENTION ATTENTION 5 2 Electrical wiring Electrical work to be car ried out by qualified and licensed electricians in strict conformity to ruling national conditions and local regul...

Страница 9: ...alding Protect electrical parts from leaking water switch on pump again after 15 30 secs close access plug again open isolating valve again It is possible that the pump shaft jams with the access plug...

Страница 10: ...e respectively at the slotted shaft end by means of a screw driver Observe safety procedures as for 6 1 At high water temperatures and system pressures close isolating valves at both pump ports First...

Страница 11: ...rective Directive basse tension und entsprechender nationaler Gesetzgebung and with the relevant national legislation et aux l gislations nationales les transposant Angewendete harmonisierte Normen in...

Страница 12: ...nvendte harmoniserte standarder s rlig 1 FIN CE standardinmukaisuusseloste Ilmoitamme t ten ett t m laite vastaa seuraavia asiaankuuluvia m r yksi S hk magneettinen soveltuvuus 2004 108 EG Matalaj nni...

Страница 13: ...0 591 5 7 81 B58 51 85 8 1 451 91 58 B58 5 85 B58 5 1 8 5 89 D 5 2 B58 7E 9 0 594 1 D1 3 9 B58 B58 7 8 5 53 9 58 B58 8A 1 8 1 B 8 D 1 5 1 8 51 A 58 5 9 58 B58 8 B58 9 101 8 0 A 1 E 5 2 B58 8 31 8 B58...

Страница 14: ...58 86 8 43 2 7 D 8 6 7 4 80 361 7 D 80 8 43 2 7 D 8 6 7 I I I I I I I I I I 4 7 7 3 7 358 86 E153 2 2 3 2 7 7 273 2 8 0 55 7 G B 71 H 7 7 3 7 708 71 H 4 9 7 H B 350 1 7 H 7 3 7 26 H 7 9 4 387 H 273 2...

Отзывы: