Installation and operating instructions Wilo-Star-Z 15 TT
23
Engl
is
h
Settings
5.2 Electrical connection
The pump is fitted with a cable and shock-proof power plug so
that it is ready to connect. Proceed as follows if the connecting
cable has to be changed:
1.
Install a permanent connecting cable with an o.d. of 5-8 mm,
complete with plug device or all-pole switch (with a contact
opening width of at least 3 mm).
2.
Open the terminal box.
3.
Guide the connecting cable through the cable connection and
strip approximately 5 mm.
4.
Secure the cores with the cable clips.
L phase, N neutral conductor, earth
5.
Firmly tighten the cable connection.
6.
Close the terminal box.
7.
Set parameters
>
Page 23.
5.3 Filling and ventilation
1.
Fill the system.
2.
The pump vents automatically. The pump will not be damaged
if it runs dry briefly.
6 Settings
6.1 To set the current time
Danger:
Only a qualified electrician may work on the elec-
trical connection. Before connecting, make sure that the con-
necting cable is dead.
Note:
So that the pump functions can be fully used, the
pump needs a permanent power supply. Do not connect the
pump to a boiler control system.
1.
2.
Select clock (flashes).
+
3.
Set the hours.
+
4.
Set the minutes.
+
5.
Select the basic display.
+
5 sec.
5 sec.
12:
:45
Содержание star z 15 tt
Страница 2: ......
Страница 15: ......
Страница 27: ......
Страница 51: ......
Страница 87: ......
Страница 88: ...88 WILO AG 02 2008 1 off on Thermal disinfection 94 90 92 95 99 92 90 96 96 97 97 97 92 95 89 91 93 93 96...
Страница 89: ...Wilo Star Z 15 TT 89 2 X Y _ Y Y Y _ Y X _ _ _ _ _ _ _ _ _ W551 DVGW VDE 0370 1 _ IEC VDE X _ Y _ _ _ _ _ _ _ Y...
Страница 93: ...Wilo Star Z 15 TT 93 Y 5 5 1 J _ _ _ _ Y J J 3 _ 3 _ _ _ J _ _ 11 30 65 8C _...
Страница 94: ...94 WILO AG 02 2008 1 2 _ _ _ A Y 0 3 _ 4 Y 5 _ 6 1 Y 7 _ _ _ Y Y Y Y X Y Y A B _ _ _ _ _ 1...
Страница 98: ...98 WILO AG 02 2008 7 _ Y 94 8 _ _ 7 _ _ _ _ _ _ _ _ Y Y...