6
WILO_IOM_ICL_1219
3.3
3.4
a.
b.
c.
i.
ii.
On-site trip unit required
Hydraulic corrections necessary depending on
liquid’s density and viscosity. Only approved
additives with corrosion inhibitors may be used.
Observe manufacturer’s instructions.
Contact WILO before using any liquids other
than above-listed liquids, different mixture
ratios and higher temperatures.
Materials
Scope of Delivery
Pump complete
Installation and operating
instructions (not displayed)
the NEMA standard.
Description
Information
Option
Mains voltage
460V
Degree of motor protection
TEFC
Protection against overheating
Integrated protection PTC /
PTOa
•
Special motor design
Closed coupled motor shaft
Max. working pressure
175 psi [12 bar] (CI)
363 psi [25 bar] (DI)
Max. permissible liquid tem-
perature range
-4 °F to 284 °F [-20 °C to +140
°C]
Max. ambient temperature
104 °F [40 °C]
Approved liquids
Heating water
Chilled/Cold water
Water/glycol mixtures b
Heat transfer oil (Viton seal only) •
Other liquids on request c
•
Legend: •Special design or accessories (at added cost on request)
Caution: Damage due to incorrect seal material
The pump must use a mechanical seal constructed with
Viton elastomer if pump is moving oil. EPDM will shrivel
in the presence of oil and will cause the mechanical seal
to fail.
Note:
For additional data, see type plate, product
information sheet or Wilo catalog.
Pump housing and lantern
Cast Iron – Class 30 ASTM A48
Ductile Iron - ASTM A536
Impeller
Bronze - CC480K-GS
Pump shaft
Stainless Steel - AISI 420
4.
4.1
4.2
4.2.1
4.2.2
4.2.3
Functionality
Application
The purpose of the pump is to
pump the liquids specified in the
technical data for the building services industry
and industrial plants. Pumping different liquids
and exceed-ing the limit values specified in the
technical data may destroy the pump.
Functions
Design:
The pump is a single-stage circulating pump
with an inline design. It is driven by an electric
motor according to the NEMA standard.
Performance Regulation:
External pressure sensors and an external
control unit can be connected to the suction
side and the discharge side by means of a
pressure gauge tapping. The motor speed
can be controlled using an external frequency
converter.
Directions of Flow:
The arrow on the volute indicates the direction
of flow.
5.
5.1
5.1.1
5.1.2
5.1.3
Transport and Shipping
Shipping
Shipping
The pump is delivered packaged in cardboard or
lashed down on a pallet and is protected against
dust and mois- ture.
Transport Inspection
Upon receipt, unpack and check pump and all
accessories. Report transit damage immediately.
Storage
Until the pump is installed, the pump must be
stored in a dry, frost-free place where it is also
protected against mechanical damage.