English
Installation and operating instructions Wilo SC-Fire Electric
29
5 Product information
5.1 Type key
Example:
W
W = Wilo
CTRL
Control
SC
Smart Control = control unit
F
F = fire fighting purposes
1x
Number of pumps
7.7 A
Maximum rated motor current [A]
T4
T = 3 phases; 4 = 400 V
DOL
SD
Direct online (direct starting)
Star delta (star-delta starting)
FM
BM
Frame mounted (on a base frame)
Base mounted (free-standing cabinet)
ND3
ND4
New Design switchbox 400 x 1300 x 250 mm
New Design switchbox 400 x 950 x 250 mm
E
Switchgear for electric pump
5.2
Technical data (standard version)
Mains supply voltage [V]:
3~400 V (L1, L2, L3, PE)
Frequency [Hz]:
50/60 Hz
Control voltage [V]:
230 VAC; 24 VDC
Max. current consumption [A]:
See rating plate
Protection class:
IP 54
Max. fuse protection on mains side [A]:
See wiring diagram
Ambient temperature [°C]:
0 to +40°C
Electrical safety:
Degree of contamination II
Alarm/signalling contact
250 VAC, 1 A
5.3 Scope of delivery
• Switchgear
• Wiring diagram
• Installation and operating instructions
• Test report acc. to EN 60204-1
5.4 Accessories
6 Description and function
6.1 Description of the product (Fig. 1)
6.1.1 Function description
The switchgear is used to control an individual
electric pump in sprinkler systems, in accordance
with EN 12845. The pump can be switched on and
off by the control depending on the pressure. The
system’s operating statuses, such as standby,
pump operation, fault etc., are displayed visually
by LEDs on the door and operating parameters
such as current or voltage values are shown on the
display. The system is operated using the rotary
knob and the buttons in the door.
Potential-free contacts are available for forward-
ing run or fault signals messages to the building
management system.
6.1.2 Set-up of the switchgear (Fig. 1)
The set-up of the switchgear depends on the
capacity of the pump to be connected. It consists
of the following main components:
• Main switch: Switches the switchgear on/off
(Fig. 1, item 2)
• Human-machine interface (HMI): signal lamps or
display for indicating the operating status (e.g.
standby, fault, and rated pump current), rotary
knob and buttons for menu selection, parameter
input and operation (Fig. 1, item 1)
• Base board: printed circuit board with microcon-
troller (Fig. 1, item 6)
• Measurement board: converting current and volt-
age values (Fig. 1, item 7)
• Transformer: 3-phase pump current measure-
ment (Fig. 1, item 4)
• Fuse protection for drives: fusing for the pump
motor by means of fusible cut-outs (Fig. 1, item 3)
• Contactors/contactor combinations: contactors
for switching on the pumps (Fig. 1, item 5)