Installation and operating instructions • Wilo-Control MS-L • Ed.02/2022-05

27

7.1.2

Buttons

Function

Buttons

Description

MS-L1...

MS-L2...

Manual mode

Pressing the button switches the respective pump on independent of the level
control. The pump operates as long as the button is held down. This function is in-
tended for test mode.

Automatic mode

Press the button to switch on automatic mode. The pumps are switched on and
off independent of the level control.

Stop

Press the button to switch off automatic mode. The pumps are not controlled de-
pendent on the level. The switchgear is in standby mode.

Buzzer off/reset

Press the button to switch the integrated buzzer off and deactivate the collective
fault signal (SSM).

Press the button for more than 1 s to acknowledge a fault. This releases the con-
trol again.

7.1.3

LEDs

Control MS-L2...

: Pump-dependent LEDs are displayed in two rows using the symbols:

Top row: current status of pump 1

Bottom row: current status of pump 2

Display

LED

LED colour

Description

MS-L1...

MS-L2...

Mains connection

Green

LED 

lights up

: Mains voltage and control voltage are on.

Automatic mode

Green

LED 

flashes

: Switchgear switched on − standby mode

LED 

lights up

: Automatic mode switched on

LED 

off

: Pump deactivated (only Control MS-L2...)

Pump operation

Green

LED 

flashes

: Pump running during the set follow-up time.

LED 

lights up

: Pump is running.

Service interval/operating
parameters

Yellow

LED 

lights up

: Service interval has elapsed.

LED 

flashes

: Operating parameters exceeded.

High water alarm

Red

LED 

lights up

: High water alarm activated

“Motor current monitoring”
fault

Red

LED 

flashes

: Switchgear is operated without any load.

LED 

lights up

: Set rated current exceeded

“Thermal motor monitoring”
fault

Red

LED 

lights up

: Temperature sensor in motor triggered

7.1.4

Key lock

Activate the key lock to prevent inadvertent or unauthorised activation of buttons:

Description

Buttons

MS-L1...

MS-L2...

Switch the key lock on and off by pressing the following but-
tons at the same time (for approx. 1 s): manual mode (pump 1),
stop and automatic mode.

All LEDs light up for approx. 2 s by way of confirmation.

Observe the following points:

If a button is pressed when the key lock is active, all LEDs light up for 2 sec.

The buzzer can be switched off and the collective fault signal (SSM) deactivated when
the key lock is active.

Acknowledgement of error messages is 

not

 possible!

Содержание Control MS-L

Страница 1: ...Pioneering for You Wilo Control MS L 2552612 Ed 02 2022 05 en Installation and operating instructions...

Страница 2: ...Control MS L https qr wilo com 1393...

Страница 3: ...M L N PE N WSK 1 230V 50 60Hz 1 L N ON OFF ON U V W L N min 12 VDC 10 mA max 250 VAC 1 A 120 60 0 Seconds ON 100 K DIP 1 2 3 4 5 6 7 8 PE 1 2 3 7 8 9 4 5 6 GL WSK HW T1 1 3 5 13 A1 2 4 6 14 A2 T2 T3...

Страница 4: ...3 M PE WSK 1 230V 50 60Hz 1 L N ON OFF ON U V W L N 1 2 3 4 1 2 3 4 120 60 0 Seconds ON 100 K DIP 1 2 3 4 5 6 7 8 PE 1 2 3 7 8 9 4 5 6 GL WSK HW T1 1 3 5 13 A1 2 4 6 14 A2 T2 T3 L1 L2 L3 NO 5 6 8 2 3...

Страница 5: ...2 U bk bn V W N L L1 L2 L3 PE 3 400V 50 60Hz L1 L L2 N PE 1 230V 50 60Hz 30 15 0 Seconds ON 100 K DIP 1 2 3 4 5 6 7 PE 1 2 5 7 8 9 6 WSK T1 1 3 5 13 A1 2 4 6 14 A2 T2 T3 L1 L2 L3 NO 5 6 8 ON 1 2 3 10...

Страница 6: ...14 13 12 11 9 8 7 6 5 4 3 2 1 HW T1 1 3 5 13 A1 2 4 6 14 A2 T2 T3 L1 L2 L3 NO L1 L2 L3 N WSK M 3 WSK M 1 T1 1 3 5 13 A1 2 4 6 14 A2 T2 T3 L1 L2 L3 NO ON DIP 1 2 3 4 5 6 7 PE L1 L2 L3 PE 3 400V 50 60H...

Страница 7: ...GL WSK P2 WSK P1 SL 10 16 15 14 13 12 11 9 8 7 6 5 4 3 2 1 HW T1 1 3 5 13 A1 2 4 6 14 A2 T2 T3 L1 L2 L3 NO L1 L2 L3 N WSK M 3 WSK M 1 T1 1 3 5 13 A1 2 4 6 14 A2 T2 T3 L1 L2 L3 NO ON DIP 1 2 3 4 5 6 7...

Страница 8: ...econds ON 100 K DIP 1 2 3 4 5 6 7 SSM Alarm WSK P2 Sensor ln WSK P1 16 15 14 13 12 11 10 9 4 3 2 1 T1 1 3 5 13 A1 2 4 6 14 A2 T2 T3 L1 L2 L3 NO WSK M 3 WSK M 1 U V W N L N L T1 1 3 5 13 A1 2 4 6 14 A2...

Страница 9: ...tion 17 6 1 Personnel qualifications 17 6 2 Installation types 17 6 3 Operator responsibilities 17 6 4 Installation 17 6 5 Electrical connection 18 6 6 Functions 25 7 Operation 26 7 1 Operating elemen...

Страница 10: ...nal and are intended as an example representation of the device 1 5 Exclusion from warranty and liabil ity Wilo shall specifically not assume any warranty or liability in the following cases Inadequat...

Страница 11: ...s can lead to serious injury Caution Failure to follow instructions can lead to property damage and possible total loss Notice Useful information on handling the product Markups Prerequisite 1 Work st...

Страница 12: ...efective connection cable immediately 2 4 Monitoring devices Circuit breaker The size and switching characteristics of the circuit breakers must conform to the rated current of the connected consumer...

Страница 13: ...nnel on how the system operates Eliminate risk from electrical current To ensure safe working practice define personnel responsibilit ies Children and persons younger than 16 years or with reduced phy...

Страница 14: ...ch pump The high water level is detected by a separate float switch Control MS L LS The level is detected continuously via a rod float sensor 4 20 mA signal The high water level is detected by a separ...

Страница 15: ...VDC 10 mA Maximum 250 VAC 1 A 4 5 Functions The switchgear is equipped with the following functions All functions are switched off at the factory The functions must be switched on as required Inputs o...

Страница 16: ...nd sewage Signal lamp Flash light Horn 5 Transportation and storage 5 1 Delivery After receiving the shipment check it immediately for defects damage completeness The transport company or the manufact...

Страница 17: ...ative humidity 40 50 Max relative humidity 50 non condensing 6 4 1 Basic advice on fixing the switchgear in place Various structures can be used for installation concrete wall mounting rail etc For th...

Страница 18: ...ctrical connection DANGER Risk of fatal injury due to electrical current Improper conduct when carrying out electrical work can lead to death due to electric shock Electrical work must be carried out...

Страница 19: ...5 Potentiometer for follow up time 6 Slot 9 V rechargeable battery 7 Terminal strip Mains connection 8 DIP switch 1 9 DIP switch 2 10 DIP switch 3 Setting the switching points only MS L LS 6 5 2 DIP...

Страница 20: ...L2 Fig 4 Mains connection 1 230 V with main switch 1 Main switch 4 Terminal strip Earth 7 Terminal strip Mains connection 8 DIP switch 1 9 DIP switch 2 NOTICE Install two cable bridges on the mains t...

Страница 21: ...elected mains voltage Control MS L1 DIP switch 1 DIP 8 OFF Control MS L2 DIP switch 2 DIP 1 OFF Control MS L O Mains connection 3 400 V without main switch L1 1 2 3 4 L2 L3 PE 3 400 V 50 60 Hz N 7 4 P...

Страница 22: ...2 T1 V 4 T2 W 6 T3 PE earth terminal bn 2 T1 bk 4 T2 gy 6 T3 PE earth terminal 6 5 5 Adjust motor current monitoring The electronic motor current monitoring monitors the rated current of the connecte...

Страница 23: ...ge which is applied destroys the component GL WSK P2 WSK P1 SL 10 9 8 7 6 5 4 3 2 1 HW HW GL WSK 6 5 4 3 2 1 3 3 Control MS L1 MS L O WSK 6 5 2 1 3 Control MS L1 LS Control MS L2 MS L O WSK P2 Sensor...

Страница 24: ...external power supply before any work Electrical work must be carried out by a qualified electrician Observe local regulations NOTICE Operational principle of the collective fault signal SSM The rela...

Страница 25: ...ers for the respective lift ing unit 6 6 1 Internal buzzer ON DIP 1 2 3 4 5 6 7 8 Fig 16 DIP switch 1 internal buzzer The internal buzzer can also issue audible warning messages in addition to the vis...

Страница 26: ...continuously at the poten tiometer 120 60 0 100 K 5 Fig 20 Adjusting the follow up time Setting ranges Control MS L 0 120 s Control MS L O 0 120 s Control MS L LS 0 30 s 6 6 6 Set switching points onl...

Страница 27: ...age are on Automatic mode Green LED flashes Switchgear switched on standby mode LED lights up Automatic mode switched on LED off Pump deactivated only Control MS L2 Pump operation Green LED flashes Pu...

Страница 28: ...for the collective fault signal SSM and the high water alarm Alarm is activated The LEDs display an alarm signal when there is a fault Additionally the internal buzzer can emit an audible alarm signal...

Страница 29: ...ransmitters within potentially explosive atmo spheres DANGER Risk of explosion if signal transmitters are installed in poten tially explosive areas The switchgear does not have an intrinsically safe c...

Страница 30: ...on charge the rechargeable battery prior to inser tion or charge it for 24 h in the switchgear The capacity of the rechargeable battery will fall if the ambient temperature drops The alarm running tim...

Страница 31: ...fications Electrical work A qualified electrician must carry out the electrical work Installation dismantling The technician must be trained in the use of the necessary tools and fixation materials fo...

Страница 32: ...nd remove the switchgear from the struc ture Switchgear removed Observe the following for storage 10 Maintenance and repair DANGER Risk of fatal injury due to electrical current Improper conduct when...

Страница 33: ...larm signal 11 3 Fault acknowledgement Press the Buzzer off reset button to deactivate the alarm and the collective fault sig nal Press the Buzzer off reset button for at least 1 s to acknowledge a fa...

Страница 34: ...ayed beneath the graphic Hg mercury Pb lead Cd cadmium 12 2 Information on the collection of used electrical and electronic products Proper disposal and appropriate recycling of this product prevents...

Страница 35: ...instructions for the connected pumps and signal transmitters 1 230 V 2 pole direct starting Power in kW System impedance in ohm Connections h 1 5 0 4180 6 1 5 0 3020 24 1 5 0 2720 30 2 2 0 2790 6 2 2...

Страница 36: ......

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ...Pioneering for You Local contact at www wilo com contact WILO SE Wilopark 1 44263 Dortmund Germany T 49 0 231 4102 0 T 49 0 231 4102 7363 wilo wilo com www wilo com...

Отзывы: