7
Table 2 SCe-DM Drive Fault Codes
Code
Response
Time
Restart
Faults
Remedies
E001
60s
Immediately
Pump is in overload condition,
defective
Density and/or viscosity of the conveyed
liquid is too high
Pump is obstructed by particles
Dismantle the pump and replace or clean
the defective components
E004
(EO32)
5s
300s
Converter supply experiences
undervoltage
Check the converter terminals:
• Fault if network < 330V
E006
5s
300s
A supply phase is missing
Check the supply
E007
Immediately
Immediately
The converter runs like a gener-
ator. Warning signal, pump is not
stopped
Pump veers, check tightness of the
non-return valve
E010
5s
Immediately
Pump is locked
Dismantle the pump, clean it and replace
defective parts. It may be a mechanical
failure of the motor (bearings)
E011
60s
Immediately
Pump is no longer primed or is
running dry
Prime the pump by filling it. Check the
tightness of the foot valve
E020
5s
Immediately
Motor overheats
Clean the cooling ribs of the motor
Ambient temperature exceeds
more than +50 °C
The motor is not designed for operation
at an ambient temperature of +50 °C
E023
Immediately
Immediately
Motor has short circuit
Dismantle the frequency converter of the
pump, check and replace it, if required
E025
Immediately
Immediately
Missing phase at the motor
Check the connection between motor
and converter
E026
5s
Immediately
The thermal sensor of the motor
is defective or is not correctly
connected
Dismantle the frequency converter of the
pump, check and replace it, if required
E030
E031
5s
Immediately
Converter overheats
Clean the cooling ribs at the rear and un-
der the converter as well as the fan cover
Ambient temperature exceeds
than +50 °C
The converter is not design to operate at
an ambient temperature of +50 °C
E042
5s
Immediately
The sensor cable (4 – 20 mA) is
interrupted
Check the correct supply and the cable
connection of the sensor
E050
300s
Immediately
BMS communication time-out
Check the connection
E070
Immediately
Immediately
Internal communication error
Contact after-sales technician
E071
Immediately
Immediately
EEPROM error
Contact after-sales technician
E072
Immediately
Immediately
Problem inside converter
Contact after-sales technician
E075
Immediately
Immediately
Inrush-current relay defective
Contact after-sales technician
E076
Immediately
Immediately
Current sensor defective
Contact after-sales technician
E099
Immediately
Immediately
Unknown pump type
Contact after-sales technician