6
7 Warranty
WILO reserve the right to inspect an installation
to verify that the equipment has been installed in
accordance with the written instructions. The full
warranty document is downloadable at www.wilo.
co.uk click on local information then downloads.
Before requesting a site visit, the following
information must be available to the service team:
• Article number of the equipment
• A purchase order to cover the work in the event
that no manufacturing defect is found.
• A site contact name and number
• A FULL description of the alleged fault
Table 1 SCe Panel Fault Codes (EM & DM)
8) Tables
Code
Fault description
Causes
Remedies
E040
Output pressure sensor
faulty
Pressure sensor defective
Replace sensor
Supply pressure sensor
faulty
No electrical connection to the
sensor
Repair the electrical connection
E054
Connection partner lost
Fault in the CAN connection
between the switchgear and
pumps
Check cable connection
Check activation of the termi-
nating resistors
E060
Maximum pressure
exceeded
The output pressure of the sys-
tem has risen above the value
set in the controller
Check controller function
(Menu 5.4.1.0) Check instal-
lation
E060
Maximum pressure
exceeded
The output pressure of the sys-
tem has risen above the value
set in the controller
Check controller function
(Menu 5.4.1.0) Check instal-
lation
E061
Pressure below mini-
mum value
The output pressure of the
system has dropped below the
value set in menu 5.4.2.0 (e.g.
due to a pipe burst)
Check the default value
corresponds to local condi-
tions. Check pipe and repair if
necessary
E062
Low water
Protection against low water
level triggered
Check inlet/break tank; pumps
restart automatically
Содержание 29992313