6 Commissioning

6.1 Commissioning 

It is recommended that the first installation is 

commissioned by Wilo customer service. Contact 

us on [email protected] or Ph: 012835230000
Before switching on for the first time check 

the customers wiring is compliant with local 

regulations and is fit for purpose. 
Check the pipe connections are stress free
Fill the storage tank and visually check for leaks
Close discharge valve and turn power on
Run pump against closed valve until pump 

switches off. This may require the adjustment of 

the pressure switch
Open system valve partially and allow unit to fill 

the system and switch off.
Ensure storage tank fill is adequate for the 

system, Do not allow pump to run dry, this may 

cause damage to the mechanical seal and other 

components.
Once system is filled fully open the system valve.

DANGER! Risk of fatal injury! Tighten all 

connection terminals prior to commissioning!

6.2 Maintenance

To ensure maximum reliability in operation we 

recommend that the expansion vessel is checked 

at least annually. This may require more frequent 

checks if the unit is subject to higher frequencies 

of use. 
Checks should be made on condition of stored 

water tank and must be debris free.
Checks should be made on switching frequencies 

and operation.
The general safety instructions must be observed 

when carrying out any remedial work. Please 

follow the Installation and Operation manual for 

pump and control u

nit.

ATTENTION! Any maintenance must be 

completed by a trained and competent person. 

Any damage to the booster could void warranty 

if this is not adhered to

7 Warranty

WILO reserve the right to inspect an installation 

to verify that the equipment has been installed in 

accordance with the written instructions. The full 

warranty document is downloadable at www.wilo.

com/gb/en/downloads. Click on local information 

then downloads. Before requesting a site visit, the 

following information must be available to the 

service team:
• Article number of the equipment
• A purchase order to cover the work in the event 

that no manufacturing defect is found.
• A site contact name and number
• A FULL description of the alleged fault

Содержание 2819142

Страница 1: ...819146 CAT5 1MHI206 PS EM 29992804 CAT5 1MHI206 EC EM 2 2819147 CAT5 1MHI402 PS EM 29992805 CAT5 1MHI402 EC EM 2 2819148 CAT5 1MHI403 PS EM 29992806 CAT5 1MHI403 EC EM 2 2819149 CAT5 1MHI404 PS EM 299...

Страница 2: ...s 4 4 4 2 Operating Features 4 5 Installation 5 1 Hydraulic Connections 4 5 2 Electrical Connections 4 6 Commissioning 6 1 Commissioning 5 6 2 Maintenance 5 7 Warranty 5 8 Figures Fig 1 MHI PS EM Elec...

Страница 3: ...ifficulty is mentioned 2 2 Modification and Spare Parts Modifications to the booster are prohibited and will invalidate the warranty Wilo Approved spares must be used at all times For information on s...

Страница 4: ...set level to stop air from entering the pump Programmable electronic menu with alarm log and run timer Table 2 4 4 MHIE EM Single Phase Variable Speed 4 4 1 Operating Mode MHIE EM is a variable speed...

Страница 5: ...recommend that the expansion vessel is checked at least annually This may require more frequent checks if the unit is subject to higher frequencies of use Checks should be made on condition of stored...

Страница 6: ...6 Fig 1 MHI PS EM Electrical Connections Fig 2 MHIE DM Electrical Connections 8 Figures...

Страница 7: ...7 Fig 3 MHI EC EM Fig 4 MHIE EM Electrical Connections...

Страница 8: ...8 Fig 5 General Arrangement Hydraulic Fig 6 PS EM Layout...

Страница 9: ...9 Fig 7 MHIE EM DM Layout Fig 8 MHIE EM Controls...

Страница 10: ...10 Manual Mode Inverter On Green LED Automatic Mode Alarm Red LED Menu Pump Running Yellow LED Enter Pump in Automatic Mode Green LED Table 1 Driver User Interface EC EM Fig 9 MHI EC EM Layout...

Страница 11: ...ressure before the pumps start 0 3 Bar Time Before Stop Time the pumps will run once the pressure has been reached at no flow 15 Sec MENU HISTORIC Running Time Total pump running hours Hrs Pump Cycles...

Страница 12: ...technical service depart ment E031 OVER T If the temperature is too high the controller will stop the motor from running Check that the water temperature does not exceed 40 C Check that the ambient te...

Страница 13: ...1 230 4024288 MHi205 1 E 1 230 4024290 MHi206 1 E 1 230 4024292 MHi402 1 E 1 230 4024294 MHi403 1 E 1 230 4024296 MHi404 1 E 1 230 4024298 MHi405 1 E 1 230 4024300 MHi406 1 E 1 230 4148406 MHIE205N 1...

Страница 14: ...2 Pumps 4024283 MHi202 1 E 3 4024285 MHi203 1 E 3 4024287 MHi204 1 E 3 4210718 MHi205 1 E 3 4210722 MHi206 1 E 3 4024293 MHi402 1 E 3 4024295 MHi403 1 E 3 4210725 MHi404 1 E 3 4210732 MHi405 1 E 3 421...

Страница 15: ...Electromagnetic Compatibility Directive WEEE Directive ROHS Directive As well as following harmonized standards If the above mentioned series are technically modified without our approval this declar...

Страница 16: ......

Отзывы: