Part Number 550-142-785/0812 

  

GWI

 Series 2 

Gas-Fired Water Boilers – 

Boiler Manual

❏ 

Boiler and heat distribution units filled with water?

❏ 

Automatic air vent, if used, open one full turn?

❏ 

Air purged from system?

❏ 

Air purged from gas piping? Piping checked for leaks?

❏ 

Correctly-sized  manifold  orifices  installed?  See 

Table 3, 

page 6

 to check size and fuel type.

  Correctly  sized  manifold  orifices  must  be  used. 

Failure to do so will cause severe personal injury, 
death or substantial property damage.

❏ 

Followed “Operating instructions” on boiler or in manual, 

page 

26

 for proper start-up?

❏ 

Proper burner flame observed? See “Verify operation”, manual 

Section 7.

❏ 

Test temperature limit — While burners are operating, turn 

Boiler Temp adjustment knob counterclockwise until display 

reading is below actual boiler water temperature. Burners 

should  go  off  while  circulator  continues  to  operate. Turn 

Boiler Temp adjustment knob clockwise until display read

-

ing is above boiler water temperature and ignition sequence 

should resume.

❏ 

Test additional field-installed controls — If boiler has a low 

water  cutoff,  additional  high  limit  or  other  controls,  test  for 

operation  as  outlined  by  manufacturer.  Burners  should  be 

operating and should go off when controls are tested. When 

controls are restored, burners should reignite.

❏ 

Test ignition system safety device:
a.  Connect manometer to outlet side of gas valve. Start boiler, 

allowing for normal start-up cycle to occur and main burn

-

ers to ignite. With main burners on, manually shut off gas 

supply at manual main shutoff gas valve. Burners should 

go off. Open manual main shutoff gas valve. Manometer 

should confirm there is no gas flow. Pilot will relight, flame 
sensing element will sense pilot flame and main burners 
reignite.

❏ 

Set limit control(s) to system temperature requirements. Adjust 

balancing valves and controls to provide design temperature 
to system.

 

Set Economy mode, fully clockwise.

❏ 

For multiple zones, adjust flow so it is about the same in each zone.

❏ 

Verify thermostat heat anticipator (if available) set properly? 

See wiring diagram label on boiler or in manual, page 24 and 
25
.

❏ 

Cycle boiler with thermostat — Raise to highest setting and 

verify  boiler  goes  through  normal  start-up  cycle.  Lower  to 

lowest setting and verify boiler goes off.

 

Cycle DHW Aquastat if used.

❏ 

Measure natural gas input:

a.  Operate boiler 10 minutes.

b.  Turn off other appliances.
c.  At natural gas meter, measure time (in seconds) required 

to use one cubic foot of gas.

d.  Calculate gas input:

 

3600 x 1000

number of seconds from step

c

=   Btuh

e.  Btuh calculated should approximate input rating on boiler 

8  Checkout procedure

Check burner flame — Pilot burner

Proper pilot flame (see 

Figure 16

):

1.  Blue flame.

2.  Inner cone engulfing  pilot flame sensor.

3.  Pilot flame sensor glowing cherry red.

Improper pilot flame:

1.  Overfired  —  Large  flame  lifting  or  blowing  past  pilot  flame 

sensor.

2.  Underfired — Small flame. Inner cone not engulfing pilot flame 

sensor.

3.  Lack of primary air — Yellow flame tip.

Figure 17  Typical main burner flame

Verify operation

Figure 16  Typical pilot burner flame

4.  Incorrectly heated pilot flame sensor.

Check burner flames — Main burner

Proper main burner flame (see 

Figure 17

):

1.  Yellow-orange streaks may appear (caused by dust).

Improper main burner flame:

1.  Overfired — Large flames.
2.  Underfired — Small flames.
3.  Lack of primary air — Yellow tipping on flames (sooting will 

occur).

7 Start-up 

continued

Содержание GWI-047

Страница 1: ...lation when determining boiler location Any claims for damage or shortage in shipment must be filed immediately against the transporta tion company by the consignee USER Please read the following Fail...

Страница 2: ...erheating occur or gas supply fail to shut off do not turn off or disconnect electrical supply to circulator Instead shut off the gas supply at a location external to the appliance 5 Do not use this b...

Страница 3: ...imum clearance to combustible materials 1 Hot water pipes must be at least from combustible material 2 Single wall vent pipe must be at least 2 inches from combus tible material 3 Type B double wall m...

Страница 4: ...isted vent cap must extend at least 3 feet above the highest point where it passes through a roof of a building and at least 2 feet higher than any portion of a building within a horizontal distance o...

Страница 5: ...e personal injury or death check for products or areas listed below before installing boiler If any of these contaminants are found remove contaminants permanently OR isolate boiler and provide outsid...

Страница 6: ...ed air dampers If the air openings are fitted with motorized dampers electrically interlock the damper to Prevent the boiler from firing if the damper is not fully open Shut the boiler down should the...

Страница 7: ...at once Failure to do so can damage boiler resulting in substantial property damage Do not use petroleum based cleaning or sealing compounds in boiler system Severe damage to boiler will occur resulti...

Страница 8: ...tallation Code 2 To prevent downdrafts chimney should extend at least 3 feet above the highest point where it passes through a roof and at least 2 feet higher than any portion of a building within a h...

Страница 9: ...elbows Do not exceed data in Table 4 4 Select vent components from separate GWI Vent Component Supplement All components including the vent starter must be of the same vent manufacturer Do not mix co...

Страница 10: ...149 1 or B149 2 Installation Code Terminate vent no less than 6 feet from another com bustion air inlet 3 feet from any other building opening and 3 feet from any gas service regulator 13 See Figures...

Страница 11: ...integral screen Elbow and termination coupling with screen not available for StaR 34 6 Do not seal vent pipe slip connector for Saf T Vent to inside or outside plate 7 If passing through noncombustibl...

Страница 12: ...ual Using any termination other than one of those shown could cause nuisance outages and loss of heat resulting in substantial property damage Direct exhaust venting continued Figure 8 Sidewall vent t...

Страница 13: ...ould result in failure of the relief valve to operate result ing in possibility of severe personal injury death or substantial property damage Test the operation of the valve after filling and pres su...

Страница 14: ...tallation and Piping Guides If boiler is connected to heating coils located in air handling units where they can be exposed to refrigerated air use flow control valves or other au tomatic means to pre...

Страница 15: ...nough to allow temperatures to level off It takes a while for the boiler water temperature to rise as the flow changes 3 Bypass valve 2 allows hot boiler outlet water to blend with colder return water...

Страница 16: ...ath or substantial property damage 5 Use pipe dope compatible with propane gases Apply sparingly only to male threads of pipe joints so that pipe dope does not block gas flow 5 Install gas piping Fail...

Страница 17: ...ments of equipment con nected to it If connected directly to boiler seeWiring diagrams 6 Field wiring page 24 and 25 for anticipator setting For other devices see manufacturer s specifications Wiring...

Страница 18: ...rop Added water will dilute the antifreeze reducing the freeze protection level Preparation Fill the system with water 1 Close manual and automatic air vents and boiler drain cock 2 Fill to correct sy...

Страница 19: ...gy by reducing the boiler water temperature as the heating load decreases This feature is equipped with an override which is provided primarily to permit the use of an external energy management syste...

Страница 20: ...ff gas valve Manometer should confirm there is no gas flow Pilot will relight flame sensing element will sense pilot flame and main burners reignite Set limit control s to system temperature requireme...

Страница 21: ...ADJUST In the MIN position the time delay is zero and the IMPORTANT notice below must be observed IMPORTANT In accordance with Section 325 f 3 of the Energy Policy and Conservation Act this boiler is...

Страница 22: ...es light and control module senses flame cur rent spark generator is turned off and main valve opens c Natural Gas If pilot does not light within 15 seconds pilot valve is closed and spark generator i...

Страница 23: ...23 Part Number 550 142 785 0812 GWI Series 2 Gas Fired Water Boilers Boiler Manual Figure 18 Control module sequence of operation status light indications 9a Sequence of operation...

Страница 24: ...24 Part Number 550 142 785 0812 GWI Series 2 Gas Fired Water Boilers Boiler Manual 9a Sequence of operation continued Figure 19 Schematic wiring diagram...

Страница 25: ...25 Part Number 550 142 785 0812 GWI Series 2 Gas Fired Water Boilers Boiler Manual Figure 20 Ladder wiring diagram 9a Sequence of operation continued...

Страница 26: ...upplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire depart ment What to do if you smell gas 1 Stop Read the safety information ab...

Страница 27: ...e could result in severe personal injury death or substantial property damage Service technician see following pages for instructions Owner maintenance see User s Information Manual for instructions A...

Страница 28: ...Severe damage to boiler will occur resulting in substantial property damage Eliminate all system or boiler leaks Continual fresh makeup water will reduce boiler life Minerals can build up in sections...

Страница 29: ...valve seat 4 Replace cap by twisting all the way onto valve and then un screwing one turn Limit controls and cutoffs 1 Inspect and test the boiler limit control Verify operation by turn ing control se...

Страница 30: ...ning label Before operating any relief valve ensure that it is piped with its discharge in a safe area to avoid severe scald potential Read manual Section 4 page 13 before proceeding further Safety re...

Страница 31: ...check pressure switch setting if specified in Troubleshooting charts Make sure boiler water temperature is 100 F or cooler before starting procedure to obtain appropri ate readings 1 See Figure 21 an...

Страница 32: ...d 20 seconds OR ignition control will automatically restart sequence of operation after 1 hour waiting period INDICATOR LIGHT CONDITION POWER TSTAT CIRC High voltage detected on TSTAT circuit POWER PU...

Страница 33: ...33 Part Number 550 142 785 0812 GWI Series 2 Gas Fired Water Boilers Boiler Manual Figure 23 Control module connections 12 Troubleshooting components continued...

Страница 34: ...4 PURGE light flashing FLAME light flashing For insufficient heat or no heat problem go to Chart 7 if POWER light is on steady with no other light flashing No Yes On steady not flashing No Yes Usuall...

Страница 35: ...the boiler thermostat leads two black low voltage leads in J box Connect a voltmeter across these two incoming wires Close each thermostat zone valve and relay in the external circuit one at a time an...

Страница 36: ...lace if necessary Retest Try reseating plug in module receptacle and restart If inducer still does not work replace inducer assembly Retest No Yes Wait 45 seconds Does inducer motor operate No Yes Rem...

Страница 37: ...ower to boiler Restart boiler following Operating instructions in this manual Section 10 Do FLAME and POWER lights still flash Boiler should now operate normally Original flashing FLAME light caused b...

Страница 38: ...e ohmmeter indicate the switch is closed Inspect and check wire harness from control module to pressure switch Reseat connector in control module receptacle If harness is intact and properly seated bu...

Страница 39: ...vice switch or breaker Check flame signal Detach sense lead from ignition control Figure 23 item 8 page 33 Connect negative lead of MICROAMMETER to control sense terminal Figure 23 item 8 page 33 Conn...

Страница 40: ...normal sequence of operation Figure 18 page 23 If you have less than sufficient heat Is vent piping free of blockage No Yes Correct conditions and recheck operation See Figure 30 page 38 for normal s...

Страница 41: ...t 460 003 700WT 2 Collector hood and transition assembly GWI 047 GWI 063 GWI 095 GWI 127 GWI 158 GWI 190 381 354 581WT 381 354 582WT 381 354 583WT 381 354 584WT 381 354 585WT 381 354 586WT 3 Temperatu...

Страница 42: ...ss tie assembly in Base assembly 4 Access panel in Base assembly 5 Base pan angle left side in Base assembly 6 Base pan angle right side in Base assembly 7 Base pan in Base assembly 8 Burner rest in B...

Страница 43: ...embly 13 Replacement parts continued The boiler contains ceramic fiber and fiberglass materials Use care when handling these materials per instructions on page 48 of this manual Failure to comply coul...

Страница 44: ...10 408 05 335 511 546 924WT 2 Combination pressure temperature gauge with 2 short shank Ametek ENFM PTA 1088 4104 510 218 099WT 3 Drain valve Fittings shown are included with boiler Conbraco Hammond V...

Страница 45: ...355WT 3 Natural gas Pilot assembly kit with orifice and aluminum pilot gas tubing All 511 330 166WT 3 Propane gas Pilot assembly kit with orifice and aluminum pilot gas tubing All 511 330 211WT 4 Cont...

Страница 46: ...nsions Boiler model number Supply tapping inches NPT Return tapping inches NPT Gas connection size Note 3 inches NPT Gas manifold size Note 3 inches NPT W Jacket width inches GWI 047 1 10 GWI 063 1 1...

Страница 47: ...pplica tions Install GWI boilers for residential radiant panel systems converted gravity heating systems or other low water temperature applications per instruc tions in this manual to avoid damage du...

Страница 48: ...it in a plastic bag for disposal Wash potentially contaminated clothes separately from other clothing Rinse clothes washer thoroughly NIOSH stated First Aid Eye Irrigate immediately Breathing Fresh a...

Отзывы: