background image

GSA

 

Gas-Fired Steam Boilers – 

User’s Information Manual

6

Part Number 550-110-739/0703

Maintenance procedures

The boiler should be inspected and started annually,
at the beginning of the heating season, only by a

qualified service technician. In addition, the maintenance and care
of the boiler designated on page 3 and explained on the following
pages must be performed to assure maximum boiler efficiency and
reliability. Failure to service and maintain the boiler and system could
result in equipment failure, causing possible severe personal injury,
death or substantial property damage.

The following information provides detailed
instructions for completing the maintenance items

listed in “Maintain your boiler using this schedule” on page 3. In
addition to this maintenance, the boiler must be serviced and started
up at the beginning of each heating season by a qualified service
technician.
See page 8 for “Troubleshooting” procedures for common problems.

Component information

Do not attempt to place
boiler in operation if spill

switch cuts off gas flow. Immediately call a
service technician. Failure to do so can
cause severe personal injury, death or
substantial property damage.

Spill switch

The Spill switch is attached to the draft
diverter. It cuts off gas flow if the vent
system becomes blocked.

Rollout thermal fuse element

The Rollout TFE is located above the
burners. It cuts off gas flow should flame
rollout occur.

Do not attempt to place
boiler in operation if rollout

thermal fuse element cuts off gas flow.
Immediately call a service technician. Failure
to do so can cause severe personal injury,
death or substantial property damage.

  Check monthly

Boiler and system piping

1. Visually inspect for leaks around piping, relief valve and other

fittings. Immediately call a qualified service technician to repair
any leaks.

Have leaks fixed at once by a qualified service
technician. Continual fresh makeup water will reduce

boiler life. Minerals can build up in sections, reducing heat transfer,
overheating cast iron, and causing section failure.

Do not use petroleum-based cleaning or sealing
compounds in boiler system. Severe damage to boiler

and system components can occur, resulting in possible severe
personal injury, death or substantial property damage.

Venting system

1. Visually inspect all parts or the flue gas venting system for any

signs of blockage, leakage or joints or deterioration of the piping.

2. Check vent system operation:

a. With boiler firing, hold a candle or match below lower edge

of draft diverter “skirt.” If flame does not blow out, but burns
undisturbed, the vent system is working properly. If flame
blows out or flickers severely, the vent system must be
checked for obstructions or other causes of improper
venting.

b.

Verify the vent damper opens before burners ignite.

3. Notify your qualified service technician at once if you find any

problem.

Failure to inspect the vent system as noted above
and have it repaired by a qualified service

technician can result in vent system failure, causing severe
personal injury or death.

Boiler area

To prevent potential of severe personal injury, death
or substantia

W-T

8201 W. Calumet Rd.

Milwaukee, WI 53223

l property damage, eliminate all materials

discussed below from the boiler vicinity. If found:

Remove products immediately from the area. If they have
been there for an extended period, call a qualified service
technician to inspect the boiler and vent system for possible
damage from acid corrosion.

If products cannot be removed, immediately call a qualified
service technician to install an outside combustion air source
for the boiler (if not already installed).

1. Combustible/flammable materials — Do not store combustible

materials, gasoline or any other flammable vapors or liquids
near the boiler. Remove immediately if found.

2. Air contaminants — See listing of contaminants on page 2.

Pressure gauge

1. Make sure the pressure reading on the boiler pressure gauge

does not exceed 15 psig. Normal operation is usually less than
5 psig. At certain times the system may be under vacuum
conditions.

2. Contact a qualified service technician if problem persists.

Air openings

1. Verify that combustion and ventilation air openings to the boiler

room and/or building are open and unobstructed.

  Check daily

Содержание RVGP

Страница 1: ...e gas odorant Propane boilers only Your propane supplier mixes an odorant with the propane to make its pres ence detectable In some instances the odorant can fade and the gas may no longer have an odo...

Страница 2: ...5 Should overheating occur or gas supply fail to shut off do not turn off or disconnect electrical supply to pump Instead shut off the gas supply at a location external to the appliance 6 DO NOT use t...

Страница 3: ...75 through GSA 250 4 Robertshaw 7200 GSA 075 through GSA 175 5 Service technician covered in Boiler Manual for use only by a qualified service technician Owner maintenance see pages 6 8 for instructio...

Страница 4: ...to the appliance 5 When equipped with Johnson Controls vent damper Model M35 manually rotate damper blade in direction of arrow to Open position indicated on damper assembly 6 Turn gas control knob cl...

Страница 5: ...n to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Stop Read the safety information above on this label 2 Set the thermostat to l...

Страница 6: ...ing section failure Do not use petroleum based cleaning or sealing compounds in boiler system Severe damage to boiler and system components can occur resulting in possible severe personal injury death...

Страница 7: ...g the heating season to verify the valve and discharge piping flow freely If corrosion and or deposits are noticed within the valve body testing must be performed more often A try lever test must also...

Страница 8: ...ant use of makeup water Call qualified service technician to de lime boiler if necessary In some cases deposits will be too heavy to remove with de liming procedures Have qualified service technician...

Отзывы: