Gas-Fired Steam Boilers – 

User’s Information Manual

2

Part Number 550-110-739/0703

Please read this page first

Failure to adhere to the guidelines on this page can result in severe per-
sonal injury, death or substantial property damage.

Air contamination

12. To prevent potential of severe personal injury or death, check

for products or areas listed in table below before installing boiler.
If any of these contaminants are found, do one of  the following:

Remove contaminants permanently.      — 

or —

Isolate boiler and provide outside combustion air. See
applicable codes for further information.

Boiler water

8. DO NOT use petroleum-based cleaning or sealing compounds

in boiler system. Water seal deterioration will occur, causing
leakage between sections and damage to heating system
components. This can result in substantial property damage.

9. DO NOT use "homemade cures" or "boiler patent medicines".

Serious damage to boiler, personnel and/or property may result.

10. Continual fresh makeup water will reduce boiler life. Mineral

buildup in sections reduces heat transfer, overheats cast iron,
and causes section failure. Addition of oxygen and other gases
can cause internal corrosion. Leaks in boiler or piping must be
repaired at once to prevent makeup water.

11. DO NOT add cold water to hot boiler. Thermal shock can cause

sections to crack.

Boiler operation

4. DO NOT block flow of combustion or ventilation air to boiler.

GSA boilers are equipped with controls which will automatically
shut down the boiler should the vent be blocked. Should the
boiler shut down due to blockage, these devices must be reset
or replaced only by a qualified installer/service technician.

5. Should overheating occur or gas supply fail to shut off, do not

turn off or disconnect electrical supply to pump. Instead, shut
off the gas supply at a location external to the appliance.

6. DO NOT use this boiler if any part has been under water.

Immediately call a qualified service technician to inspect the
boiler and to replace any part of the control system and any
gas control that has been under water.

7. Have the building monitored when it is vacant for an extended

period. Safety controls can shut down the boiler at any time.
The loss of heat can result in significant damage due to freezing.

Service and maintenance

1. To avoid electric shock, disconnect electrical supply before

performing maintenance.

2. To avoid severe burns, allow boiler to cool before performing

maintenance.

3. You must maintain the boiler as outlined in the manual and have

the boiler started up and serviced at least annually by a qualified
service technician to ensure boiler/system reliability.

Products to avoid

Spray cans containing chloro/fluorocarbons

Permanent wave solutions

Chlorinated waxes/cleaners

Chlorine-based swimming pool chemicals

Calcium chloride used for thawing

Sodium chloride used for water softening

Refrigerant leaks

Paint or varnish removers

Hydrochloric acid/muriatic acid

Cements and glues

Antistatic fabric softeners used in clothes dryers

Chlorine-type bleaches, detergents, and cleaning solvents found in 
household laundry rooms

Adhesives used to fasten building products and other similar products

Areas likely to have contaminants

Dry cleaning/laundry areas and establishments

Swimming pools

Metal fabrication plants

Beauty shops

Refrigeration repair shops

Photo processing plants

Auto body shops

Plastic manufacturing plants

Furniture refinishing areas and establishments

New building construction

Remodeling areas

Garages with workshops

Содержание RVGP

Страница 1: ...e gas odorant Propane boilers only Your propane supplier mixes an odorant with the propane to make its pres ence detectable In some instances the odorant can fade and the gas may no longer have an odo...

Страница 2: ...5 Should overheating occur or gas supply fail to shut off do not turn off or disconnect electrical supply to pump Instead shut off the gas supply at a location external to the appliance 6 DO NOT use t...

Страница 3: ...75 through GSA 250 4 Robertshaw 7200 GSA 075 through GSA 175 5 Service technician covered in Boiler Manual for use only by a qualified service technician Owner maintenance see pages 6 8 for instructio...

Страница 4: ...to the appliance 5 When equipped with Johnson Controls vent damper Model M35 manually rotate damper blade in direction of arrow to Open position indicated on damper assembly 6 Turn gas control knob cl...

Страница 5: ...n to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Stop Read the safety information above on this label 2 Set the thermostat to l...

Страница 6: ...ing section failure Do not use petroleum based cleaning or sealing compounds in boiler system Severe damage to boiler and system components can occur resulting in possible severe personal injury death...

Страница 7: ...g the heating season to verify the valve and discharge piping flow freely If corrosion and or deposits are noticed within the valve body testing must be performed more often A try lever test must also...

Страница 8: ...ant use of makeup water Call qualified service technician to de lime boiler if necessary In some cases deposits will be too heavy to remove with de liming procedures Have qualified service technician...

Отзывы: