background image

5

VENTILATION  AIR

Ventilation  Air  From  Inside Building :
This  fresh  air  would  come  from  an      
adjoining    unconfined    space.    When           
ventilating   to  an  adjoining  unconfined 
space, you  must  provide  two permanent 
openings: one  within  12

  of  the  ceiling 

and  one  within  12

  of  the  floor  on  the 

wall  connecting  the  two  spaces  (see 
options  1  and  2,    Figure    2).  You    can  
also remove  door  into  adjoining  room 
(see option 3, Figure 2). 

Follow  the  Na-

tional  Fuel    Gas    Code    NFPA  54/ANS 
Z223.1. Section  5.3,  Air  for  Combus-
tion  and Ventilation

  for  required size of              

ventilation  grills  or  ducts

 Example:
 Gas  water  heater          40,000        Btu/Hr
 Vent  free  heater    +      10,000        Btu/Hr
 total                         =      50,000       Btu/Hr

 

If  the actual  Btu/Hr  used  is  less  than  the  maximum  Btu/Hr  the  space  can  support, the  space  is  an

unconfined  space. You  will  need  no  additional  fresh  air  ventilation. 

3. Add  the  Btu/Hr of all fuel burning appliances in the space.

     Vent-free heater                                                       Btu/Hr
     Gas water heater*                                                        Btu/Hr
     Gas furnace                                                              Btu/Hr
     Vented gas heater                                                   Btu/Hr
     Gas Fireplace logs                                                   Btu/Hr
     Other gas appliances* +                                          Btu/Hr
    Total                                =                                        Btu/Hr

        *Do    not    include    direct-vent    gas    appliances.  Direct-vent    draws    combustion    air    from    the    outdoors    and       
       vents to the outdoors.
4. Compare  the  maximum  Btu/Hr  the  space  can  support  with  the  actual amount of Btu/Hr used.

                          

Btu/Hr (maximum the space can support)

                         

Btu/Hr (actual amount of Btu/Hr used)

         

Example

 :  46,100 Btu/Hr(maximum the space can support)

                           50,000 Btu/Hr(actual amount of Btu/Hr used)
The  space  in  the  above  example  is  a  confined  space  because  the  actual  Btu/Hr  used  is  more  than  the 
maximum  Btu/Hr  the  space  can  support.
You  must  provide  additional  fresh  air.  Your  options  are  as  follows:
A.  Rework  worksheet, adding  the  space  of  an  adjoining  room. If  the  extra  space  provides  an  unconfined 
space, remove  door  to  adjoining  room  or  add  ventilation  grills   between  rooms. 

See  Ventilation  Air  From 

Inside  Building

, page 5.

B.  Vent  room  directly  to  the  outdoors. See  

Ventilation  Air  From  Outdoors

, page 6.

C.  Install  a  lower  Btu/Hr  heater, if  lower  Btu/Hr  size  makes  room  unconfined.

Figure  2 -Ventilation  Air  from  Inside  Building

AIR  FOR  COMBUSTION  AND  

VENTILATION 

Continued

  WARNING:     

Rework    worksheet, 

adding    the    space    of    the    adjoining  
unconfined  space.  The  combined  spaces  
must   have  enough  fresh air  to supply  all  
appliances  in  both  spaces.

Содержание 2696541

Страница 1: ...qualified installer service agency or gas supplier F I T R I I D S E E C GN D E R Table of Contents Important Safety Information 2 Product Features 3 Proper Ventilation Fresh Air 4 Installation 6 Oper...

Страница 2: ...un heater with control knob at LOW or HIGH locked positions Never set control knob between locked positions Poor combustion and higher levels of carbon monox ide may result 5 This heater needs fresh o...

Страница 3: ...1 Remove heater from carton 2 Remove all protective packaging applied to heater for shipment 3 Check heater for any shipping damage If heater is damaged promptly inform dealer where you bought heater...

Страница 4: ...Length Width Height cu ft volume of space Example Space size18ft length 16ft width 8ft ceiling height 23040cu ft volume of space If additional ventilation to adjoining room is supplied with grills or...

Страница 5: ...Btu Hr Do not include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount...

Страница 6: ...Installing heater next to vinyl or cloth wall cover ings or operating heater where impurities such as tobacco smoke aromatic candles cleaning fluids oil or kerosene lamps etc in the air exist may dis...

Страница 7: ...sert mounting screws through mount ing bracket and into wall studs Attaching to Wall Anchor This method allows you to attach mounting bracket to hollow walls wall areas between studs or to solid walls...

Страница 8: ...aching Mounting Bracket To Wall Note Wall anchors mounting screws and spacers are in hardware package The hardware package is provided with heater Attaching to Wall Stud Method For attaching mounting...

Страница 9: ...o not reduce incoming gas pressure heater regulator damage could occur Install external regulator with the vent pointing down as shown in Figure 12 Pointing the vent down protects it from freezing rai...

Страница 10: ...n main gas valve located on or near gas meter 3 Make sure control knob of heater is in the OFF position 4 Check all joints from equipment shutoff valve to control valve see Figure 15 Apply mixture of...

Страница 11: ...e Release the downward pressure on the knob while continuing to turn until the knob locks at the desired setting position Do not operate between locked positions TO TURN OFF GAS TO APPLIANCE Shutting...

Страница 12: ...re 23 With the unit off lightly blow air through the air inlet hole You may blow through a drinking straw if compressed air is not available Figure 23 Pilot Air Inlet Hole CABINET Air Passageways Use...

Страница 13: ...in 2 Control knob is not pressed in long enough 3 Equipment shutoff valve is not fully open 4 Thermocouple connection is loose at control valve 5 Pilot flame is not touching thermocouple This allows...

Страница 14: ...cked positions 1 Residues from manufacturing processes 1 Metal is expanding while heating or contracting while cooling 1 When heated the vapors from furniture polish wax carpet cleaners etc turn into...

Страница 15: ...any 3 Clean ODS pilot see Cleaning page 12 1 Locate and correct all leak s see Checking Gas Connections page 10 2 Contact Dealer or Williams Furnace 1 Take apart gas tubing and remove foreign matter 2...

Страница 16: ...ed propane LP or natural gas purchase date warranty card Usually we will ask you to return the defective part to the factory PARTS NOT UNDER WARRANTY Contact authorized dealers of this product If they...

Страница 17: ...17 ILLUSTRATED PARTS BREAKDOWN 2696541 ODS Pilot Assembly Burner Assembly...

Страница 18: ...mbly Lower Front Panel Assembly Reflector Unit Burner Assembly ODS Pilot Assembly Thermocouple lgnitor Electrode ODS Mounting Bracket Self Tapping Screw Control Valve Ignitor Line Control Valve Bracke...

Страница 19: ...voids this warranty The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit WHAT IS NOT COVERED This warranty does not apply t...

Отзывы: