background image

 

Operating Your Furnace

 

 

14 

The furnace operates in the following sequence: 

1.  The Thermostat turns on the main burner. 

2. Heat builds up in the furnace and starts the fan (if 

equipped). The heated air comes out the panel louvers. 

3.  When the thermostat setting is reached, it shuts off the 

main burner. 

4.  The fan runs until the heat is removed from the furnace, 

then it turns off. 

Your furnace is equipped with a built-in pressure regulator. L.P. 
gas models also have a regulator at the supply tank. If you 
have a question regarding the amount of fuel consumed, call 
your local gas utility or gas supplier.  

WARNING: 

DO NOT TAMPER WITH THE 

REGULATOR OR BURNER ORIFICES, AS 

PROBLEMS RESULTING FROM THERE MAY 

CAUSE PRODUCT FAILURE NOT COVERED 

BY WARRANTY. 

Input and output ratings shown on the rating plate, located in 
burner compartment, must not be exceeded.  

IMPORTANT: 

KEEP BURNER AND CONTROL 

COMPARTMENT CLEAN. 

 

WARNING: 

Do not store or use gasoline or other 

flammable liquids or vapors near the furnace. 

 

WARNING: 

Danger of bodily injury or death. Do 

not operate the furnace with a broken or missing 

pilot observation door. 

 

 

Lighting the Pilot

FOR YOUR SAFETY, READ BEFORE LIGHTING 

This furnace is equipped with a manually operated piezo spark 
ignition device to ignite the pilot gas. Follow the steps below 
and use the manual spark igniter to light the pilot in place of a 
match. Press spark igniter button repeatedly and vigorously. If 
the spark igniter fails to provide spark to light the pilot, loosen 
the wing nut holding the pilot cover. This opens to the 
combustion chamber. The pilot may be ignited with a match.  

1.  Follow the instructions below and use a match to light the 

pilot as instructed. 

2.  After lighting the pilot, carefully replace the pilot observation 

door and tighten wing nut down. 

On new installations, the gas lines will be filled with air and it 
may take several tries to establish the pilot flame. Check the 
manual shutoff valve in the gas line. It must be in the open 
position (handle parallel to the gas line) before you can light 
your furnace. Your furnace is equipped with a 100% safety 
pilot, which will shut off the gas valve in case the pilot is not 
burning or functioning properly. Make sure the pilot is adjusted 
properly and that the generator connection at the control valve 
is tight. If furnace will not stay lit, call your local gas utility 
company. 

WARNING: 

If you do not follow these 

instructions exactly, a fire or explosion may result 

causing property damage, personal injury or loss 

of life. 

 

A.  This appliance has a pilot which must be lit by hand. When 
lighting the pilot, follow these instructions exactly. 

B. BEFORE LIGHTING smell around the appliance area for 
gas. Be sure to smell next to the floor because some gases are 
heavier than air and will settle on the floor.  

C.  Use only your hand to push in or turn the gas control knob. 
Never use tools. If the knob will not push in or turn by hand, do 
not try to repair it, call a qualified service technician. Force or 
attempted repair may result in a fire or explosion. 

D.  Do not use this appliance if any part has been under water. 
Immediately call a qualified service technician to inspect the 
appliance and to replace any part of the control system and 
any gas control which has been under water. 

WHAT TO DO IF YOU SMELL GAS 

  Do not try to light any appliance. 

  Do not touch any electric switch. Do not use any telephone 

or cell phone in your building.  

  Immediately call your gas supplier from a neighbour’s 

phone. Follow the gas supplier's instructions.  

  If you cannot reach your gas supplier call the fire 

department. 

 

IMPORTANT:

 

KEEP BURNER AND CONTROL 

COMPARTMENT CLEAN.

 

 

 

 

 

Содержание 1403821

Страница 1: ...any open flame Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service...

Страница 2: ...n 4 This warranty does not cover claims which do not involve defective workmanship or materials DUTIES OF THE CONSUMER 1 The heating equipment must be installed by a qualified installer and operated i...

Страница 3: ...our Wall Furnace 6 Thermostat Installation 9 Cabinet Installation 11 Gas Supply and Piping 11 Operating Your Furnace 14 16 Lighting the Pilot 14 Operating Instructions 15 To Turn Off Gas to Appliance...

Страница 4: ...ry and even death 3 Reference is made in this manual regarding gas type as L P G Be advised that L P G is not available in Canada refer to propane L P Gas 18 BEFORE INSTALLING To avoid electrical shoc...

Страница 5: ...adjustable wrenches Keyhole or sabre saw 2 10 inch or 12 inch pipe wrenches Gloves and safety glasses Materials Pipe joint compound resistant to L P gases Caulking compound silicone rubber with a temp...

Страница 6: ...proper operation Interior Clearances Figure 2 14036 Series 1 There must be at least 1 3 16 inches of space between the floor top of floor covering and the bottom of cabinet 2 The top of the furnace m...

Страница 7: ...ide of this stud The inside edge of the next stud should be about 14 1 2 inches from the one found Drive a finishing nail on the inside edge of this stud then another nail on the outside edge FIGURE 2...

Страница 8: ...te Do not trim flue extension or air inlet collar Install Vent Cap Outside place a single strip of mastic provided around the back flange of the vent cap Figure 5 Install the vent cap by inserting it...

Страница 9: ...elected location for the thermostat 5 From the attic feed the thermostat wire or a stiff wire through the wall until even with thermostat location 6 Snag the thermostat wire through the wall so that 6...

Страница 10: ...h any excess wire back through hole in the wall and plug the hole with insulation to prevent drafts from affecting thermostat operation 4 Being sure to level thermostat for the best appearance Fasten...

Страница 11: ...t remove seal until you are ready to connect piping WARNING Danger of property damage bodily injury or death Make sure the furnace is equipped to operate on the type of gas available Models designated...

Страница 12: ...All piping must comply with local codes and ordinances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 whichever applies In Canada CAN C G A B149 Refer to Figure 12 for the general layout of...

Страница 13: ...ceed specified pressures for testing Higher pressures may damage the gas valve and cause over firing which may result in combustion chamber failure Liquefied petroleum gas L P G is heavier than air an...

Страница 14: ...fully replace the pilot observation door and tighten wing nut down On new installations the gas lines will be filled with air and it may take several tries to establish the pilot flame Check the manua...

Страница 15: ...Set the thermostat to its lowest setting 2 If servicing is to be performed turn off all electric power to the appliance 3 Open the control access panel 4 Push in the gas control knob slightly and turn...

Страница 16: ...cubic foot and 34 seconds per cubic foot as determined by step 2 above then Input 1 000 x 3 600 34 106 000 Btu hr This measured input must not be greater than the input indicated on the rating plate...

Страница 17: ...et outer mantle Cleaning Blower If Equipped Turn off electric power supply at the disconnect switch fuse box or service panel before servicing For maximum motor life of the optional blower inspect the...

Страница 18: ...quipment such that only one service switch services both the appliance and the carbon monoxide detector b Have battery back up power c Meet ANSI UL 2034 Standards and comply with NFPA 720 2005 Edition...

Страница 19: ...from binding against the blower casing 5 Plug in the factory supplied three prong grounding plug and cord or see field wiring instructions below Model 2303 1 Set the blower on top of the furnace with...

Страница 20: ...03 20 Note If any of the original wire as supplied with the appliance has to be replaced use only 18 Ga 4 64 insulation 105 C AWM wire or its equivalent 115V 60Hz less than 3 amps Total electrical loa...

Страница 21: ...or Support 8 P128400 Vibration Isolator 2 Required 9 P130700 Blower Wheel 10 6B64 Blower Frame 11 P323335 Plug and Cord Model 2303 Ref Number Part Number Description 1 8A128 Back Plate 2 P101000 Wire...

Страница 22: ...001 P147001 5 Inner Casing 8B62 8B62 6 Air Inlet Gasket P147000 P147000 7 Air Inlet Shield Standard Maximum 9 Thick Wall 6C54 1 6C54 1 8 Vent Cap 9306 9306 9 Air Inlet Collar Standard Maximum 9 Thick...

Страница 23: ...1 6A190 6A190 5 Air Inlet Gasket P147000 P147000 P147000 P147000 6 Air Inlet Collar Standard Maximum 9 Thick Wall 6C51 6C51 6C51 6C51 7 Mounting Spacer Plate 6C66 6C66 6C66 6C66 8 Air Inlet Shield Sta...

Страница 24: ...andard hardware items and may be purchased locally Ref Number Description 2203621 2233621 2253621 2203622 2233622 2253622 3003621 3033621 3053621 3003622 3033622 3053622 1 Burner P147400 P147400 P1474...

Страница 25: ...may be overrated Check for high pressure at the valve See rating plate for specified min max supply pressure Check the burner orifice A Thermostat location Check the thermostat location It should not...

Страница 26: ...pliance Do not touch any electrical switch Do not use any phone or cell phone in your building Extinguish any open flame Immediately call your gas supplier from a neighbor s phone If you cannot reach...

Отзывы: