Williams 1403821 Скачать руководство пользователя страница 16

 

Operating Your Furnace

 

 

16 

 

Type of Gas

 

Manifold Pressure, In W.C.

Natural 4 

L.P. 10 

The rated input will be obtained on 2,500 Btu of propane at 10 
inches manifold pressure with factory-sized orifices. If L.P. Gas 
having a different value is supplied, orifices must be changed 
by a qualified installer before the furnace is operated. 

Check the Manifold Gas Pressure 

A tapped opening is provided in the gas valve to facilitate 
measuring the manifold gas pressure. A “U tube” manometer 
having a scale range from 0 to 12-inches water column should 
be used for this measurement. The manifold pressure must be 
measured with the burner and pilot operating. Any major 
changes in the flow must be made by changing the size of the 
burner orifice. Check with your local gas company for the 
proper orifice size. 

Check the Gas Input (Natural Gas Only) 

Under firing could cause inadequate heat, excessive 
condensation or ignition problems. Over firing could cause 
shooting flame impingement or overheating of the combustion 
chamber. Before starting the natural gas input check, obtain 
the heating valve of the gas (BTU per cubic foot) at standard 
conditions from your local supplier. This factor is used in the 
"Check the Gas lnput" section and procedure. 

To measure the input using the gas meter, proceed as follows: 

1.  Turn off the gas supply to all other appliances except the 

furnace. 

2.  With the furnace operating, time the smallest dial on the 

meter for one complete revolution. If this is a 2 cubic foot 
dial, divide the seconds by 2; if it is a 1 cubic foot dial, use 
the time in seconds as is. (3,600 = Sec. Per Hr.) This gives 
the seconds per cubic foot of gas being delivered to the 
furnace. 

3.  Assuming natural gas with a heating valve of 1,000 Btu per 

cubic foot and 34 seconds per cubic foot as determined by 
step 2 above, then: 
Input: 1,000 x 3,600÷34 = 106,000 Btu/hr. 
This measured input must not be greater than the input 
indicated on the rating plate of the furnace. 

4.  Relight all other appliances turned off in step 1 above. Be 

sure all pilot burners are operating. 

WARNING: 

Natural gas heating valve (Btu per 

cubic foot) can vary significantly; therefore, it is 

the installer's responsibility to see that Btu input 

to the furnace is adjusted properly. Failure to do 

so could cause combustion chamber failure, 

asphyxiation, fire or explosion, resulting in 

damage, bodily injury or death. Refer to the 

Natural Fuel Gas Code (NFPA-54) to be sure the 

furnace is burning fuel at the proper rate. 

Check Pilot Burner 

The pilot flame should surround the generator tip 3/8-inch to 
1/2-inch. Pilot gas may need adjustment depending on the inlet 

pressure. Increase or decrease the pilot flame to obtain proper 
setting.  

 

 

FIGURE 15 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIGURE 16 

 

 

 

 

Burner Flame Characteristics 

Start the furnace and let it operate at least 10 minutes. Open 
the access door to view the burner flame. Limit your 
movements near the furnace a few more minutes before 
making your final observation. The flame may look yellow due 
to dust particles in the room air. The flame should change to a 
nice blue color with firm inner and secondary cones. An 
occasional flash of orange might be seen as dust particles burn 
in the flame. This is normal. No burner adjustment is provided, 
or is necessary. (Figure 16). 

Normal Appearance 

Natural Gas: 
1.  Inner cone- blue color - 1/2 to 3/4-inch above ports. 
2.  Secondary inner cone - light blue - 1 to 2-inches above 

ports. 

3.  Total flame - from blue to nearly invisible - approximately 6-

inches above ports. 

L.P Gas: 
1.  Inner cone - blue color - 1/2 to 3/4-inch above ports. 
2.  Secondary inner cone - light blue - 1 to 2-inches above 

ports. 

3.  Total flame - from blue to nearly invisible - approximately 6-

inches above ports. 

 

 

 

Содержание 1403821

Страница 1: ...any open flame Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service...

Страница 2: ...n 4 This warranty does not cover claims which do not involve defective workmanship or materials DUTIES OF THE CONSUMER 1 The heating equipment must be installed by a qualified installer and operated i...

Страница 3: ...our Wall Furnace 6 Thermostat Installation 9 Cabinet Installation 11 Gas Supply and Piping 11 Operating Your Furnace 14 16 Lighting the Pilot 14 Operating Instructions 15 To Turn Off Gas to Appliance...

Страница 4: ...ry and even death 3 Reference is made in this manual regarding gas type as L P G Be advised that L P G is not available in Canada refer to propane L P Gas 18 BEFORE INSTALLING To avoid electrical shoc...

Страница 5: ...adjustable wrenches Keyhole or sabre saw 2 10 inch or 12 inch pipe wrenches Gloves and safety glasses Materials Pipe joint compound resistant to L P gases Caulking compound silicone rubber with a temp...

Страница 6: ...proper operation Interior Clearances Figure 2 14036 Series 1 There must be at least 1 3 16 inches of space between the floor top of floor covering and the bottom of cabinet 2 The top of the furnace m...

Страница 7: ...ide of this stud The inside edge of the next stud should be about 14 1 2 inches from the one found Drive a finishing nail on the inside edge of this stud then another nail on the outside edge FIGURE 2...

Страница 8: ...te Do not trim flue extension or air inlet collar Install Vent Cap Outside place a single strip of mastic provided around the back flange of the vent cap Figure 5 Install the vent cap by inserting it...

Страница 9: ...elected location for the thermostat 5 From the attic feed the thermostat wire or a stiff wire through the wall until even with thermostat location 6 Snag the thermostat wire through the wall so that 6...

Страница 10: ...h any excess wire back through hole in the wall and plug the hole with insulation to prevent drafts from affecting thermostat operation 4 Being sure to level thermostat for the best appearance Fasten...

Страница 11: ...t remove seal until you are ready to connect piping WARNING Danger of property damage bodily injury or death Make sure the furnace is equipped to operate on the type of gas available Models designated...

Страница 12: ...All piping must comply with local codes and ordinances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 whichever applies In Canada CAN C G A B149 Refer to Figure 12 for the general layout of...

Страница 13: ...ceed specified pressures for testing Higher pressures may damage the gas valve and cause over firing which may result in combustion chamber failure Liquefied petroleum gas L P G is heavier than air an...

Страница 14: ...fully replace the pilot observation door and tighten wing nut down On new installations the gas lines will be filled with air and it may take several tries to establish the pilot flame Check the manua...

Страница 15: ...Set the thermostat to its lowest setting 2 If servicing is to be performed turn off all electric power to the appliance 3 Open the control access panel 4 Push in the gas control knob slightly and turn...

Страница 16: ...cubic foot and 34 seconds per cubic foot as determined by step 2 above then Input 1 000 x 3 600 34 106 000 Btu hr This measured input must not be greater than the input indicated on the rating plate...

Страница 17: ...et outer mantle Cleaning Blower If Equipped Turn off electric power supply at the disconnect switch fuse box or service panel before servicing For maximum motor life of the optional blower inspect the...

Страница 18: ...quipment such that only one service switch services both the appliance and the carbon monoxide detector b Have battery back up power c Meet ANSI UL 2034 Standards and comply with NFPA 720 2005 Edition...

Страница 19: ...from binding against the blower casing 5 Plug in the factory supplied three prong grounding plug and cord or see field wiring instructions below Model 2303 1 Set the blower on top of the furnace with...

Страница 20: ...03 20 Note If any of the original wire as supplied with the appliance has to be replaced use only 18 Ga 4 64 insulation 105 C AWM wire or its equivalent 115V 60Hz less than 3 amps Total electrical loa...

Страница 21: ...or Support 8 P128400 Vibration Isolator 2 Required 9 P130700 Blower Wheel 10 6B64 Blower Frame 11 P323335 Plug and Cord Model 2303 Ref Number Part Number Description 1 8A128 Back Plate 2 P101000 Wire...

Страница 22: ...001 P147001 5 Inner Casing 8B62 8B62 6 Air Inlet Gasket P147000 P147000 7 Air Inlet Shield Standard Maximum 9 Thick Wall 6C54 1 6C54 1 8 Vent Cap 9306 9306 9 Air Inlet Collar Standard Maximum 9 Thick...

Страница 23: ...1 6A190 6A190 5 Air Inlet Gasket P147000 P147000 P147000 P147000 6 Air Inlet Collar Standard Maximum 9 Thick Wall 6C51 6C51 6C51 6C51 7 Mounting Spacer Plate 6C66 6C66 6C66 6C66 8 Air Inlet Shield Sta...

Страница 24: ...andard hardware items and may be purchased locally Ref Number Description 2203621 2233621 2253621 2203622 2233622 2253622 3003621 3033621 3053621 3003622 3033622 3053622 1 Burner P147400 P147400 P1474...

Страница 25: ...may be overrated Check for high pressure at the valve See rating plate for specified min max supply pressure Check the burner orifice A Thermostat location Check the thermostat location It should not...

Страница 26: ...pliance Do not touch any electrical switch Do not use any phone or cell phone in your building Extinguish any open flame Immediately call your gas supplier from a neighbor s phone If you cannot reach...

Отзывы: