EN
14073045.06 10/2020 EN/DE/FR/ES
WIKA operating instructions model TR25 (Ex i)
24
6.4.2 Possible installation methods with the marking II 1/2 Ex ib IIC T6 Ga/Gb or
II 1/2 D Ex ib IIIC T65 °C Da/Db
The probe or thermowell tip protrudes into zone 0. The case or connection head is in zone
1 (zone 21) or zone 2 (zone 22). It is sufficient to use an Ex ib type circuit.
Zone separation is guaranteed if sufficiently tight (IP67) process connections are used.
Examples of suitable process connections include gas-tight standardised industrial
flanges, threaded connections or pipe connections.
The welded parts, process connections, compression fittings, thermowells or cases used
must be designed such that they withstand all influencing variables resulting from the
process, such as temperature, flow forces, pressure, corrosion, vibration and impacts.
Zones 1, 2 or
zones 21, 22
Hazardous area
Non-hazardous area
Thermowell
Thermowell
welded
TWxx
TWxx
Process
connection
Connection head/
Field case
Tx10-B
Tx10-C
Tx10-C
Tx10-D
Tx10-H
Tx10-H
Option:
with built-in
transmitter
e.g. T32
Tx10-A
Process
connection
Compression
fitting
Associated
electrical equipment
Intrinsically
safe supply or
suitable barrier
Intrinsically
safe supply or
suitable barrier
Intrinsically
safe supply or
suitable barrier
Intrinsically
safe supply or
suitable barrier
Tx10-A
Tx10-A
Tx10-A
Zones 0, 1, 2 or
zones 20, 21, 22
6. Information on mounting and operation in hazardous areas
Содержание TR25 (Ex i)
Страница 36: ...EN 14073045 06 10 2020 EN DE FR ES WIKA operating instructions model TR25 Ex i 36 ...
Страница 66: ...DE WIKA Betriebsanleitung Typ TR25 Ex i 66 14073045 06 10 2020 EN DE FR ES ...
Страница 96: ...FR 14073045 06 10 2020 EN DE FR ES WIKA mode d emploi type TR25 Ex i 96 ...
Страница 126: ...14073045 06 10 2020 EN DE FR ES WIKA operating instructions model TR25 Ex i 126 ...
Страница 127: ...14073045 06 10 2020 EN DE FR ES WIKA operating instructions model TR25 Ex i 127 ...