5. Commissioning, operation
■
The assembly of the thermowells or measuring instruments to the vessel/pipeline
should be carried out so that it is permanently technically sealed.
■
Electrostatic discharges of the thermowells or measuring instruments when grounding
the vessel or pipeline should be eliminated.
5.2 Electrical connection values
5.2.1 Electrical data without built-in transmitter or digital display
For group II instruments (potentially explosive gas atmospheres)
3)
, the following maximum
connection values apply:
U
i
= DC 30 V
I
i
= 550 mA
P
i
(at the sensor
1)
) = 1.5 W
For group II instruments (potentially explosive dust atmospheres), the following maximum
connection values apply:
U
i
= DC 30 V
I
i
= 550 mA
P
i
(at the sensor
2)
) = For values, see “Table 2” (column 2), chapter 3.7 “Ex marking”
The internal inductance (L
i
) and capacitance (C
i
) of the TR25 are negligibly small.
Sensor circuit in Ex ia or ib, IIC intrinsic safety ignition protection
Only for connection to intrinsically safe circuits with the following maximum output values
for group II instruments (potentially explosive gas atmospheres):
U
o
= DC 30 V
I
o
= 550 mA
P
o
= 1.5 W
For group II instruments (potentially explosive dust atmospheres), the following maximum
output values apply to their connection to intrinsically safe circuits:
U
o
= DC 30 V
I
o
= 550 mA
P
o
= For values, see “Table 2” (column 2), chapter 3.7 “Ex marking”
1) The permissible power to the sensor depends on the temperature of the medium T
M
, the temperature class
and the thermal resistance R
th
, but shall not be more than 1.5 W.
Calculation examples see chapter 8 “Calculation examples for self-heating of the pipe body at the sensor
2) The permissible power to the sensor depends on the temperature of the medium T
M
, the maximum
permissible surface temperature and the thermal resistance R
th
, but shall not be more than the values
from “Table 2” (column 2), see chapter 3.7 “Ex marking”.
3)
Use in methane atmospheres
Owing to the higher minimum ignition energy of methane, the instruments can also be used where
methane causes a potentially explosive gas atmosphere. The instrument can optionally be marked with IIC
+ CH
4
.
Содержание TR25 (Ex i)
Страница 36: ...EN 14073045 06 10 2020 EN DE FR ES WIKA operating instructions model TR25 Ex i 36 ...
Страница 66: ...DE WIKA Betriebsanleitung Typ TR25 Ex i 66 14073045 06 10 2020 EN DE FR ES ...
Страница 96: ...FR 14073045 06 10 2020 EN DE FR ES WIKA mode d emploi type TR25 Ex i 96 ...
Страница 126: ...14073045 06 10 2020 EN DE FR ES WIKA operating instructions model TR25 Ex i 126 ...
Страница 127: ...14073045 06 10 2020 EN DE FR ES WIKA operating instructions model TR25 Ex i 127 ...