EN
11258421.13 10/2017 EN/DE
WIKA operating instructions model T32.xS
30
10. Notes for mounting and operating in hazardous areas
In hazardous areas, only use temperature transmitters that are approved for those
hazardous areas. The approval is marked on the product label.
When connecting them to other devices or component, observe the connection
requirements regarding explosion protection, such as maximum admissible voltage, power
or load with capacitances (see chapter 10.2 “Specific conditions for safe use”).
The following information is based mainly on the EC type examination certificate,
Certification No. BVS 08 ATEX E 019 X.
9.4.2 Typical connection for safe area
HART
®
communicator
Transmitter
Safe area
Transmitter
Power supply
24 V
11242299.02
USB
FSK modem
Terminal 1-4:
sensor, see
designation
of terminal
connections
If RL is < 250 Ω in the respective electrical
circuit, RL must be increased to at least
250 Ω by connecting external resistances.
RL = Resistance for the HART
®
communication
RL min. 250 Ω, max. 1100 Ω
9. Electrical connections / 10. Notes for mounting and ...
Содержание T32.1S
Страница 38: ...EN 11258421 13 10 2017 EN DE WIKA operating instructions model T32 xS 38 ...
Страница 74: ...DE WIKA Betriebsanleitung Typ T32 xS 74 11258421 13 10 2017 EN DE Anlage 1 Installation drawing CSA FM ...
Страница 75: ...DE WIKA Betriebsanleitung Typ T32 xS 75 11258421 13 10 2017 EN DE Anlage 1 Installation drawing CSA FM ...
Страница 76: ...DE WIKA Betriebsanleitung Typ T32 xS 76 11258421 13 10 2017 EN DE Anlage 1 Installation drawing CSA FM ...
Страница 77: ...DE WIKA Betriebsanleitung Typ T32 xS 77 11258421 13 10 2017 EN DE Anlage 1 Installation drawing CSA FM ...
Страница 78: ...DE WIKA Betriebsanleitung Typ T32 xS 78 11258421 13 10 2017 EN DE Anlage 2 EU Konformitätserklärung ...
Страница 79: ...11258421 13 10 2017 EN DE WIKA operating instructions model T32 xS 79 ...