Operating instructions model OLS-C20
4. Transport, packaging and storage
4.1 Transport
Check the switch for any damage that may have been caused by
transport.
Obvious damage must be reported immediately.
4.2 Packaging and storage
Do not remove packaging until just before mounting.
Permissible conditions at the place of storage:
Storage temperature: 0 ... 70 °C
5. Commissioning, operation
When unpacking the switch, check all components for any external
damage. Prior to installation, a functional check can also be carried out.
For this, the instrument should be connected temporarily and the glass
prism dipped in and out of a glass of liquid to test it.
5.1 Mounting
■
Before installation, it must be ensured that the mounting hole and
the fixing device for the switches in the vessel are correct in size
and dimension.
■
Mount the switch, pressure-sealed, into the process connection.
■
Following installation, the glass tip should have a distance of at
least 10 mm to the opposite wall. This minimum clearance can vary
dependent upon the geometry and surface finish of the wall. Note:
with electropolished pipes, the minimum distance to the opposite
surface must be a minimum of 20 mm.
4. Transport, packaging ... / 5. Commissioning ...
Содержание OLS-C20
Страница 18: ...EN 31076041 03 08 2017 EN DE FR ES 18 Operating instructions model OLS C20...
Страница 33: ...DE Betriebsanleitung Typ OLS C20 31076041 03 08 2017 EN DE FR ES 33 Anlage EG Konformit tserkl rung...
Страница 34: ...DE 31076041 03 08 2017 EN DE FR ES 34 Betriebsanleitung Typ OLS C20...
Страница 49: ...FR 31076041 03 08 2017 EN DE FR ES Mode d emploi type OLS C20 49 Annexe D claration de conformit CE...
Страница 50: ...FR 31076041 03 08 2017 EN DE FR ES 50 Mode d emploi type OLS C20...
Страница 66: ...31076041 03 08 2017 EN DE FR ES 66 Operating instructions model OLS C20...
Страница 67: ...31076041 03 08 2017 EN DE FR ES Operating instructions model OLS C20 67...